Week 5: Simulator Morning Questions Flashcards
What is the Point of Adding Heat?
The point at which Rx power impacts core components.
A control rod drops into the core. The plant does not trip. Describe the plant response.
Tavg goes down to counteract the negative reactivity insertion.
Describe how you would recover a dropped rod.
Lower power to 50%, open lift disconnect switches for the other RCCAs in the bank with the dropped rod, reset step counters to 0, pull dropped rod up and out.
Describe the process of transferring house loads from the Unit Aux XFMR to the Startup XFMR on a plant shutdown.
Source selector switch to startup, close the PA01 startup XFMR breaker to PA01, then close the PA02 startup XFMR breaker to PA02. When the breaker closes for each bus, the unit aux breaker for that bus should automatically open.
List all pumps that can add water to the SGs.
MFW Pumps
AFW Pumps
Startup FW Pump
Condensate Pump
List all DNB-related trips.
OTDT
RCP Undervoltage/Underfrequency
RCS Flow
PZR Low Pressure
SG Low Level
What criteria are needed to declare the reactor critical?
Constant positive SUR and increasing counts with no rod motion.
You are at 5% power on a start-up. Explain in detail how you will raise power to 15%.
Critical at 5%
Pull rods - + reactivity
Raises power - Tavg > Tsteam
Steam dumps open to control pressure
Steam flow increases = Rx power at new high level
You are conducting a startup. Explain how and why you will level power at 10^-8 amps.
Start critical, with a positive startup rate - drive the rods in until the SUR reads a little bit negative when power reads 10^-8 amps on the IR.
At this point, you are a few decades out of the source range, so you are less affected by fixed sources when taking critical data.
You are critical at 10^3 cps. You pull rods to add 50 pcm of reactivity. What is the startup rate?
SUR = 26.06[(lambdarho)/(Beta-rho)]
lambda = slow up = 0.1
Beta = BOC = 0.0065
rho = 50 pcm = 50E-5
SUR = 0.217 dpm
What are the auto SI signals?
SL pressure at 615 psig
PZR pressure at 1849 psig
CTMT pressure at 3.5 psig
N43 fails high at 100%. Explain the plant and operator response.
Rod control thinks Rx power is much higher than Turbine power, begins to step in rods to compensate. Left alone, this will drive Tavg down and Rod control will not be able to recover due to C-2 being in. The RO will confirm with BOP that there is not a load rejection occurring, and will take manual control of the rods to prevent them from erroneously inserting.
What is the minimum pressure for running a RCP?
320 psig
I&C is performing maintenance on Channel 3 PZR pressure. Channel 1 vital instrument bus feeder breaker opens. Describe your operator actions.
Channel 3 is most likely in trip during maintenance; the channel 1 bus failing open will also put all channel 1 bistables in trip, leading to a Rx trip. Operators enter E-0.
Plant is at 18% power. Main turbine trips on high S/G level. Describe the plant response.
MFW trips on the high SG level, FW isolates, SG level decreases due to shrink as turbine power goes to zero, AFW starts (due to either Lo SG level or loss of both MFW pumps).