Mode 5 to Mode 3 Flashcards

1
Q

What is the Max Press/Temp Limit for CS during SDC Operations?

A

RCS Pressure shall be <250 PSIA and Temp <200F when CS is aligned to SDC (preclude pump damage)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the temperature requirements and bases for initiating/securing SDC?

A

Initiation: Tcold <350F, <300F for LPSI seals, <180F for Max seal life long term, <135F when more than 4 days

Securing: During HU, stop SDC before >300F prevent thermal bind of LTOPs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How do we increase purification flowrate thru the Letdown line?

A
  1. Adjust PIC-201 LD BP Controller for desired flow
  2. For Increase: Raise DP across system by throttline A/B train SDC valves

NOTE: LD Flow limited to 150 GPM (resin damage)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is SDC flow throttled, and how low can it go?

A
  1. Close down on 1 Injection Valve 1st until fully closed, then close 2nd (minimize cavitation)
  2. M5 - SDC Flow as low as 3780 GPM. M4 - >210F, Min Flow >4000 GPM
  3. > 230F = SDC secured
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When is a Charging Pump Non-Functional during pulsation dampener adjustment operations?

A

When put in Pull to Lock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is Max RCS Temperature before O2 concentration must be within TRM Limits?

A

Prior to 250F (TLCO 3.4.101)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the Vent flowpath of the PZR and RDT?

A

Steam Bubble: Thru RCA-HV-103 & RCB-HV-105 to RDT

RDT: To Waste Gas Surge Header or Refuel Purge (923)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When a N2 bubble exists on the PZR, what is used to determine proper curve to use for Level?

A

PZR Temperature (not pressure)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What must level be via LI-103 before energizing PZR Heaters?

A

25% or Greater

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the allowed actual max deviation between LI-110X/Y and LI-103?

A

<3%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When must the use of PZR spray be logged in 40ST-9RC01, RCS PZR HU and CD Rates?

A

Main Spray: All cycles when <4 RCP’s running

Aux Spray: All cycles

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the requirements for RCP Seal Injection?

A
  1. RCS Level >102’
  2. RCS Temperature >195F & Pressure >215PSIA
  3. Stop Seal engaged when secured. Sys Engineer.
  4. No Seal Injection to ANY RCP if stop seal is on ANY RCP.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Why are “Singe RCP Ops” Limits imposed?

A

To minimize pump wear due to runout

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the RCP Temperature Limits?

A
  1. 2 RCP’s or less if Tc <200F
  2. 3 RCP’s or less if Tc 200F to 500F
  3. Heat Removal via SG’s limited at low RCS temps, HU Rates may be exceeded if 3 RCP’s operating
  4. After 3rd RCP start, HU rates > 3.4.3, then stop 3rd RCP
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Why don’t we start RCP’s when SG Temperatures are greater than RCS Cold Leg Temperatures?

A

Prevent RCS Over-Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When can LTOP’s be isolated?

A

RCS Temperature >221F but <300F and after SDC has been secured.

17
Q

What are the SIAS Low PZR pressure setpoint requirements?

A

Cold Leg is >485F, the setpoint must be >140# greater than saturation pressure of Cold Leg

Ensures SIAS prior to RX Vessel upper head void formation in event steam line break

18
Q

What are the time limits for placing the Main Turbine turning gear in operation?

A
  1. Bearing Oil Header temp 80-102F
  2. Generator Seal Oil
  3. CD Vacuum broken on loss of seal steam (seals)
  4. > 4 hours before turbine startup (steam roll)
19
Q

How do we prevent core “lift” via RCP Operation?

A

3 or less operating when Temps are <500F