Incore Instrumentation Flashcards
How many fixed, incore instrumentation assemblies are there?
61
What does each ICI assembly consist of?
5 self-powered rhodium detectors
1 background detector
1 core exit thermocouple (CET)
1 dry, movable detector calibration tube
How are the ICI assemblies placed on the core?
10, 30, 50, 70, and 90% of active core height
What is the process range of the thermocouples?
200F - 2300F
The CETs and Heated Junction Thermocouples provide direct input into what?
why?
QSPDS
determining an approach to inadequate core cooling during core uncovery
The CET’s are one of the indications used to monitor what in the core by CET subcooling and delta-T between max quadrant CET temperature and T-hot?
natural circulation conditions
What provides power to the incore amplifiers?
PN
Fixed incore detectors provide inputs to the core operating limit supervisory system (COLSS) for what?
calculation of azimuthal tilt
axial peaking factor
local power density
DNB margin.
What are the Neutron detectors?
How do they work?
Self-powered Rhodium detectors
they give off a Beta decay, giving the detector a signal
Where are the CETs physically located?
above the fuel alignment plate in the Rx Coolant outlet plenum
allowing for an accurate measure of the coolant as it exits the fuel
What could bring in the FIXED INCORE AMP SYS TRBL alarm?
Causes for this annunciator include:
* Fixed Incore Amp Trouble
* Incore Amplifier Ch (A-D) Bin Assy In Test