Turbine trips Flashcards
State Low Main Shaft Oil Pump Discharge Pressure Trip
100# 2/3, only if Turbine is >1350 RPM
State Low Bearing Oil Header Pressure trip
12# 2/3
Low EHC pressure trip
1100# 2/3
Low ETS trip
> 200# 2/3
Loss of Generator Stator winding coolant trip
After 2 min of runback if generator armature current is not less than 25,000 amps or
after 3.5 min of runback if generator armature current is not less than 7,000 amps then the turbine will trip
High MSR/ Drain tank level
if level is 3” below top of shell for >10 seconds 2/3 thne the turbine will trip
High LP exhaust hood temp
2/3 @ 225F
Low Exhaust hood vacuum
2/3 @ 22.4” HgV
State Turbine trip on High vibrations
11 mils on 2/2 for >3 seconds
State turbine trip on High thrust wear position
2/3 @ 35 mils
State turbine trip on Turbine Overspeed
110% or 110.5% primary/emergency overspeed
Turbine speed probe failure
Any speed probe failure
Discuss Manual turbine trip
Both Manual push buttons on the front standard or MCB