What’s the purpose of leak Detection?
Consists of temperature, flow, level, and pressure sensors to detect, alarm, and sometimes isolate leakage
When will RCIC isolate?
Group 4 RCIC manual isolation initiation Rx pressure low 60 psig Exhaust diaphragm pressure Hi 10psig Steam flow Hi Steam leak detection - 165°F RHR Room / 185°F RCIC and MSL
Why is there a 30 minute TD for the MSL temp isolation for RCIC? -
Allows main steam line and RWCU to isolate prior to isolate RCIC prolongs the availability of reic as a make Up source to the vessel and prevents unnecessary isolation of RCIC if the leak is from MSL OR RWCU
Where does identified leakage drain to?
Equipment drains
Where does unidentified leakage drain to?
Floor drains
When will rwcu isolate?
Group 8
Where does unidentified leakage come from?
CRD flange / Valve flange / Drywell cooling units
When will MSIVs isolate?
Group 1
What is identified leakage
Valve stems Recirc pump seals Reactor Head flange Fuel pool seal Other equipment routed to equipment drains
When is the ECCS Line break detection indication valid?
Reactor Power >80%
Core flow 790%