How does the F073A/B fail?
PSW Control Valve
Open
What must you do if instrument air is lost?
Throttle F073 A/B to maintain pressure
What will trip STBY fresh air fans?
Smoke in the filter train
If the fan for CRAC A goes away what other systems do you use?
Stay Fresh air A
What mode of CRAC is used during accident conditions?
Recirc - no outside air
What is the control room envelope penetration area limit for each mode?
Modes 1,2,3-20 sq in
Modes 4,5 - 205 sq in
What crac dampers close on control room isolation?
F010/F011 inlet dampers
F003/F004 exhaust dampers
What is used to maintain positive pressure in the control building?
Utility exhaust fan
Will smoke in the intake trip the AC unit during normal operations?
Yes
Will smoke in the intake trip the AC unit during emergency operation?
No
What are the power supplies for all CRAC components?
A= 15AA B= 16AB
What is cooled by CRAC A/B?
Control Room 166’ elevation
Mezzanine 177’ elevation
Upper Control Room 189’
What type of pressure is the control room maintained and why?
Positive to Keep out the zoomies
Where does the standby Fresh Air Unit get suction from?
Recirc air from AC or outside air if safe
In a control room isolation event, How Much of the control room air is filtered by standby fresh air?
25%
What are the control room isolation signals?
- 41.6”
1. 23 psig
4. 5 mRem on the outside air intake duct(HiHi rads)
What auto starts on control room isolation?
Standby fresh air
When will the standby CRAC Unit start?
<16,500 scfm low flow on running unit if no trip signals are present
What are the trip signals for CRAC A/B?
High compressor discharge pressure >280 psig
Low compressor suction pressure <20psig
Low compressor oil pressure <30 psid
Condenser cooling water inlet valve fully closed (bypassed on the start for 5 minutes)
What Temp is the control room maintained?
70°F
Is Control Room purge manual or auto?
Always manual
What happens to control room purge on a control room isolation signal?
Trips because dampers close
Can control room purge be used during accidents?
NO
What does control room purge do?
Exhaust smoke, Freon, fumes, and other vapors from the control room
Normal and backup cooling for CRAC A/B
PSW- normal
SSW - backup
When will the standby standby fresh Air Unit auto start?
< 2000 Scfm outlet of running standby fresh air unt