HT- Turbine building HVAC Flashcards

1
Q

What is the purpose of the HT system?

A

Maintains turbine building environmental conditions suitable for personnel occupancy and safe operation of equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Why is the non-class battery room ventilated?

A

To prevent accumulation of hydrogen in excess of 2% during normal operation and shutdown conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How many outside air supply normal AHUs are provided for the turbine building?

A

Six, supplying 100% OSA to the turbine building area

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is different about the HT system line up during winter conditions?

A

25% of the air is recirculated from the turbine building and about 75% of the air is replenished from outside air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Operation of the Outside Air and Recirculation dampers and the A Exhaust fan in the turbine building is dependent on the position of what switch?

A

Winter Shutdown Mode Switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What two positions does the HT winter shutdown mode switch have?

A

NORMAL

AUTO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How is operation affected when the HT winter shutdown mode switch is in NORMAL?

A

When outside air temperature falls to 36 degrees, the Outside Air Dampers and the Recirculation Damper will reposition such that 75% of the air comes from outside and 25% of the air comes from the Turbine Building

When outside air temperature rises to above 36 degrees the dampers will reposition back to normal such that 100% of the air comes from outside
The ‘A’ Turbine Exhaust Fan will stay running when the Winter Shutdown Mode Switch is in the NORMAL position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens when the HT Winter Shutdown Mode Switch is placed in AUTO?

A

Outside air dampers and recirculation damper will shift to the 75% outside 25% Turbine building position

When outside air temperature drops to 36 degrees the A Turbine Building Exhaust fan will stop

When outside air temperature rises above 36 degrees the A Exhaust Fan will start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does NH do for the HT system?

A

Powers normal roof exhaust fans, battery room normal exhaust fans, and lube oil area, demineralizer room and elevator room normal exhaust fans

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What powers the HT AHU fans?

A

NG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What system provides water for the air washers in the HT system?

A

DS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What system supplies air for the OSA intake dampers and recirculation dampers in the HT system? What would happen if that supply is lost?

A

Instrument Air

Normal supply dampers fail open and the recirc dampers fail closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where are the HT Normal AHUs located?

A

HTN-A01A, B, C – Yard north of the Turbine building

HTN-A02A, B, C – Outside on the 176’ Turbine building south side

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which HT normal AHU supplies air to the Non-Class Switchgear Room and Battery Room? How are the other rooms supplied?

A

HTN-A02C

transfer grills

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Where are the controls for HT system located?

A

Plant northwest corner of the turbine building on the 100’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How many normal roof exhaust fans are provided for the HT system and what is their purpose?

A

Four fans provided to exhaust warm air from the turbine building ceiling area and to help force air up from the lower elevations

17
Q

How many fans are provided for the non-class battery rooms?

A

Two 100% capacity normal exhaust fans

18
Q

How would I know that a non-class battery room exhaust fan flow is low?

A

Low flow switch will cause an alarm at the local panel and in the Control Room

19
Q

How many fans are provided for the Lube Oil room in the turbine building? What is their purpose?

A

Two 100% capacity normal exhaust fans

remove combustible gases and heat generated in the area

20
Q

How many exhaust fans are provided for the elevator room in the turbine building?

21
Q

Where is the HT Demin Area Fan Switch located?

A

100’ Turbine Building East Area

22
Q

Where is the HT Elevator Exhaust Fan Switch located?

A

194’ Turbine Building Elevator room

23
Q

What happens to the HT system if NKN-D41 is lost?

A

Power is lost to the Turbine Building HVAC panel, which means any operations will need to be done at the breakers

24
Q

When does the HT system operate? Is it required for safe shutdown?

A

continuously during all modes

not required for safe shutdown

25
How does the HT system interface with the OW system?
AHU evap cooler sump overflow drains to the OW sump in the plant north yard
26
What does each HT AHU consist of? What electrical protection do the AHUs have?
pleated filters WETdek evap. module system moisture eliminator vane-axial fan over current
27
What HT exhaust fans have auto features?
A exhaust fan only
28
What is the difference between the control switches for the HT normal AHUs and the other HVAC equipment in the turbine building?
normal AHUs have a spring loaded return to neutral switch everything else has a two position selector switch
29
What components does the HT cold lab ACU consist of? How is it controlled?
heat pump, blower unit and a moderate efficiency filter thermostat
30
What effect does the Ultrasonic Flow Measurement device in the switch gear room have on reactor power? What would cause the UFM to be lost?
affects feedwater flow to the steam generators, limiting power to 98% loss of the supply fan or air washer