AOP-2 Excessive Load Flashcards
What is AOP-2 and its entry criteria?
AOP-2 Criteria
Excessive Load Procedure. Goal is to isolate the load.
Entry Criteria:
- EK-0968, “LOOP 1 TAVE/TREF GROSS DEVIATION” (5F)
- EK-0969, “LOOP 2 TAVE/TREF GROSS DEVIATION” (5F)
- EK-1362, “CONTAINMENT PRESSURE OFF NORMAL” with a steam leak in containment
- Turbine Governor Valve Control Malfunction (open)
What are the AOP-2 Exit Criteria?
AOP-2 Exit Criteria
- An inappropriate procedure has been implemented. An inappropriate AOP may have been implemented if the event was misdiagnosed.
- Once the event has been mitigated, and the plant is stable, the appropriate operating procedure should be used.
What happens with increased steam flow?
Feed Reg valves open to match increase in steam flow and maintain SG water level.
Secondary (SG) system pressure drops. Temperature drops.
SG Primary Side outlet temperature drops (Tcold). Tave drops.
Pressure level drops as PCS shrinks.
If negative MTC, reactor power rises.
Will the reactor trip during a increased steam demand event?
Depending on the magnitude of the increase in steam demand, a reactor trip
may not be activated.
Instead, the reactor system will reach a new steadystate
condition at a power level greater than the initial power level which is
consistent with the increased heat removal rate.
What is most likely to trip the reactor during an excess steam demand event?
TM/LP
Variable High Power
- The limiting DNB case will typically trip on the variable overpower trip.
How does the VHP Trip function and what/why is decalibrated?
VHP auctioneers the highest of Delta-T or NI-Power.
- Delta-T signal is decalibrated due to hot and cold leg RTD lag times.
- NI-Power is decalibrated due to excore shadowing by cold water in the downcomer region.
What is the criteria for tripping the reactor during an excess steam demand event? Turbine?
Reactor
- An un-isolable load rise which exceeds 1% change in HB Power Steady, NI or ΔT Power
- A plant condition requiring a power reduction at a rate greater than 30%/hour
- EK-1362, “CONTAINMENT PRESSURE OFF NORMAL” in alarm AND a steam leak inside containment
- Reactor power greater than or equal to 15% AND Turbine Governor Valve Control in manual and not controlling
Turbine
- Reactor power less than 15% AND Turbine Governor Valve Control in manual and not controlling
What AOP-2 Criteria would leak to an EI Plan entry?
Unusual Event
Any loss or any potential loss of Containment (Table F-1)
Containment Pressure greater than 55 psig
Contain pressure 4 psig with less than one full train of containment cooling system operating.
What MWe output on the generator equates to a 1% reactor power rise?
9 MW
Reactor Trip Criteria
- An un-isolable load rise which exceeds 1% change in HB Power Steady, NI or ΔT Power
What events cause an excess load within AOP-2?
- Turbine Governor Valve Control malfunction
- Turbine Bypass Valve (CV-0511) open
- Atmospheric Steam Dump Valve(s) open
- High Energy Line Break or Steam Generator Code Safety stuck open
What are the actions for Governor Valve Malfunction?
Governor Valve Malfunction
- PLACE Turbine Controls to MANUAL
- VERIFY Turbine Governor Valve control restored.
- CLOSE the Governor Valves using the Governor Close button to restore Reactor power to pre-event level or less as indicated by HB Power Steady, NI or ΔT Power.
What are the actions for a TBV Malfunction?
TBV Malfunction
CLOSE CV-0511 as follows:
- DEPRESS the “M” pushbutton on PIC-0511, Turbine Bypass Valve Controller.
- PLACE AND HOLD PIC-0511 manual lever to CLOSE until the valve position green closed light illuminates.
- RELEASE PIC-0511 manual lever.
RNO
Isolate valve manually
What are the actions for an ASDV Malfunction?
ASDV Malfunction
CLOSE Atmospheric Steam Dump Valve(s) as follows:
- DEPRESS the “M” pushbutton on HIC-0780A, Atmospheric Steam Dump Controller.
- PLACE AND HOLD HIC-0780A manual lever to CLOSE until the valve position green closed light(s) illuminate.
- RELEASE HIC-0780A manual lever.
RNO
Closed air supply valve for affected ASDV (preferred)
Manually isolate ASDV
What are the actions for a MS Code Safety?
MS Code Safety
If verified that a code safety is lifting then:
COMMENCE a power reduction at a rate of less than or equal to 30%/hour. Refer to
GOP-8, “Power Reduction and Plant Shutdown to Mode 2 or Mode 3 525F.”
What are the actions for a HELB?
HELB
VERIFY containment parameters normal.
- IF indications of a steam leak inside Containment, AND EK-1362, “CONTAINMENT PRESSURE OFF NORMAL” is in alarm, THEN TRIP the Reactor.
LOCATE AND ISOLATE the High Energy Line break.
- COMMENCE a power reduction at a rate of less than or equal to 30%/hour. Refer to GOP-8, “Power Reduction and Plant Shutdown to Mode 2 or Mode 3 <= 525F.”