Z77 Safeguard and Switchgear Ventilation Flashcards
What is the timeline once a fire is detected in the Z77 ventilation system?
5 sec delay supply and exhaust fans trip
30 seconds fire dampers close
45 sec CO2 valves open flooding area
50 sec Z77 fans restart
What will trip a supply fan if it is manually started?
Nothing, it must be manually stopped
What will de-energize the heating coil?
Low flow or if fan trips
How is System Z77 balanced to battery room and why?
Provide outside air at a rate of 10 changes per hour to prevent accumulation of hydrogen
How to air operated dampers fail Z77?
Fail open on loss of air so fans can still be operated
How does the 10-times an hour air swap for battery rooms work?
The exhaust fans suck directly from battery rooms
don’t blow batteries
Z77 How to Unit 2 fans work in relation to unit 1?
Unit 2 is slave to unit 1
How does the red and green light indication work in the control room for supply fans?
Both must be running (same speed) to get a red light. Green light means either no units are running or only Unit 1 is running
Z77 How does the light indication work in the control room for the dampers?
Both must be open to get a red light. Green means either one or both are closed.