Discuss SGWLC Level lag
Level deviations have a 5 second lag to minimizes the effects of shrink and swell
Discuss how the SGWLC flow controller develops a signal
Feed Flow develops and error signal
and/or
Level develops an error signal
SGWLC output = Feed error plus Level error
Discuss Feed pump speed Control
DP is sensed from PT-507 and PT-508.
Programmed DP is sensed from all 4 SG steam flow (selected channel for SGWLC)
0-20%:80#
20-1005: 135#
State FWI signals
P-14: SG Hi-Hi Level (90.8% 2/4 in any SG)
P-4 with Low Tave (557F 2/4)
Any SI signal
Discuss train specific actions for FWI signal
A train: SUFP, A MFP
B train: B MFP
State FWI auto actions
FRVs, FRV bypasses, FW Isolation Valves all close MFPs trips (train specific) Turbine trips (when caused by P-14 or SI) SUFP blocked (A train P-14 or SI)
State how to reset FWI
FWI reset switches on MCB (P-4 only)
Cycle Reactor trip breakers (SI or P-14)
State what must happen if Containment Integrity is lost (T.S. 3.6.1.1) modes 1-4
Without primary CONTAINMENT INTEGRITY, restore CONTAINMENT INTEGRITY within
1 hour or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN
within the following 30 hours.
State what happens when the Controlling Level Channel fails high
FRV closes and Rx trips on 2/4 SG level Lo-Lo (20%)
State what happens when the Controlling Level Channel fails low
FRV opens
P-14 FWI and turbine trip (RX trip of >P-9)
- 2/4 SG Hi-Hi 90.8%
State what happens when the Controlling Feed Flow Channel fails high
FRV closes on error signal
Final SG level 42-44%
State what happens when the Controlling Feed Flow Channel fails low
FRV opens due to error signal
SG level will be >80%, possible P-14 due to overshoot and turbine trip
State what happens when Steam Flow Channel fails high
FRV opens due to flow error,
This will be balanced by level error
FRV closes back to original position
State what happens when the Steam Flow Channel fails low
FRV closes due to error
Rx will trip on Lo-Lo SG Level (2/4 @20%)
State what happens when PT-508 fails high or PT-507 fails low (max DP)
MFPs slow down to minimum (3700 RPM)
RX trips on SG level Lo-Lo (2/4 @ 20%)