State auto actions for decreasing condenser vacuum
Normal: >27" MPCS alarm: 27" AR pump auto start: <26" Steam Dump Block: 25" Alarm: 24.9" Turbine trip: 22.4" MFP trip: 18.5"
Discuss the Flow of air through the AR pump
At <2” HgV the inlet valve opens
<23” HgV the interstage check valve is closed
once at NOP (28” HgV) the exhaust is directed to the PAB
State the CO pump start permissive
SCCW flow must be:
>26GPM to left nd right air cooler
>5 GPM to the bearing oil cooler
State auto start of CO pump
CO start permissive must be satisfied
<250# MFP suction (1/2)
or any running CO pump trip
When does the short term recirc valve open
> 490# CO pump discharge pressure
allows 2300 GPD flow
Discuss exhaust hood spray
Starts to open at 140F, full open at 200
Turbine trip at 225F
Discuss Long term recirc
6000 GPM per running pump after SPE back to hotwells
>330# for >10 seconds for valve to open
Discuss CO-V-75
Opens when any other inlet or outlet in the 21 or 22 heaters go close.
Recloses by operator after all inlets and outlet are open
State sources of steam for CO heaters
HTR - Stage 21 - 12th stage LP 22 - 11th stage LP 23 - 9th stage LP 24 - 8th Stage LP 25 - 7th Stage HP
Discuss Hotwell level control Make up valve
Auto opens at -3”
Closes at 0”
Deenergizes at 233K CST level
State Hot Well Level setpoints
\+9" MPCS High alarm 0" Normal water level -3" Make-up valve opens, closes at 0" -6" MPCS Low alarm -12" MPCS Low-Low alarm