MA- Main Generation Flashcards
What is the purpose of the main generator?
Converting mechanical, rotational energy to electrical energy
How does the main generator interface with NK?
Provides power for the generator protection system
How does the main generator interface with the MB (excitation and Voltage regulation system)?
Provides regulated DC voltage to the MA system generator for field excitation
Provides trip signals to the MA generator trip logic
What are the major components of the main generator?
Stater frame, stater, rotor, Generator support
What type of generator is the main generator? How does it work?
It’s a revolving field AC generator in which direct current From the excitation system Is passed through windings on the rotor by means of slip rings and brushes.
What Is the purpose, operation and location of the stater frame?
A gas tight construction that supports and encloses the stator windings, core and rotating field.
Also directs hydrogen throughout the generator through multiple paths
Outer end shields supports the generator rotor bearing, hydrogen shaft seals and oil passages
Inner end shields separate the gas entering the fans from the gas discharged from the fans
What is in the lower frame extension of the main generator?
The main leads come down through this section which includes bushings, lower leads and insulators
How many windings does the secondary side of the unit aux transformer, MAN-X02, have?
Two
What are the necessary components to produce an electrical current in a conductor?
Field, conductor, and relative motion
Why is it necessary to add mechanical energy above and beyond that needed to overcome friction to the rotor to keep it rotating?
The current generated in the stator creates a magnetic field which interacts with, and opposes, rotation of the rotors magnetic field
How does the main generator (MA) interface with the GH system?
Transmits hydrogen from the service gases system (GA) to the generator and maintains the hydrogen quantity and quality
Hydrogen provides cooling medium for the generator rotor
Purging of the generator for maint. Is received from the CO2 portion of the GH system
How does the main generator interface with the generator lube oil system (LO)?
Supplies lube/lift oil to the main generator and exciter bearings.
Provides a low pressure supply of seal oil upon a loss of the main seal oil pumps.
How does the main generator interface with the generator seal oil system (SO)?
Controls the atmospheric leakage of the generator hydrogen gas at the annulus between the rotor shaft and the generator casing.
Maintains hydrogen purity
How does the main generator interface with the main turbine system (MT)?
Provides the motive power for the generator
Provides valve position signals to the MA system for generator trip logic
How does the main generator interface with the NA system?
NA receives 13.8kV power from the unit aux. transformers
How does the main generator interface with the NG system?
MA system cooling units are powered, normal and alternate sources, from NG
How does the main generator interface with the Remote Multiplex System (MX) system?
MA provides billing metering output and net MW and MVAR outputs
How does the main generator interface with the Stator cooling water system (CE) system?
Provides deionizing cooling water for the main generator stator windings, generator lower frame housing, generator bushings and the rectifier excitation system
what is the purpose of the Stator?
generates the voltage and current supplied to the unit auxiliary transformer and the main transformers
armature winding is formed by inserting insulated bars into the core slots and joining the ends to form coils each bar is hollow to allow stator cooling water to flow through them
what is the purpose, operation and location of the rotor?
it produces the magnetic flux.
flux strength is determined by the number of turns in the rotor winding and current in the winding. DC voltage (excitation) is ran through the rotor.
what is the purpose, operation and location of the isolated phase bus?
Purpose:
supplies power to the unit aux. transformer and the main transformers at 24kV.
operation:
the three generator phases exiting the generator are isolated and air cooled to reduce the heat generated by bus losses.
there are three aluminum conductors with porcelain insulators and cooled by the isophase bus cooling system,.
location:
runs from the generator on the 176’ turbine building, out and down the south side of the turbine building to the unit aux transformer, main transformers and MB transformers
what is the primary heat sink for the isophase busses?
turbine cooling water
If isophase bus cooling is lost, how long can rated current be maintained for without causing damage?
30 minutes
there is a hydrogen detection system for the isophase busses. What does high hydrogen concentration in the isophase bus ducts mean?
leakage of hydrogen from the generator stator through the main lead bushings