Essential Cooling Water (EW) Flashcards

1
Q

What are the loads EW can carry on a loss of NC?

A

Priority Heat loads:
-RCP coolers (seal cooler, HP cooler, thrust bearing cooler, motor coolers, motor lube oil coolers)
-CEDM coolers
-Norm Chiller
-Nuclear Sample coolers

Non-Priority Heat loads:
-SFP HXs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the design basis maximum temperature that EW will maintain ESF system water to during a LOCA?

A

135*F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will autostart EW pumps?

A

SLAC-CC

SIAS
LOP
AFAS
CSAS

CREFAS
CRVIAS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If EW is isolated from the EC system, which of the two systems is inoperable?

A

EC only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

If EW is isolated from the SDC, which of the two systems is inoperable?

A

Both

EW can’t maintain its acceptable limits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Between what levels does the auto makeup maintain EW Surge Tank level?

A

22” and 26”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the makeup supply options for EW surge Tank?

A

Norm - DW
Class ALT - CT
ALT (never use) - Cooling water holdup tank (CM)
Emergency - Fire Protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What level in the EW Surge Tank will auto close the ‘A’ EW to NC cross-tie valves (EWA-UV-65 and EWA-UV-145)?

A

Lo-Level 17”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the low-level in the EW Surge Tank will isolate makeup? Why?

A

14”

prevent feeding a leak

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the purpose of the RHPCV?

A

prevent stacking

installed at the EW outlet of EC condenser section

closes on low pressure, opens for high pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What auto closes the ‘A’ MOV, EW -> NC cross-tie valves?

What can be overridden?

A

SIAS, Lo Tank level (14”)

SIAS ONLY

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is required to make EW operable again after EW is cross-tied to the SFP-HX?

A

flow balance on EW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly