On smaller capacity refrigeration compressors the_________ valves prior to starting.
A) Close the suction and open the discharge
B) Close the suction and discharge
C) Open the bypass
D) Open the suction and discharge
E) Open the suction and close the discharge
D) Open the suction and discharge
The high-pressure float valve is a liquid level operated control valve located on the:
A) Evaporator
B) High-pressure side of the system
C) Low-pressure side of the system
D) Downstream side of the evaporator
E) Downstream side of the expansion valve
B) High-pressure side of the system
Positive pressure testing of a refrigeration system is done using dry __________ gas as the pressure agent.
A) Carbon monoxide
B) Helium
C) Nitrogen
D) Hydrogen sulphide
E) Oxygen
C) Nitrogen
A pressure-actuated refrigeration control cannot be used in conjunction with a/an __________ expansion valve.
A) Solenoid
B) Humidity
C) Hand
D) Thermostatic
E) Automatic
E) Automatic
Flow switches are used on chilled water and cooling water lines and air ducts are used as __________ switches.
A) Safety lockout
B) Low temperature lockout
C) Over pressure lockout
D) Evaporator level control
E) Condenser pressure control
A) Safety lockout
The thermostatic refrigeration controller has a differential adjustment that sets the temperature at which the:
A) Cut-in and cut-out occurs
B) Condenser cooling water control activates
C) Expansion valve opens and closes
D) Level in the evaporator control activates
E) Fan starts and stops
A) Cut-in and cut-out occurs
The most common application of evaporator capacity control is to use:
A) Adjustable evaporators
B) Sectional condensers
C) Sectional evaporators
D) Variable evaporators
E) Sectional receivers
C) Sectional evaporators
What is the symptom of a refrigeration system when the compressor fails to start due to an open control circuit?
A) Seized compressor
B) Circuit breaker closed
C) Power on motor terminals
D) Full line voltage at terminals
E) No power on terminals of starter holding coil
E) No power on terminals of starter holding coil
One of the safety devices on a centrifugal refrigeration compressor that acts preventing the compressor from being started is the ____________ switch.
A) Refrigerant level high
B) Refrigerant level low
C) Vane closed
D) Evaporator temperature high
E) Condenser temperature low
C) Vane closed
If any moisture or water vapour is present in a refrigerating system that contains chlorine or fluorine an acid is formed that reacts with the compressor oil to produce sludge that will:
A) Coat the evaporator
B) Plug the expansion valve
C) Restrict cooling water flow
D) Corrode metal parts
E) Clog the condenser
D) Corrode metal parts
The purging unit of the refrigeration system should be operated for at least ________ minutes before the compressor is started (time depends on the size of the system).
A) 20
B) 10
C) 15
D) 5
E) 25
B) 10
One of the disadvantages of evaporator capacity control by face damper is that the:
A) Refrigerant volume to the space is reduced
B) Refrigerant pressure to the space is reduced
C) Temperature of the space is increased
D) Temperature of the space is reduced
E) Air volume to the space is reduced
E) Air volume to the space is reduced
The most widely used refrigerant control is the:
A) Capillary tube
B) Automatic expansion valve
C) Hand operated expansion valve
D) Low pressure float
E) Thermostatic expansion valve
E) Thermostatic expansion valve
The benefits of a good preventative maintenance program may include all of the following except:
A) Increased operating efficiency and a reduction in energy consumption
B) Reduction of overall maintenance costs
C) More dependable service from the equipment
D) Efficient scheduling of maintenance operations
E) Increase in major breakdown repairs
E) Increase in major breakdown repairs
It may be illegal to ____________ a refrigeration system without determining the location of and repairing the system leak.
A) Simply add refrigerant to
B) Drain refrigerant from
C) Change the compressor of
D) Evacuate the evaporator of
E) Flush the condenser of
A) Simply add refrigerant to