SB Flashcards

1
Q

State closing signals for SB IRC valves

A

Flash tank HI-HI pressure 65#
Flash tank high level 50%
A HELB signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State Closing signal for SB ORC valves

A

B HELB
EFW actuation
T Signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Discuss Where BD flash tank vapor is aligned and how

A

<10% power to C Condenser
>10% to HTR 23C
pressure is controlled to 55# via PCV-1926-1
Can go to atmosphere via PCV-1926-2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Discuss SB Bottoms coolers

A

normal outlet temp: 115F
High temp: 200F
on high temp SB-CV-6519

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State normal BD flash parameters

A

Level: 20%
Pressure: 55#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

State which valve controls level in the BD flash tank depending on alingment

A

Ocean: SB-LCV-1909
Condenser: SB-LCV-1909-1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

State closing signals for SB-CV-6519

A

High rad signal from SB rad monitors

High Bottom coolers outlet temp (200F)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

State setpoints for the SB Recovery HX

A

115F: SB-V-398 opens to bypass HX
120F: Alarm at SB panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Discuss which valves close on a HELB signal

A
SB IRC valves: Train A
SB ORC valves: Train B
CS-V-149: IRC Train A
CS-V-150: ORC Train B
AS-V-175: Train A
AS-V-176: Train B
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Discuss the operation of the SB Isolation Bypass Switches

A

Train related switches bypasses signals for ORC SB isolation valves
Train A bypasses MS-V-393 and 394 switches
Train B bypass switches for B EFW pump and MS-V-394 B Train switches
HELB and T Signals are not affected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly