G41/46 Fuel Pool Cooling and Cleanup Flashcards
Fuel pool pump trips
17% drain tank level low 400 gpm pump discharge low flow, 30s TD 8" HgVac pump pressure low, 4 sec TD 141 gpm differential flow for 45 sec ESF Load shed BUV
What signals isolate a Filter Demin? FPCCU
Hi Hi conductivity 2 umho/cm
Hi Hi precoat dP of 30 psid
Hi Hi effluent strainer dP of 10 psid
Low filter demin flow of 220 gpm after 120 s TD
Which trip will the LDS switches bypass? FPCCU
Differential flow 141 gpm for 45 seconds
What max percent level does the BWRT for FPCCU have to be at to perform a backwash?
<44%
What level trips FPCCU backwash transfer pump?
<7%
When does the fpccu holding pump turn on?
<990 gpm
When does FPCCU holding pump secure?
> 998gpm
Power supply for FPCCU pumps
A = 15AA B = 16AB
What is the FPCCU Hx cooled by? Normal and backup
CCW and SSW
What is the purpose of the skimmers?
Maintain normal pool level
What’s the purpose of the scuppers?
Maintain level during transients and prevents water from entering ventilation system
What’s the purpose of fuel pool sweep?
Sweep airborne contaminates from aux Bldg pools
What are the levels for the fuel pool drain tank?
High level 90%
Low level 30%
Low low level 17% (pump trips)
What’s the purpose of SFP diffusers?
Reduce turbulence
Prevent stagnant regions in the pool
Enhance mixing of warm water with cool water
Where does the water return to the SFP?
Bottom of pool