AOP-37, Loss of Instrument Air Flashcards

1
Q

What is the purpose of AOP-37, Loss of Instrument Air?

A

Provides operator actions that must be accomplished subsequent to a loss of instrument air.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the entry criteria for AOP-37, Loss of Instrument Air?

A
  • EK-1101, “CONTAINMENT INSTR AIR LO PRESS” (85 psig)
  • EK-1102, “INSTRUMENT AIR LO PRESS” (85 psig)
  • EK-1103, “SERVICE AIR LO PRESS” (80 psig)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the automatic actions for AOP-37, Loss of Instrument Air?

A
  • Standby Instrument Air Compressor(s) starts at 92 psig
  • CV-1212, Service Air Header Isol closes at 85 psig in the Instrument Air Header
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the trip criteria for AOP-37, Loss of Instrument Air?

A

Erratic equipment behavior observed on equipment required for safe plant operation

Approximately 50 psig.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the immediate actions of AOP-37, Loss of Instrument Air?

A

None

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the operator actions for AOP-37, Loss of Instrument Air?

A

As needed:

  • Place C-2A/B/C to Hand
  • Cross-tie FW Purity Air
  • If Instrument Air NOT greater than 85
    • THEN announce twice (“Personnel using breathing air stop work and leave your immediate work area now.”)
    • Trip V-7
  • Send NPOs to compressors/dryer.
    • Bypass dryer
  • EOP Supplement 36, CV Tracking Sheet
How well did you know this?
1
Not at all
2
3
4
5
Perfectly