What is the purpose of GEN-N-10?

A

To reduce plant load at power to 1%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the boration requirements of the PZR? How is this maintained?

A

PZR boron concentration must be within 50 ppm of RCS.
PZR boron concentration is equalized with the RCS via spray actuation by engaging the backup heaters.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What GEN-N-10 steps will be taken at 80% and 60% RTP?

A

A condenser demin will be taken out of service at each power level.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What GEN-N-10 steps will be taken at 50% RTP?

A

Reduce to 2 circ pumps
Reduce to 1 MFW pump
Reduce to 2 cond pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What GEN-N-10 steps will be taken at 40% RTP?

A

Stop both heater drain pumps
Reduce to 2 condenser demins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What GEN-N-10 steps will be taken at 20% RTP?

A

Transfer house loads to the startup XFMR

Take 1 demin out of service

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What GEN-N-10 steps will be taken at 15% RTP?

A

Transfer SG Level control to MFW bypass valves
Steam dumps to steam pressure mode
Control rods to manual

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What GEN-N-10 steps will be taken at 10% RTP?

A

Verify P-10, P-13, and P-7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What GEN-N-10 steps will be taken at 5% RTP?

A

Trip Main Turbine and Generator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What GEN-N-10 steps will be taken at 1% RTP?

A

Start S/U FW pump
Stop 2nd MFW pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the purpose of GEN-N-11?

A

To change the plant status from 1% to subcritical.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Describe the major steps of GEN-N-11.

A

Insert Control Banks
Verify P-6 off at < 10^-10 Amps on IR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Describe the purpose of GEN-N-12.

A

To cooldown the RCS from Hot Standby to between 335F and 345F (Hot Shutdown)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Describe the major steps of GEN-N-12.

A

Open Steam Dumps
Stop 2 RCPs
Depressurize RCS with PZR sprays
At RCS pressure < 1000 psig, isolate accumulators

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What permissives are encountered in GEN-N-12?

A

P-12 during the cooldown
P-11 during RCS depressurization

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the purpose of GEN-N-13?

A

To take the RCS from between 335F and 345F (hot shutdown) to 140F or less and ambient pressure (cold shutdown)

17
Q

What are the major steps of GEN-N-13?

A

Reduce RCS pressure to 320-360 psig
Place RHR in service
Before Tavg = 275F, arm COPS
Stop 1 cond pump (1 left)
Stop last Circ water pump
At Tavg = 160F, stop remaining RCPs

18
Q

What are the requirements for placing RHR in service?

A

Tavg < 350F
320 psig < RCS Pressure < 360 psig