State T.S. level of CST

A

212,000 gallons

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State min flow requirements for the EFW pumps

A

225 GPM/ 222GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Discuss opening MS-V-393/394 and 395

A

MS-V-393/394 opens first and then 28 seconds later MS-V-395 opens, this allows for moisture to be removed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State what causes an EFW actuation

A
LOLO SG Level <20% 2/4 NR on 1 of 4 SGs
SI
LOP
AMSAC, 3/4 SG's NR <13% and >20% power 2/2
- Actuation isolates SB
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State how train separation for EFW FCVs and Basis

A

A/C SG FCV are A then B train
B/D SG FCV are B then A train
Only the “bench section” valves are throttled for each S/G
This ensures that a loss of 1 vital power supply will not result in a complete loss of flow to all SG’s

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Discuss the EFW flow venturi

A

Limits flow to 750 GPM

Provides flow indication to RSS panels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Discuss the EFW Flow Orifice

A

Provides indication to MCB

Closes EFW flow control valve on high flow 565 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

State actions for loss of all 3 EFW pumps T.S. 3.7.1.2

A

Loss of all three requires immediate corrective action to restore at least one pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

State how RSS switches can affect EFW

A

RSS switch in local will defeat the high flow isolation scheme from the flow orifice