EC- Essential Chilled Water Flashcards
What is the purpose of the Essential Chilled Water system?
Supplies chilled water to the essential air cooling units and air handling units in the control and aux building during essential equipment operation
Can the two trains of Essential Chilled Water systems be cross connected?
No
The chilled water supplied to the AHUs and ACUs will cool what spaces?
Control Room Essential ventilation
DC equipment Room Essential Cooling
Electrical Penetration Room cooling
HPSI Pump Room cooling
CS Pump Room cooling
LPSI Pump Room cooling
ESF switchgear and equipment room cooling
AFP Room cooling
Essential Cooling
Water Pump room cooling
What is the normal source of makeup water to the Expansion tank? Backup? Emergency?
Normal: DW
Backup: CT
Emergency: FP
What are the Essential Chilled Water pumps rated for?
400 gpm at 100 ft head
What powers the Essential Chilled Water pumps? Where are they located?
PH powered 20 hp electric motor
74’ control building next to essential chillers
Where are the Essential Chilled Water pumps operated from?
Control switch in the Control room, and locally at the breaker
What is the capacity of the Essential Chillers?
235 ton capacity
What major components makeup the chiller package?
Cooler Compressor and motor Condenser Flash Economizer Pump down unit
Where are the Essential chillers normally operated from? Where else can it be operated from?
Control Room
A three position spring return switch located at the 4160 V class switchgear for each chiller
When would I start the chilled water pump independently of the chiller from the local push button on the supply MCC breaker?
Routinely done to perform chemical sampling of the chilled water
What is the Chiller start sequence?
(T + 0) Chiller start signal
(T + 0) Program timer starts
(T + 0) Chilled water pump starts
(T + 23) Chiller LO pump starts ~23 seconds after the chilled water pump
(T + 51) Chiller compressor starts ~28 seconds after the chiller LO pump starts
When the chiller starts, what energizes to block a restart attempt?
A 20 min restart relay
For the essential chillers, If the start signal is from the ESF, how would that affect the restart relay?
A 2 min emergency time delay will bypass the 20 min restart relay after two minutes if the sequence permissive relay de-energizes
What is the Chiller Stop sequence?
(T + 0) Chiller stop signal
(T + 0) Program timer starts
(T + 0) The chiller compressor and chilled water pump both stop
(T + 0) The inlet guide vanes go closed
(T + 41) Approximately 40 seconds after the chiller stops, the LO pump stops
What is used to set and control the desired chilled water supply temp?
Thermostat
What is used to set and limit compressor motor current flow by positioning the compressor inlet guide vanes?
Electrical Demand Unit
What are the basic flow paths of the two fluids flowing through the Essential Chiller Cooler?
Low pressure, liquid refrigerant on the shell side absorbs heat from chilled water flowing through the tubes as the refrigerant flashes to vapor
What feature of the Essential Chiller Cooler maximizes efficiency at all load conditions through equal use of all tubing surface areas for heat transfer?
A distribution system delivers the liquid refrigerant uniformly to all parts of the cooler tube bundle
Concerning the Essential Chiller Cooler, what is installed above the tube bundle to provide balanced suction pressure throughout the cooler? What other function does it serve?
Flow equalizer plates
These plates also prevent liquid carry over into the compressor
What is the purpose of the Essential Chiller Compressor?
A two stage, centrifugal compressor that takes suction on the cooler shell, increases the refrigerant gas pressure, and discharges to the condenser
How is refrigerant flow controlled in the Essential Chiller Compressor?
By the inlet guide vanes installed in the suction. These vanes are controlled by the temperature of the chilled water leaving the chiller
What feature of the Essential chiller compressor increases efficiency?
An inlet connection is provided between the first and second stages to allow single stage compression of refrigerant gas returning from the flash economizer. This means the flash gas only requires one stage of compression
What is “Surging” and how does it occur? Why is it a concern?
A momentary gas flow reversal from the condenser through the compressor
It occurs when the system heat load is not great enough to evaporate a sufficient volume of refrigerant in the cooler.
The compressor alternately tries to deliver the gas to the condenser, but is unable to equal condenser pressure and the condenser returns the gas
Continued surging may cause compressor bearing damage due to overheating
What is a way to avoid “Surging” during low heat load conditions?
Use of the “hot gas bypass” that directs a portion of the discharge gas to the bottom of the cooler, flashing some of the liquid refrigerant to gas and increasing gas flow from the cooler to the compressor suction
What powers the Essential Chiller Compressor motor?
PB
How is the Essential chiller compressor cooled and lubricated?
Refrigerant cooled and oil lubricated
What maintains the motor cooling flow?
D/P between the condenser and the cooler
How long after the chilled water pump starts will the oil pump energize?
23 seconds
When a chiller is shutdown, why do we have an electric heating coil energized in the oil sump?
To ensure proper oil viscosity and to prevent excessive Freon absorption