Z77 Safeguard and Switchgear Ventilation Flashcards

1
Q

What is the timeline once a fire is detected in the Z77 ventilation system?

A

5 sec delay supply and exhaust fans trip
30 seconds fire dampers close
45 sec CO2 valves open flooding area
50 sec Z77 fans restart

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will trip a supply fan if it is manually started?

A

Nothing, it must be manually stopped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will de-energize the heating coil?

A

Low flow or if fan trips

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is System Z77 balanced to battery room and why?

A

Provide outside air at a rate of 10 changes per hour to prevent accumulation of hydrogen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How to air operated dampers fail Z77?

A

Fail open on loss of air so fans can still be operated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How does the 10-times an hour air swap for battery rooms work?

A

The exhaust fans suck directly from battery rooms

don’t blow batteries

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Z77 How to Unit 2 fans work in relation to unit 1?

A

Unit 2 is slave to unit 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How does the red and green light indication work in the control room for supply fans?

A

Both must be running (same speed) to get a red light. Green light means either no units are running or only Unit 1 is running

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Z77 How does the light indication work in the control room for the dampers?

A

Both must be open to get a red light. Green means either one or both are closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly