GSC Flashcards
State normal GSC flow to stator and HV bushing
700 GPM to stator
85 GPM to HV bushing
State purpose of Pressure Control valve CV-Y-63
Maintains GSC pressure 3# less than H2 pressure
State what will auto start standby GSC pump
A pressure switch senses when GSC pump discharge pressure is less than 10# of normal
Another pressure switch will activate at 20# less than normal
State GSC runbacks
Stator return temperature high - 80C
Stator supply low inlet pressure - 50#
Stator Coolant flow low - 586GPM
High Voltage bushing flow low - 47GPM
State response time and rate of runback
There is a 15 sec TD before initiation
Runback at a rate of 30%/min
State Turbine Trip on GSC runback
If after 2 minutes Amps are not <25,000 then Turbine trip
If after 3.5 minutes Amps are not <7,000 then Turbine Trip
State action on high-high conductivity
At 9.9 mhos/cm VAS states to trip turbine