State the function of the Steam Dump system
Prevents plant trips following a 50% load reduction with auto control rods
Returns plant temperature to a zero load value (557) following a plant trip
Creates an artificial steam load during turbine startup and shutdown to ensure smooth reactor load shifts
Provides a means of cooling down the reactor plant following reactor shutdown
State Arming signals for Steam dumps
C-7a, turbine load reduction arming, sensed from PT-506
P-4, A-train reactor trip and bypass breaker opened
Steam Pressure mode
C-9, condenser available
State Blocking signals for Steam dumps
C-9, if condensers are not available
P-12, Lo-Lo Tave 550F (2/4)
Manual, place the P-12 bypass switches to off
Discuss how and why the steam dump valves are arranged
4 banks open sequentially, this provides a smooth linear response to steam flow increases
Total capacity: 6.4X10^6 lbm/hr
1 valve = 3.33%
Discuss how Steam Dumps trip open on Load Reduction
Banks 1 and 2 will open at 8.1F Tave-Tref
Banks 3 and 4 will open at 14.2F Tave-Tref
Discuss how Steam Dumps trip open on Reactor Trip
Banks 1 and 2 will open at 15F Tave-Tref
Banks 3 and 4 will open at 30F Tave-Tref
State why the load reduction-arming signal (C-7a) is provided with seal-in memory logic
The seal-in memory logic allows the steam dumps to remain armed once the transient has stopped
State why two pressure transmitters are required for the load reduction logic
two transmitters are used to prevent inadvertent opening of steam dumps due to a single instrument failure