what are 4 basic things that any control system must perform?
measure, compare, compute, correct
what does the term manipulated variable mean?
any quantity or condition that is varied by a control systems to affect the value of the controlled variable
what does the term controlled variable mean?
any quantity or condition that is measure and controlled by a control system
an example of a final control element in the three element feed system would be what?
the feed water control valve
the steady satte difference between the control point and the value of the controlled variable corresponding to the set point is called what?
offset
deviation is the instantaneous difference between the actual valley of the controlled valve and the value of the controlled variable corresponding to what?
set point
the term dead time refers to what?
the time required to transport a change from one place to another
what are 3 ways that computing and comparison can be accomplished in a pneumatic transmitter?
the nozzle and vane assembly; bellows; escapement valves
continuous changing of the controlled variable is called what?
cycling
what re the three modes of control in the automatic boiler control system?
automatic, remote manual, local manual
what are the three loops associated with the automatic boiler control system?
steam pressure control loop, airflow control loop, fuel flow control loop
what will be the position of the feed water control valve if the diaphragm ruptures?
100% Open
what is the only authoritative source of information on the boiler control system on any ship?
the manufacturer’s technical manual
what does the term supply air pressure refer to?
the compressed air that is supplies to each pneumatic unit
compressed air that goes from one pneumatic unit to another pneumatic unit is known as?
loading pressure
a general regulator automatic combustion control system on a 600 psi steam plant is designed to maintain what set point when measured from the superheater outlet?
600 - 615 psig
what is the effective loading pressure range on a General Regulator combustion control system?
3- 5 psi
what component within the general regulator combustion control system develops a demand signal to maintain the boiler at a desired standard for any boiler load?
steam pressure controller
what is the desired set point on general regulator steam pressure transmitter?
7 psi
what is the function of the high limit and low limit relays on a general regulator combustion control system?
to prevent the master demand signal from bleeding out of range on the high end or the low end of the signal range operating pressure
the output of the high limit relay is applies to what component
low limit relay
what is the function of the airflow transmitter?
measures the pressure difference across the burner opening and develops a loading signal proportional to the rate of airflow per burner
the air flow controller serves what function?
develops a loading signal to the force draft blower speed control
the airflow controller is what type of controller?
proportional plus reset
what component within the general regulator combustion control systems designed to speed up force draft blower response time?
steam flow rate relay
what component converts the fuel oil demand signal a nonlinear signal?
characterizing relay
how is the minimum fuel oil pressure set on a general regulator FO control valve?
by adjusting the spring fore in the valve with the external spring adjusting screw and locking it in place with jam nut
a blown diaphragm within the FO characterizing relay on a general regulator combustion control system will have what effect on fuel oil header pressure?
fuel oil pressure will go to maximum and cause black smoke boiler assembly
what three elements are measured within the feed water control system?
boiler drum level, steam flow and feed flow
what component within the three element feed water control system develops a pneumatic signal proportional to actual boiler water level?
drum level transmitter
what terms are used to describe the three pneumatic signals associated with the feed water control system?
drum level = supervisory signal, steam flow = demand signal, feed flow = response signal
what component within the three element feed water control system compares the steam flow signal, feed flow signal and set point signal and develops a pneumatic output signal proportional to the difference between its inputs?
steam flow/ feed flow differential relay
what is the set point adjuster set at to maintain a normal water level on the three element feed water control system?
9 psi