EHC Flashcards

1
Q

State what the wobbulator does for the turbine

A

At 1500 RPM the turbine is unstable so the wobbulator

changes speed by 50RPM every 6 min 1450, 1500, 1550

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State the speed that the TG switches to Auto Voltage Regulator mode

A

270 RPM

The exciter will auto start if the TG reaches 1710RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

State precaution with using the Manual Raise lower buttons in the DCS

A

There is no confirmation box. Once you release the box the load setpoint is changed and ramp rate is 600%/HR (10%/min)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State the precaution with using the Remote Raise lower switch on the MCB

A

Make small adjustments to avoid excessive power transients.
This switch interfaces directly with the DEHC cabinets
increases load at 600%/HR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State how a turbine Runback affects the DCS

A

A Runback will adjust the load setpoint at the Runback rate.

The Load Limit will Track down with it staying 5% above the setpoint as long as Tracking is on.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

State how a turbine Setback affects the DCS

A

A Setback will lower the Load limit at the Setback ramp rate. The Load Limiter tracking function is automatically turned off. The Load setpoint also changes to 2% above the Load Limit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

State how the Load Limiter tracking function operates

A

The Load Limiter tracker will auto follow 5% above Load Actual

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

State the Turbine Runback signals

A
  • Stator Cooling water high outlet temp 2/3 @
    176F, 80C
  • Low Stator Inlet Pressure 2/3 @ 586 GPM (50#)
  • Low Flow to High Volt Bushing 2/3 @ 47 GPM
  • Stator inlet flow Low 2/3 @ 586 GPM
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

State Turbine Runback rate

A

Runback reduce load @ 30%/min
Runbacks to 22.1%
with a 15 second time delay to prevent spurious actions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

State Turbine trip from Runback signals

A

After 2 minutes if armature current is not less than 25,000 amps then the turbine will trip
After 3.5 minutes if armature current is not less than 7,000 amps then the turbine will trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

State the Load Limit Ramp rates

A

Fast: 10%/second
Slow: 1%/second

How well did you know this?
1
Not at all
2
3
4
5
Perfectly