AOP-28, Pressurizer Pressure Control Malfunctions Flashcards
What are the entry conditions for AOP-28, Pressurizer Pressure Control Malfunctions?
- EK-0753, “PRESSURIZER PRESSURE OFF NORMAL HI-LO” (HI-2110 psia, LO-1975 psia)
- EK-0754, “PRESSURIZER PRESSURE OFF NORMAL HI-LO” (HI-2110 psia, LO-1975 psia)
- EK-1373, “SV AND /OR PORV OPEN”
- Charging or Letdown System malfunctions during solid plant operation
What are the automatic actions of AOP-28, Pressurizer Pressure Control Malfunctions?
Possible reactor trip on TM/LP.
What are the trip criteria (reactor/equipment) of AOP-28, Pressurizer Pressure Control Malfunctions?
Reactor Trip
- Either Pressurizer Spray Valve failed open AND Pressurizer pressure not being maintained.
Equipment Trip
- CV-1057 Pressurizer Spray Valve failed open.
Trip P-50A and P-50B, PCPs.
Pressurizer pressure not being maintained. Trip P-50D, PCP.
- CV-1059 Pressurizer Spray Valve failed open.
Trip P-50C and P-50D, PCPs.
Pressurizer pressure not being maintained. Trip P-50A, PCP.
- Operating PCPs
- Pressurizer pressure less than 235 psia for greater than 1 minute, on PI-0104,
- Narrow Range Pressurizer Pressure Ind.
- Pressurizer pressure less than 200 psia on PI-0104, Narrow Range Pressurizer Pressure Ind.
What are the immediate actions of AOP-28, Pressurizer Pressure Control Malfunctions?
None
What are the three main branching areas of AOP-28, Pressurizer Pressure Control Malfunctions?
- Pressurizer Pressure Control Malfunctions
- Solid Plant Control (Letdown Pressure Control)
- LTOP System Actuation
What pressurizer heaters are fed from D-bus?
Group 2 - 75KW
Group 3 - 300KW
Group 4 - 375KW
What is the 2-hour load limit for the 1-2 EDG?
2750 KW
Why would a containment entry be required for AOP-28, Pressurizer Pressure Control Malfunctions?
On pressurizer spray valve failed open and heaters not keeping up, you trip the reactor.
Post trip you trip P-50A and P-50B. (P-50C/D)
If that doesn’t allow heater to maintain, you trip P-50D (P-50A).
You may need to perform an entry to isolate spray valves manually.
How does shutdown margin relate to AOP-28, Pressurizer Pressure Control Malfunctions?
You may need to establish shutdown margin per EM-04-08 “Shutdown Margin Requirements” or COLR section 2.1 “Shutdown Margin”
If it is a letdown pressure control issue, what might you do?
Manually operate PIC-0202, Intermediate Pressure Controller.
Alternate Backpressure Regulating Valve CV-2012 or CV-2122
How many starts can you perform on a tripped charging pump?
One Attempt
When do you trip primary coolant pumps for low pressure?
Less than 235 psia, on PI-0104, Narrow Range Pressurizer Pressure Ind, for more than 1 minute
When does LTOP alarm for no protection?
EK-0759, “No PCS Protection Channel A”
EK-0765, “No PCS Protection Channel B”
at 460F on a Tc
What are the LTOP trip setpoints?
Normal per LTOP Curve with pre-trip at 50-psi before set-point.
Shutdown Cooling
Trip 310 psia
Pre-trip 265 psia