SGWLC Flashcards

1
Q

Discuss SGWLC Level lag

A

Level deviations have a 5 second lag to minimizes the effects of shrink and swell

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Discuss how the SGWLC flow controller develops a signal

A

Feed Flow develops and error signal
and/or
Level develops an error signal
SGWLC output = Feed error plus Level error

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Discuss Feed pump speed Control

A

DP is sensed from PT-507 and PT-508.
Programmed DP is sensed from all 4 SG steam flow (selected channel for SGWLC)
0-20%:80#
20-1005: 135#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State FWI signals

A

P-14: SG Hi-Hi Level (90.8% 2/4 in any SG)
P-4 with Low Tave (557F 2/4)
Any SI signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Discuss train specific actions for FWI signal

A

A train: SUFP, A MFP

B train: B MFP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

State FWI auto actions

A
FRVs, FRV bypasses, FW Isolation Valves all close
MFPs trips (train specific)
Turbine trips (when caused by P-14 or SI)
SUFP blocked (A train P-14 or SI)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

State how to reset FWI

A

FWI reset switches on MCB (P-4 only)

Cycle Reactor trip breakers (SI or P-14)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

State what must happen if Containment Integrity is lost (T.S. 3.6.1.1) modes 1-4

A

Without primary CONTAINMENT INTEGRITY, restore CONTAINMENT INTEGRITY within
1 hour or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN
within the following 30 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

State what happens when the Controlling Level Channel fails high

A

FRV closes and Rx trips on 2/4 SG level Lo-Lo (20%)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

State what happens when the Controlling Level Channel fails low

A

FRV opens
P-14 FWI and turbine trip (RX trip of >P-9)
- 2/4 SG Hi-Hi 90.8%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

State what happens when the Controlling Feed Flow Channel fails high

A

FRV closes on error signal

Final SG level 42-44%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

State what happens when the Controlling Feed Flow Channel fails low

A

FRV opens due to error signal

SG level will be >80%, possible P-14 due to overshoot and turbine trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

State what happens when Steam Flow Channel fails high

A

FRV opens due to flow error,
This will be balanced by level error
FRV closes back to original position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

State what happens when the Steam Flow Channel fails low

A

FRV closes due to error

Rx will trip on Lo-Lo SG Level (2/4 @20%)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

State what happens when PT-508 fails high or PT-507 fails low (max DP)

A

MFPs slow down to minimum (3700 RPM)

RX trips on SG level Lo-Lo (2/4 @ 20%)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

State what happens when PT-508 fails low or PT-507 fails high (min DP)

A

FRV close due to flow error and then level error
Final Level 50%
FW pressure high alarm