PK: Class 125VDC Flashcards
1
Q
How long will the Class Batteries provide power on a loss of AC?
A
2 Hours
2
Q
What prevents the Class Battery Swing Chargers from being aligned to two PK buses at the same time?
A
A mechanical interlock
3
Q
What from the PK system is required to operate SIC-653 or SID-654?
A
The Battery and the Battery Charger both have to be on the bus
4
Q
What happens to the DG if its control power from PKA or PKB is lost?
A
- If its running, it will trip and the output breaker will remain closed causing the DG to motorize.
- If its not running, it won’t start