Class 125 VDC Control Power (PK) Flashcards

1
Q

Is PK grounded or ungrounded?

Why?

A

ungrounded with ground detection system

Ungrounded system more reliable because a ground would be required on both the positive and negative bus to significantly degrade the system.

alarm in CR
white light locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How long will the PK batteries maintain full loading?

A

Battery can maintain loads for 2 hours at a minimum temperature of 60 degrees F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does the DG need PK for?

A

control power

field flashing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens to the DG on a loss of PK?

A

can’t start without PK

If running, DG will trip and output breaker will stay closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens to AFA on a loss of PK?

A

trip on overspeed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What SDC isolation valves does PK provide power to?

A

SIC-UV-653
SID-UV-654

through inverter (DC power to AC motor)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the limitation for the PK busses when operating SIC/D-UV-653/654?

A

battery and charger must both be connected to the bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Can the PK indications and controls be isolated from the control room?

A

‘B’ train has the App R disconnect switch

B/D charger also has the App R disconnect

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where does PK get power from?

A

PH

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Can PK control centers be paralleled via the swing charger?

A

No, break before make

mechanical interlock doesnt allow it and you cant connect trains together

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where are the PK Battery Breakers normally operated from?

A

CR

can be done locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What SEIS alarms are available for PK?

A

white light only

battery breaker not closed or inop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

what ventilation fans are provided for the PK Battery rooms?

A

normal and essential fans

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

On a loss of normal cooling to the PK battery rooms, what provides cooling?

A

ESF Switchgear room AHU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When would the ESF Equip. Room AHU be supplying the DC equipment rooms?

A

SIAS or LOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How can you tell if we lost a charger to the PK bus regarding voltage and amperage?

A

voltage closer to 130
battery amps to the right (discharging)

17
Q

Each battery charger designed to restore battery from minimum to normal steady state within how long?

A

12 hours

18
Q

What could bring this alarm in?

A

This annunciator indicates either a loss or problem with a
particular 125 VDC Control Center or Distribution Panel.

Inputs to this alarm include:
* PKA-M41 under voltage, ground or breaker trip
* Battery Charger problems including over or under
voltage, AC supply voltage low, charger failure or
reverse current
* Distribution Panel overload also inputs to the
annunciator

19
Q

What could bring this alarm in?

A

This annunciator indicates either a loss or problem with a
particular 125 VDC Control Center or Distribution Panel.

Inputs to this alarm include:
* PKB-M42 under voltage, ground or breaker trip
* Battery Charger problems including over or under
voltage, AC supply voltage low, charger failure or
reverse current
* Distribution Panel overload also inputs to the
annunciator

20
Q

What could bring this alarm in?

A

This annunciator indicates either a loss or problem with a
particular 125 VDC Control Center or Distribution Panel.

Inputs to this alarm include:
* PKC-M43 under voltage, ground or breaker trip
* Battery Charger problems including over or under
voltage, AC supply voltage low, charger failure or
reverse current
* Distribution Panel overload also inputs to the
annunciator

21
Q

What could bring this alarm in?

A

This annunciator indicates either a loss or problem with a
particular 125 VDC Control Center or Distribution Panel.

Inputs to this alarm include:
* PKD-M44 under voltage, ground or breaker trip
* Battery Charger problems including over or under
voltage, AC supply voltage low, charger failure or
reverse current
* Distribution Panel overload also inputs to the
annunciator