What is the purpose of the Radioactive Drains system?

A

Collects and transports noncorrosive, radioactive, or potentially radioactive liquid wastes from equipment and floor drains.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which areas have radiactive drains?

A
  • Containment Building
  • Auxiliary Building
  • Fuel Building
  • Radwaste Building
  • Holdup Tank Area
  • Main Steam Support Structure
  • Decontamination and Laundry Facility (Unit 1 only)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What areas does the Radioactive Drain system detect leakage from?

A
  • Reactor Coolant system
  • Refueling Pool
  • ESF Equipment
  • Spent Fuel Pool
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where do the Radioactive drain systems flow?

A

They are pumped to Liquid Radwaste system for processing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which systems does Radioactive Drains receive waste from?

A

RC, SI, CH, PC, HC, HA, HR, HF, DW, SG, FW, AF (aux feedwater), GR (gaseous radwaste), EC, CP (containment purge system), LR (liquid radwaste), SR/RF (solid radwaste and raioactive filter handling system), NC, RL (decontamination system), SE (Ex-core neutron monitoring system)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the purpose of the reactor cavity sump/pump?

A

Collects leakage and condensate from the Reactor Cavity and Excore Instrumentation. 520 gallons would require 2 pumps to be running, 30 gpm per, 100% cap. Vented to containment bldg atmosphere.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the purpose of the Containment East and West Sumps/Pumps?

A

Leakage of water and condensed liquid from steam in containment are collected and routed to the Containment East/West Radwaste Sumps.
390 gal, 1 pump per, 100% cap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What does the west sump receive effluent from?

A
  • floor drains
  • equipment drains
  • Refueling Pool
  • Refueling Pool liner plate leak detector compartment.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does the east sump receive effluent from?

A
  • One is a 4-inch stainless steel penetration receiving effluent from
    o floor Drains
    o equipment Drains
    o Refueling Pool
  • The Second Is A 2-1/2 Inch Stainless Steel Penetration Receiving Effluent from the Reactor Cavity Sump Pumps.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does Tech Spec 3.4.16 state?

A

Both of the following RCS leakage detection instrumentation shall be OPERABLE:
a. One Containment Sump monitor
b. One Containment atmosphere radioactivity monitor (gaseous and particulate).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where do containment radwaste sump pumps send water?

A

Liquid Radwaste TDS (total dissolved solids) Holdup Tanks.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What does the AO take rounds on daily for the Containment Sump?

A

Sump run time.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the purpose of the ESF Sumps?

A

Drainage system for the rooms containing redundant ESF equipment , utilize independent drain trains (train A and train B), so that flooding of the redundant ESF rooms of one train will not jeopardize the operation of the remaining train of redundant ESF equipment.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How many separate penetrations does each train specific and separate sump have?

A

5 penetrations
Shutdown Cooling HX room
Containment Spray Pump room
HPSI Room
LPSI Room
Pipe Chase area room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the purpose of the ESF pumps?

A

Transfer the ESF Sump contents to the Liquid Radwaste TDS Holdup Tanks.
100% cap, 50gpm, lubricated by demineralized water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the purpose of Non-ESF Sump?

A

For the Non-ESF equipment which empties into a separate sump in the Auxiliary building and vents to auxiliary exhaust.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the purpose of the Non-ESF Sump Pumps?

A

Pump the sump contents to the Liquid Radwaste TDS Holdup Tanks, lubricated by DW, 100% cap, 50 gpm, vents to the aux bldg atmosphere

18
Q

What is the purpose of the Radwaste Building Sump?

A

Collects leakage from equipment and drainage from floor drains in the Radwaste Building. 920 gal, vented to radwaste build hvac.

19
Q

Where does oil from charging pump collect in the radwaste building?

A

A Charging pump oil drain tank. When tank is full it gets pumped to a 55gal drum.

20
Q

What is the purpose of the Radwaste Building Sump Pumps?

A

Pump their sump contents to the Liquid Radwaste TDS Holdup Tanks. 100% cap, 50 gpm, lubricated by DW

21
Q

What is the purpose of the Fuel Building Sump?

A

Collects leakage from equipment and drainage from floor drains in the Fuel Building. 1700 gallons, vented to fuel bldg hvac

22
Q

How many penetrations does the Fuel Building Sump have?

A

4 penetrations
Floor & equipment drains in Fuel Bldg
Cask decontamination pit.
Fuel pool liner plate leak detector compartment.
Cask pit

23
Q

What is the purpose of the fuel building sump pumps?

A

Pump their sump contents to the Liquid Radwaste TDS Holdup Tanks. 100% cap, 100 gpm,

24
Q

What is the purpose of the Holdup Tank Area Sump?

A

Collects overflow and drainage from equipment and tanks in the RCA Yard. 1660 gal, vented to atmosphere

25
Q

How many penetrations does the Hold up tank area sump have?

A

2 Penetrations
* A 6-inch pipe from the:
o Reactor Makeup Water Tank
o CVCS Holdup Pump Room
o Refueling Water Tank overflows
* A 3-inch from the CVCS HUT overflow.

26
Q

What is the purpose of the Holdup Tank Sump Pumps?

A

Pump their sump contents to the Liquid Radwaste TDS Holdup Tanks. 100% cap, 150 gpm, lubricated by DW

27
Q

What is the purpose of the Decontamination and Laundry Facility Sump?

A

Collects drainage from equipment and floor drains in the Decontamination and Laundry Facility.790 gal, only in Unit 1

28
Q

What is the purpose of the Decontamination and Laundry Facility Sump Pumps?

A

Pump their sump contents to the Liquid Radwaste Chemical Drain Tanks. 100% cap, 50 gpm, lubricated by DW

29
Q

What are the controls for the Radioactive Drains system Sump Pumps?

A

(STOP/AUTO/START) handswitch
In Auto- alternator switches between pumps to equalize run times. Pump starts on Hi level, stops on a Lo level.
LSHH will start standby pump. Hi-Hi sumps will alarm B07 in CR. Lo-Lo level will trip pump.

30
Q

How will the loss of Radioactive Drain system impact the plant?

A

Would have a long term affect on the plant. If no pumps, the sumps would eventually overflow =radioactive spill. If the level got high enough it could cause a loss of safety equipment.

31
Q

What is the purpose of the Special Process Heat Tracing System (QM)?

A

Maintains given temps associated with special processes. (in pipes, tanks, and pumps)

32
Q

Which systems use Special Process Heat Tracing?

A
  • Boric Acid Batching Tank
  • Reactor Makeup Water Tank piping
  • Holdup Tank piping
  • Refueling Water Tank piping
  • RU-141(Condenser Vacuum/Gland seal Exhaust(/143(Plant Vent) piping
  • Hydrogen Analyzer System
  • Solid Radwaste System
  • Liquid Radwaste System Evaporator
  • Boric Acid Concentrator
33
Q

What is the purpose of the step down transformers?

A

Supplies power to a control panel by stepping down the voltage from a 480 VAC MCC power supply to 120 VAC

34
Q

What is the purpose of the control panels?

A
  • Cntrl& distrb heater element power
  • Monitor and display the temperature
  • Monitor continuity and power supply.
  • Annunciate and indicate alarms.
  • Integrate alarms for 1 CR alarm.
  • Wall mounted w/ doors. All line temps, alarm lights, and indications are visible from outside the panel. The panel& controllers are on the front.
35
Q

What is the purpose of the heater elements?

A

Heat the required physical subsystems, installed along pipes, under the insulation, etc. For use < 200°. For >200°F mineral insulationis useed

36
Q

What is the purpose of the heater elements?

A

Heat the required physical subsystems, installed along pipes, under the insulation, etc. For use < 200°. For >200°F mineral insulation is used

37
Q

What is the NORMAL operation of the Special Process Heat Tracing system?

A

RTD sends input signal to controller > line temp displayed> and compared to set temp > heater element turns on/off to regulate w/i +/-2.5°F

38
Q

What is the power source for Heaters for outdoor Q-class piping?

A

NH

39
Q

What is the power supply for Heat tracing for the hydrogen analyzer?

A

Class 1E MCC (PH)

40
Q

How does a loss of the Special Process Heat Tracing system impact the operation of the plant?

A

If the hydrogen monitor heat tracing becomes nonfunctional, entry into TRM 3.3.105 Condition A is required.