ESFAS Flashcards
Given the following plant conditions: Unit 3 has received a LOP on PBA-S03. The control operator notices that the Train ‘A’ Spray Pond pump has a blue SESS alarm. This alarm tells the operator that the Train A Spray Pond pump …..
A. is in the proper position for the current actuation.
B. pump has lost control power.
C. has tripped due to an 86 Lockout.
D. was called upon to start but did not start.
Answer: D
Given the following conditions: The unit is operating at rated power. A loss of PNA-D25 occurs. What impact (if any) will this loss have on BOP ESFAS?
A. Nothing will actuate or become non-functional solely due to the power loss.
B. Train ‘A’ CREFAS, CPIAS and FBEVAS actuations ONLY.
C. Train ‘A’ BOP ESFAS will become de-energized and not function.
D. Train ‘A’ and ‘B’ CPIAS, CREFAS, and FBEVAS will actuate.
Answer: D
You are investigating a trip of FBEVAS at the BOP ESFAS cabinets. The following lights are illuminated on the Train “A” FBEVAS module: The TRIP and RESET halves of the TRIP/RESET pushbutton. The ACTUATE of the ACTUATE/MAN/RST button. Based upon these indication, this train of FBEVAS has tripped due to…
A. a manual actuation from B05.
B. RU-31 (Fuel Building) exceeding the trip setpoint and subsequently decreasing below this setpoint.
C. a manual actuation from BOP ESFAS Cabinet.
D. RU-31 (Fuel Building) exceeding its trip setpoint and remaining above this value.
Answer: B
Which of the following signals does NOT directly result in a start of a Spray Pond pump?
A. LOP
B. CIAS
C. SIAS
D. CREFAS
Answer: B
Which of the following describes the BOP ESFAS power supply arrangement? Each cabinet receives power from its associated train of…
A. PK and PN, which is auctioneered so that a loss of either supply to the cabinet does not impact the operation of the system.
B. PK ONLY. A loss of this power supply to the cabinet will cause an actuation of the components controlled by that train of BOP ESFAS.
C. PN ONLY. A loss of this power supply to the cabinet will cause an actuation of the components controlled by that train of BOP ESFAS.
D. PK and PN. A loss of either power supply to the cabinet will prevent those components controlled by the affected BOP ESFAS cabinet from actuating when needed.
Answer: A
What impact would depressing the AFAS 1 TEST push button on the Train B BOP ESFAS Load Sequencer module have on the AFAS?
A. AFA and AFB would start, associated feed valves would remain closed.
B. AFB would start, all associated feed valves would open.
C. AFA and AFB would start, all associated feed valves will open.
D. AFB would start, associated feed valves would remain closed.
Answer: D
What impact would depressing the SIAS/CSAS TEST push button on the Train “A” BOP ESFAS Load Sequencer module have on the Safety Injection system?
A. Both Train A and B HPSI, LPSI and CS pumps would start, no injection valves open.
B. The Train A HPSI, LPSI, and CS pumps would start and all injection valves would open.
C. The Train A HPSI, LPSI, and CS pumps would start, no injection valves open.
D. Both Train A and B HPSI, LPSI, and CS Pumps would start and all injection valves would open.
Answer: C
Which of the following signals will cause an EDG start to occur?
A. CIAS
B. RAS
C. CSAS
D. MSIS
Answer: C
You are investigating a trip of CPIAS ‘A’ at the BOP ESFAS cabinets. The following lights are illuminated on the Train ‘A’ CPIAS module: Both the TRIP and RESET halves of the TRIP/RESET button. The ACTUATE half of the ACTUATE/MAN/RST button. Based upon these indications, which one of the following has caused this trip?
A. High radiation signal from RU-37 (Power Access Purge Monitor ‘A’) which has subsequently cleared.
B. Cross train trip signal.
C. Manual actuation from B05.
D. High radiation signal from RU-37 (Power Access Purge Monitor ‘A’) which is still above its trip setpoint.
Answer: A
Given the following conditions: The unit is operating at rated power. A loss of PNC-D27 occurs. What impact (if any) will this loss have on BOP ESFAS?
A. Train “A” and “B” CPIAS, CREFAS, and FBEVAS will actuate.
B. Train “A” CPIAS, CREFAS and FBEVAS actuations only.
C. Nothing will actuate or become non-functional due to the power loss.
D. Train “A” BOP ESFAS will become deenergized and not function.
Answer: C
Given the following initial conditions: Reactor has tripped. Standard Post Trip Actions are complete. SIAS/CIAS/MSIS. Steam Generator #2 has a tube rupture. Steam Generator #2 has a stuck open Steam Generator Safety Valve. Pressurizer level is 0. SG#1 level is 40% WR and decreasing. SG#2 level is 30% NR and increasing slowly. Which of the following represents an appropriate Feedwater configuration?
A. Feed SG#1 only at approximately 500 gpm.
B. Feed both SGs approximately 250 gpm.
C. Feed SG#2 only at 1360 to 1600 gpm.
D. Feed SG#2 only at approximately 500 gpm.
Answer: C
Which of then following signals will result in a start of a Spray Pond pump if initiated from B05?
A. RAS
B. CREFAS
C. CIAS
D. FBEVAS
Answer: B
Given the following conditions: Unit at 50% power. PNC-D27, 120 VAC distribution panel, loses power. All systems operate as designed. WHICH ONE of the following describes the expected response of the Reactor Protection and BOP-ESFAS Systems?
A. Reactor trip and all ESFAS and BOP-ESFAS actuations.
B. Initiation relays deenergize on PPS Channel’s A & C and no BOP ESFAS actuations.
C. CREFAS, CPIAS, and FBEVAS Train actuations and initiation relays deenergize on Channels A and C.
D. CREFAS, CPIAS, and FBEVAS Train actuations and initiation relays deenergize on Channels C and D.
Answer: B
Choose the statement below which describes the plant response if the TEST pushbutton is depressed on the Train “A” FBEVAS module on the BOP ESFAS cabinet.
A. Actuation of Train A FBEVAS and Train A CREFAS ONLY.
B. Actuation of Train A FBEVAS ONLY.
C. Actuation of Train A and B FBEVAS ONLY.
D. Complete actuation of FBEVAS and CREFAS.
Answer: D
Given the following conditions: Unit 2 is operating at rated power. Because of a suspected problem, the Train B Loss of Power (LOP)/Load Shed (LS) relays are all bypassed. While the crew is looking into the Technical Specifications, a loss of off-site power occurs. Assuming no operator action, how would the electrical distribution system look after the electric plant transient is stabilize?
A. PBB-S04 energized by Diesel Generator
B. PBB-S04 de-energized, Diesel Generator never received a start signal.
C. PBA-S03 de-energized, Diesel Generator running unloaded.
D. PBA-S03 de-energized, Diesel Generator tripped on high temperature.
Answer: B
If a SIAS is manually initiated from B05 and the”A” load sequencer fails to operate, which of the following pieces of equipment would fail to go to their SIAS position?
- “A” HPSI pump
- “A” CS pump
- “A” HPSI injection valves
A. 3 ONLY.
B. 1, 2 and 3.
C. 1 and 3 ONLY.
D. 1 and 2 ONLY.
Answer: D
Given the following conditions: The unit is operating at rated power. The DC supply breaker to Train “A” BOB ESFAS cabinet trips. What, if anything, occurs as a result of this failure?
A. The lights on BOP-ESFAS train will flash, indicating that an error has been detected.
B. Full actuation of Train “A”.
C. Full actuation of Train “A”, with appropriate cross trips to Train “B”.
D. This failure should have no impact.
Answer: D
Given the following conditions: Unit is operating at rated power. CREFAS Train “A” is in BYPASS. RU-31 (Fuel Pool Area Monitor) fails HIGH. Which of the following describes the expected plant response?
A. Both Trains of FBEVAS and both Trains of CREFAS actuate.
B. Train A FBEVAS actuates ONLY.
C. No actions should occur due to this signal failure.
D. Both Trains of FBEVAS and Train “B” of CREFAS actuate.
Answer: A
Given the following plant conditions:
Unit 1 is operating in Mode 5 with SDC in service. The ‘A’ LPSI pump is operating. An inadvertent Train ‘A’ RAS occurs. Based on these conditions, what actions, if any, are necessary to maintain and/or restore the plant to a stable condition?
A. Override and start the ‘A’ LPSI pump and restore SDC to service.
B. No actions should be necessary, since the RAS is only Train ‘A’.
C. Override and open the LPSI injection valves to restore SDC to service.
D. Override and open the minimum recirc valves to restore minimum flow protection for the ‘A’ LPSI pump.
Answer: A
You are investigating a trip of FBEVAS at the BOP ESFAS cabinets. The following lights are illuminated on the Train “A” FBEVAS module: The ACTUATE, MAN and RST of the ACTUATE/MAN/RST button. Based upon these indication, which one of the following has caused this trip?
A. Manual actuation from B05.
B. Cross train trip signal.
C. Manual actuation from BOP ESFAS Cabinet.
D. High radiation signal from RU-31 (Fuel Pool Monitor).
Answer: A
A rad monitor trip has caused a FBEVAS to actuate. How can an operator at the BOP-ESFAS cabinets determine that the rad monitor signal has dropped below the FBEVAS setpoint?
A. The TRIP portion of the TRIP/RESET pushbutton will dim but not extinguish.
B. The TRIP portion of the TRIP/RESET pushbutton will extinguish.
C. The RESET portion of the TRIP/RESET pushbutton will illuminate.
D. Both the TRIP and RESET portions of the TRIP/RESET pushbutton will extinguish.
Answer: C
Given the following conditions: Unit 1 is operating at rated power. Because of a suspected problem, the Train A Loss of Power (LOP)/Load Shed (LS) relays are all bypassed. While the crew is looking into the Technical Specifications, a loss of off-site power occurs. Assuming no operator action, how would the electrical distribution system look after the electric plant transient is stabilize?
A. PBA-S03 de-energized, Diesel Generator running unloaded.
B. PBA-S03 energized by Diesel Generator
C. PBA-S03 de-energized, Diesel Generator never received a start signal.
D. PBA-S03 de-energized, Diesel Generator tripped on high temperature.
Answer: C
Given the following conditions Unit 2 operating at 100% full power. Radiation monitor RU-31, train “A” Fuel Building area monitor, fails high. Train “B” Control Room Essential Filtration Actuation System module is in BYPASS. Fuel Building Essential Filtration (FBEVAS) train “A” actuates. All other systems and components are operating correctly. WHICH ONE of the following states all expected balance of plant engineered safety features actuation(s) in addition to FBEVAS Train “A”?
A. CREFAS Trains “A” and “B”.
B. CREFAS Train “A”.
C. FBEVAS”B” and CREFAS Trains “A” and “B”.
D. FBEVAS Train “B” and CREFAS Train “A”.
Answer: C
Unit 1 is operating in Mode 1. The fuses for a bus potential transformer (PT) located in on PBA-S03 blow. The PT supplies undervoltage relays 727-1 and 727-5. Assuming this is the only failure, how will the plant respond?
A. The D/G will start and run unloaded while PBA-S03 remains energized from offsite power.
B. PBA-S03 will load shed, the D/G will start and close in on the bus.
C. PBA-S03 will load shed, the D/G will need to be manually started to re-energize the bus.
D. No actuation should occur.
Answer: D
Choose the statement below which describes the plant response if the Train ‘A’ FBEVAS manual switch on B05 is taken to TRIP.
A. Actuation of Train A FBEVAS and Train A CREFAS ONLY.
B. Actuation of Train A and B FBEVAS ONLY.
C. Actuation of Train A FBEVAS ONLY.
D. Complete actuation of FBEVAS and CREFAS.
Answer: C
Unit is operating at rated power. CREFAS Train “B” is in BYPASS. Due to a Fuel Handling problem, the operator manually actuates Channel “A” FBEVAS from B05. Which of the following describes the expected plant response?
A. Both Trains of FBEVAS actuate and ONLY Train “A” of CREFAS actuates.
B. Both trains of FBEVAS actuate ONLY.
C. Both trains of FBEVAS and CREFAS actuate.
D. Channel “A” FBEVAS actuates ONLY.
Answer: D