SA/IA Flashcards
State when SA-V-92/93 close and when they can open
Close at 90#
can manually open at 95#
State Lead Lag SA compressor setpoints
LEAD: 115 - 125#
LAG: 110 - 120#
State SA compressor response on LOP
SA-C-A and B will restart at step 9 of EPS
State Sullair compressor response on LOP
Will start if SA header pressure dips below 100#
State how to reset Containment Air compressor
Local push button
OR
Cycling the breaker at MCC-531/631
Discuss how the ring headers are protected
Isolation valves and check valves ensures separation
State MCB indication for compressed air
IA-V-530 CS
SA-V-92/93 CS
Containment air compressors CS
IA/SA/Containment Air Pressures
State what loads have backup N2
EFW turbine Steam supply valves
ASDVs
PCCW TCV and HX Bypass
State impact of loss of IA
ON1242.01 addresses this
- Need to manually start compressors
- Isolate SA
- Rx trip and RCP shutdown
State what closes IA-V-530
Fails closed on LOP and T-signal
State what’s used for loss of containment IA
ON1242.02
Open IA-V-530