CO Flashcards

1
Q

State auto actions for decreasing condenser vacuum

A
Normal: >27"
MPCS alarm: 27"
AR pump auto start: <26"
Steam Dump Block: 25"
Alarm: 24.9"
Turbine trip: 22.4"
MFP trip: 18.5"
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Discuss the Flow of air through the AR pump

A

At <2” HgV the inlet valve opens
<23” HgV the interstage check valve is closed
once at NOP (28” HgV) the exhaust is directed to the PAB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

State the CO pump start permissive

A

SCCW flow must be:
>26GPM to left nd right air cooler
>5 GPM to the bearing oil cooler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State auto start of CO pump

A

CO start permissive must be satisfied
<250# MFP suction (1/2)
or any running CO pump trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When does the short term recirc valve open

A

> 490# CO pump discharge pressure

allows 2300 GPD flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Discuss exhaust hood spray

A

Starts to open at 140F, full open at 200

Turbine trip at 225F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Discuss Long term recirc

A

6000 GPM per running pump after SPE back to hotwells

>330# for >10 seconds for valve to open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Discuss CO-V-75

A

Opens when any other inlet or outlet in the 21 or 22 heaters go close.
Recloses by operator after all inlets and outlet are open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

State sources of steam for CO heaters

A
HTR - Stage
21 - 12th stage LP
22 - 11th stage LP
23 - 9th stage LP
24 - 8th Stage LP
25 - 7th Stage HP
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Discuss Hotwell level control Make up valve

A

Auto opens at -3”
Closes at 0”
Deenergizes at 233K CST level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

State Hot Well Level setpoints

A
\+9" MPCS High alarm
0" Normal water level
-3" Make-up valve opens, closes at 0"
-6" MPCS Low alarm
-12" MPCS Low-Low alarm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly