CO: Control Oil Flashcards
Which valves in the Main Turbine System does CO operate?
Control Valves
Stop Valves
Intercept Valves
How many pumps does the CO System have? How many are normally running?
2
1 running, 1 in standby
What is normal discharge pressure for a CO pump?
1600 psig
At what pressure will the standby CO pump start?
1300 psig as long as its not in PULL-TO-LOCK
How does a CO pump get an amber Control Room light?
Auto start with the pump originally ‘Green Flagged’
How do the CO pumps maintain a constant discharge pressure with changing system demand?
They vary their pump stroke on system demand
How is cooling and lubrication supplied to the CO pumps?
Via a chain driven aux pump
When do the CO pump discharge filters alarm?
100 psid
What temperature is the CO reservoir maintained?
> 85F
How many inches in the reservoir is 1 barrel?
4”
How many accumulators does the CO system have?
4
What are the CO accumulators charged with? To what pressure?
N2
1000 psig
What is the capacity of the CO system accumulators?
200% for transients
How many coolers does the CO system have? What cools them?
2
TC
What is the purpose of the Fullers Earth Filters?
They maintain the pH of the oil neutral by absorbing water and acids.