AOP-12, LOSS OF PREFERRED AC BUS EY-10 Flashcards

1
Q

What is the mitigating strategy of AOP-12, LOSS OF PREFERRED AC BUS EY-10?

A
  1. Trip Reactor if greater than 80% power and CV-0711, Feed Pump P-1A Recirculation is not isolated.
  2. Isolate CV-0711, Feed Pump P-1A Recirculation Valve.
  3. Determine if an actual fault exists on EY-10, Preferred AC Bus No 1.
  4. If a fault does not exist, supply power to EY-10 with the Bypass Regulator.
  5. If a fault does exist, perform compensatory actions for lost indicators and equipment.
  6. Restore EY-10.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the entry conditions of AOP-12, LOSS OF PREFERRED AC BUS EY-10?

A

EK-0543, “PREFERRED AC BUS NUMBER 1 TROUBLE”

AND

Channel ‘A’ RPS Trip Ladder Logic Lights Illuminated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the automatic actions of AOP-12, Loss of Preferrend Instrument AC Bus Y-10?

A
  • P-8A, Motor Driven Auxiliary Feedwater Pump, control circuitry transfers to EY-30, Preferred AC Bus No 3.
  • P-8B, Steam Driven Auxiliary Feedwater Pump, control circuitry transfers to EY-30, Preferred AC Bus No 3.
  • Main Feedwater control for E-50A, ‘A’ S/G, transfers to EY-30, Preferred AC Bus No 3.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the Reactor Trip Criteria of AOP-12, Loss of Preferred Instrument AC Bus EY-10?

A

Greater than 80% power, trip the reactor.

  • CV-0711, Feed Pump P-1A Recirculation Valve, fails open with Reactor power greater than 80%
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the immediate actions of AOP-12, Loss of Preferred Instrument AC Bus EY-10?

A

None

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How is RIA-1805 impacted by a loss of EY-10, Preferred AC Bus? What could happen?

A

RIA-1805 fails to tripped status.

One other 1806-1808 monitor trips and containment will isolate.

While left channel CIS is deactivated by a Loss of Y-10, CV-2009 is actuated by either channel.

CV-2009 closing isolates the letdown line and will result in lifting RV-2006.

PCS leak. 3.4.13 PCS Operational LEAKAGE. MODES 1, 2, 3, and 4.

4 Hours to Limit.

PCS operational LEAKAGE shall be limited to:
a. No pressure boundary LEAKAGE;
b. 1 gpm unidentified LEAKAGE;
c. 10 gpm identified LEAKAGE; and
d. 150 gallons per day primary to secondary LEAKAGE through any
one steam generator (SG).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How is HS1/LIC-0101 impacted by the loss of Y-10?

A

HS1/LIC-0101, Heater Select Switch is normally in the “A+B” position.

It passes the low level signal (<36%) from A&B controllers to trip off the pressurizer heaters and close CV-2003, letdown orifice stop valve.

If Y-10 fails, LIC-0101A fails to low level. System goes to maximum charging, isolates letdown and shuts down the heaters.

HS1/LIC-0101, Heater Select Switch, is taken to ‘B’ channel.

Ensures affected components (Charging Pumps and Letdown Orifice Stop Valves) are provided a neutral process signal (50% Pressurizer Level Controller process output signal). Remember: OOS controller is placed in manual with output signal at 50% to avoid saturating the controller.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens on pressurizer level on loss of EY-10, Preferred AC?

A

Pressuizer level begins to rise. You have approximately 3 minutes before reaching the 62.8% limit of T.S. 3.4.9. when at full power (57% starting level)

With ‘A’ Channel PPCS and PLCS in service, Charging Pumps P-55B and P-55C will start and P-55A will go to maximum speed and Letdown will be isolated. This results in PZR level rising ~ 1.95 %/min. (133 gpm - 4 gpm) / 66 gal/% = 1.95 %/min.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What happens to Tave on loss of Y-10?

A

Loop 1 Tave signal fails low.

Causes Pressurizer Level to be calculated as 42%.

Switch to Loop 2 to provide Pressurizer Level Control with a valid signal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What do you do if Tave/Tref deviation is not within 5 degrees?

A

REDUCE Reactor Power or Turbine load to lower TAVE/TREF deviation within 3F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

For West ESG sump, what must you do and why must you do it?

A

MONITOR West ESS Room Sump Level locally every 4 hours.

Due to the loss of power to the West EES Sump level and Sump Pump pressure instruments.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Why are all fuel or irradiated component handling activities stopped?

A

Proactively implements LCO 3.7.10 actions due to loss of FIC-1711 which prevents opening of Damper D-20, Air Filtering Unit V-26A Modulating Damper, which in turn prevents V-26A, Air Filter Unit VF-26A Fan, from starting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Why is T cold verified greater than 460F?

A

If it were not, LTOP would be in service.

Due to loss of power to TT-0112CA, Temperature Input to Channel ‘A’ LTOP could result in spurious actuations.

A channel is defeated if in service so that spurious actuations will not complicate event recovery when power is restored to EY-10.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Why must you bypass the A Channel Trips?

A

If the reactor is reset, then spurious RPS channel actuations can occur when
a trip unit is reenergized.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens to Left Channel CIAS on loss of Y-10?

A

A valid CHP or CHR signal results in Right Channel CIAS initiation only.

For a valid CHP you will need to:

  1. PRESS PB1-1, (LEFT) Injection Initiate, to manually actuate Left Channel SIS.
  2. OPEN CV-3001, Containment Spray Valve.
  3. START Containment Spray Pumps: P-54B & P-54C
  4. PERFORM EOP Supplement 6, “Checksheet for Containment Isolation and CCW Restoration.” to ENSURE CLOSED Left Channel CIAS valves.

For a valid CHR you will need to:

  1. PERFORM EOP Supplement 6, “Checksheet for Containment Isolation and CCW Restoration.” to ENSURE CLOSED Left Channel CIAS valves.
  2. PLACE the following ESS Sump Pump handswitches to OFF.
  • 42-155B/SS, P-72B
  • 42-165B/SS, P-73B
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What happens to the ASDV on loss of Y-10?

A

Atmospheric Steam Dumps are inoperable due to loss of EY-10.
Turbine Bypass Valve Controls and S/G Code Safety Valves are still available.

17
Q

How do you tell there is or is not a fault on the Preferred AC Bus?

A

Loss of the preferred AC bus due to the Inverter Output breaker opening indicates
that there is likely a fault on the preferred AC bus.

Loss of the preferred AC bus due to a tripped DC Input breaker when the AC
Output breaker remains closed indicates that the Preferred AC Bus is likely free of
a fault.

18
Q

What are some key equipment losses from Y-10 deenergizing?

A

A Channel Pressurizer Level Control

A Channel Pressurizer Pressure Control

Left Channel CIAS

ASDV Controller - HIC-0780A, 0780B, 0781B

West Safeguards Sump Level/Auto Pump

NI-5, Power Range NI

LTIR-0101A, RV Level/Qualified CETs

Auto Start Low Pressure on A & C CCW Pumps

Condenser Off-Gas Monitor