Matt's Initial Driver Bible Flashcards
Important sentences from P&A 3rd Ed./ Truck 2nd Ed./Strategy and Tactics 3rd Ed.
- NFPA 1901, Standard for Automotive Fire Apparatus, contains the requirements of pumper design. The standard specifies a minimum pump capacity of ____ gpm and a water tank with a capacity of at least ____ gallons. Pump 14.
- 300
- Pump capacities larger than 750 gpm increase in increments of ____ gpm with most municipal fire departments operating pumpers of _______ gpm or less. Pump 14.
- 2000
- The foam proportioning systems commonly found on municipal fire pumpers are scaled down versions of those used for industrial fire pumpers. Likewise, the foam tanks are correspondingly smaller, usually ranging from ___ to ____ gallons. Pump 16.
20 to 100
- TQ** The articulating or telescoping devices most commonly combined with pumpers generally range in height from ____to ____ feet. Pump 16.
- 50 to 75
- Mini-Pumper. — Small fire apparatus mounted on a pickup-truck-sized chassis, usually with a pump having a rated capacity less than _____ gpm. Its primary advantage is speed and mobility, which enables it to respond to fires more rapidly than larger apparatus. Pump 16.
- 500
- Midi-Pumper. — Apparatus sized between a mini-pumper and a full-sized fire department pumper, usually with a gross vehicle weight of _______ pounds or greater. The midi-pumper has a fire pump with a rated capacity generally not greater than _____ gpm. Pump 16.
- 12,000. 1000
- Mobile water supply apparatus, as stated in NFPA® 1901, Chapter 7, are equipped with a tank capacity of at least _______ gallons. Pump 17.
- 1000
- Specially designed wildland apparatus are often mounted on ______or larger chassis, usually featuring all-wheel drive. Pump 19.
- one-ton
- Commonly known as brush trucks, brush breakers, or booster apparatus, these vehicles often have pump capacities and water tanks of _____ gallons or less. However, some jurisdictions operate larger apparatus with pumps up to 1,000 gpm and water tanks of 1,000 gallons or larger. Pump 19.
- 500
IFSTA does not recommend riding on the outside of the apparatus, and this practice is prohibited by NFPA ______ Standard on Fire Department Occupational Safety and Health Program.
- NFPA 1500. Fire Department Occupational Safety and Health Program
- Requirements for ARFF apparatus are found in NFPA _______, Standard for Aircraft Rescue and Fire-Fighting Vehicles. Pump 20.
- NFPA 414
Some fireboats have capacities as high as __________ gpm. Pump 21.
- 50,000
A quint is an apparatus equipped with a fire pump, water tank, and hose, in addition to an aerial device and ground ladders. According to the NFPA® 1901, Standard for Automotive Fire Apparatus, the vehicle must be equipped with a pump rated at a minimum of _______ gpm and a water tank of at least _______ gallons. Pump 22.
- 1000, 300
Portable generators are available with a variety of power capacities; _________watts is typically the largest capacity. Pump 23.
- 5,000
Rescue apparatus or other specialized units may feature fixed generator systems with capacities of ___________ watts or greater. Pump 23.
- 50,000
Ranging from _______to _______watts, portable lights are advantageous during incidents where illumination is needed some distance away from a piece of apparatus, or where additional lights are required. Pump 23.
- 300 to 1000
- Driver/ operators in many jurisdictions are required to perform these routine maintenance checks and functions. NFPA _______ also requires that driver/operators be skilled in the performance of certain maintenance tasks. Pump 29.
- NFPA 1002
- NFPA®___________, Standard for Emergency Vehicle Technician Professional Qualifications, provides a basis to train and certify fire apparatus mechanics and fire department maintenance officers. Pump 29.
- NFPA 1071
- TQ**___________________________— Inspecting an apparatus and equipment on the apparatus to ensure that all equipment is in place, clean, and ready for service. Pump 36.
- Operational Readiness Inspection
- ______________________________— A visual inspection of an apparatus to ensure the major components of the chassis are present and in proper working condition. Pump 36.
- Pre-trip Road Worthiness Inspection
- ____________________— An inspection where a certain system or component of an apparatus is operated to ensure that it is functioning properly. Pump 36.
- Functional Check
- CAUTION: Diesel exhaust may contain up to _______ harmful chemicals and compounds. Pump 37.
- 100
NFPA® 1911 requires that all tires be replaced every _______ years, regardless of their condition. Pump 39.
- Seven
- In general, steering wheel play should be no more than approximately _______degrees in either direction. Pump 40.
- 10
- On a 20-inch diameter steering wheel, the play may be about ______ inches in either direction. Pump 41.
- 2
Per NFPA® 1901 and 1911, a side-to-side variance in weight should not exceed ______ percent. Pump 42.
- Seven
- Most commercial and private vehicles built since 1990 are equipped with____________________________. Pump 42.
- Anti-Lock Braking Systems
- Apparatus with air brakes are to be equipped with an air pressure protection valve that prevents air horns or other nonessential devices from being operated when the pressure in the air reservoir drops below ______ psi. Pump 43.
- 80
- In addition to a DPF system, engines produced after January 1, 2010, may be equipped with an exhaust after-treatment system called____________________________. Pump 45.
- Selective Catalyst Reductant (SCR)
- NFPA®_______ , Standard for Fire Apparatus Driver⁄Operator Professional Qualifications, has established minimum qualifications for apparatus driver/ operators. Pump 79.
- NFPA 1002
A periodic medical evaluation, in accordance with the NFPA_______, Standard on Fire Department Occupational Safety and Health Program, should be administered under the direction of the authority having jurisdiction (AHJ) in order to establish and maintain a driver/operator’s fitness for duty. Pump 82.
- NFPA 1500
- NFPA ________, Standard on Comprehensive Occupational Medical Program for Fire Departments, provides specific standards that contain information and specific details on uncorrected vision and diseases of the eye. Pump 82.
- NFPA 1582
- NFPA _________ contains a list of frequencies that a driver/ operator must be able to hear and recommends rejecting a candidate who has hearing loss among those frequencies. Pump 82.
- NFPA 1582
- In a study conducted by the Society of Automotive Engineers (SAE), it was determined that in _____ percent of all collisions, the driver/operator was not aware of a problem until it was too late to correct. Pump 88.
- 42 percent
- NFPA ________, Standard for Automotive Fire Apparatus, and NFPA _______, Standard on Fire Department Occupational Safety and Health Program, establish requirements for seat belt use on the apparatus. Pump 90.
- NFPA 1901, NFPA 1500
- Beginning with engines produced in_________, apparatus began to be equipped with a diesel particulate filter (DPF). Pump 94.
- 2007
- After a driver/operator continues to ignore an empty DEF tank, the apparatus may be limited in speed to _______ mph and will need service from the dealer. Pump 95.
- 5 mph
- TQ** Weigh the apparatus after loading it with all equipment and personnel to ensure that the axle loading is balanced within _______ percent from side to side and within the axle weight ratings front-to-back. Pump 98.
- 7 percent
- There are ________ locations in the U.S. where there is less than 100 feet following the railroad tracks.
- 19,824 locations
- It may take ____to ____ times greater distance for a vehicle to come to a complete stop on snow and ice than it does on dry pavement. Pump 99.
- 3 to 15 times greater
- At speeds above _____ mph , an emergency vehicle may outrun the effective range of its audible warning device. Pump 101.
- 50 mph
- In some instances, increasing the speed of an apparatus by 20 mph can decrease the audible distance by _____ feet or more. Pump 101.
- 250 feet or more
- *When more than one emergency vehicle is responding along the same route, they should travel at least ________to _______ feet apart. Pump 101.
- 300 to 500 feet
- NFPA 1901 requires that all apparatus with a GVWR of _________ lb or greater be equipped with an auxiliary braking system. Pump 109.
- 36,000 lb
- TQ** The ____________is the least capable of the four auxiliary brake devices. Pump 110.
- Exhaust brake
- ** When preparing to back the apparatus, the spotter should be positioned in the vision of the driver/operator, preferably in the left (driver’s side) mirror, approximately ___ to ____ feet behind and slightly to the left of the apparatus. Pump 114.
- 8 to 10 feet
- At 5 mph, ______feet of hose is pulled out each second. Pump 120.
- 7 feet
- TQ** NFPA 1901 specifies that any equipment not needed while driving to the scene must be secured in brackets or contained in a storage cabinet. The bracket or cabinet must be capable of restraining the equipment against a force of up to _____ times the equipment’s weight. Pump 120.
- Ten times
- High pressure hydraulic fluid at pressures as low as _____ psi can penetrate skin. Pump 122.
- 100 psi
- Apparatus may be equipped with manually applied tire chains or automatic chains featuring short lengths of chain on a rotating hub in front of each drive wheel. The hubs swing down into place upon activation from the cab. The hub with chains attached is driven by the drive wheel and the lengths of chain are spun under the tire by centrifugal force. These chains maybe ineffective in snow deeper than ___to ___ inches depending on consistency of the snow, or when the vehicle is moving at very slow speeds, or in reverse.
- 3 to 6 inches
- Depending on the incident, apparatus, equipment, and personnel operating within _____ feet of the base of a high-rise fire may need to be protected from falling glass and debris. Pump 139.
- 200 feet
- In tandem pumping operations apparatus may be located up to _____ feet apart. Pump 146.
- 300 feet
- NFPA ______, Standard for the Inspection, Care, and Use of Fire Hose, Couplings, Nozzles, and the Service Testing of Fire Hose, contains test pressures for various types of fire hose. Pump 146.
- NFPA 1962
- Because it is not always possible to stop the flow of trains on a track during emergency operations and it may require _____ to _____ miles for a fully loaded train to make a complete stop, fire apparatus should never position on railroad tracks. Pump 154.
- One to two miles
- Apparatus should maintain a clear zone of at least _____ feet from railroad tracks to prevent contact with objects on the railroad cars. Pump 154.
- 30 feet
- TQ** Water’s density, or its weight per unit of volume, is measured in pounds per cubic foot. For fire protection purposes, ordinary fresh water is considered to weigh ____lb/ft3 gal or _____ lb/gal. Pump 167.
- 62.4 lb/ft3 gal or 8.3 lb/gal
- Methylene Chlorides’ specific gravity is _____. Pump 168.
- 1.33
- Gasoline’s specific gravity is _____-_____. Pump 168.
- 0.72-0.76
At 212°F (100°C), water converted to steam occupies approximately ______ times its original volume, helping to dissipate heat in a well-vented room. Pump 169.
- 1,700 times
- Shut down the engine immediately if oil pressure gauge does not fall within manufacturers recommendations within ____to _____ seconds. Pump 125.
- 5 to 10 seconds
- The ________ at which a fluid travels through a hose or pipe is determined by the pressure upon that fluid as well as the size of the orifice through which it is flowing. Pump 172.
- Speed
- ______ principles determine the action or pressure on fluids. Pump 172.
- Six
First Principle.
63. Fluid pressure is __________________to any surface on which it acts.
Pressure exerted by the weight of the water is _____________________ to the walls of the container.
- Perpendicular, perpendicular
Second Principle.
64. Fluid pressure at a point in fluid at rest is the same ___________ in all directions.
This principle is used in hydrostatic testing.
- Intensity
Third Principle.
65. Pressure applied to a confined fluid is transmitted __________ in all directions.
- Equally
Fourth Principle.
66. The pressure of a liquid in an open vessel is proportional to its_________.
- Depth
Fifth Principle.
67. The pressure of a liquid in an open vessel is proportional to the ________ of the liquid.
- Density
Sixth Principle.
68. The pressure of a liquid at the bottom of a vessel is _____________ of the shape of the vessel.
- Independent
- A common method of measuring atmospheric pressure is by comparing the weight of the atmosphere with the weight of__________. When observing a vertical cylinder, the greater the atmospheric pressure, the taller the column of ______________. A pressure of 1 psi makes the column of mercury about 2.04 inches tall. At sea level, the column of mercury is 2.04 x 14.7, or ______ inches tall. Pump 174.
- Mercury.
mercury.
29.9 inches tall.
- Head — Alternate term for pressure, especially pressure due to elevation. For every 1-foot increase in elevation, _______ psi is gained. Also known as Head Pressure. Pump 175.
- 0.434
- To convert head in feet to head pressure, you must divide the number of feet by ______(the number of feet that 1 psi will raise a one square inch column of water). Pump 175.
- 2.304
- Above sea level, atmospheric pressure decreases approximately _____ psi for every 1,000 feet. Pump 176.
- 0.5 psi
- The friction loss in older hose may be as much as _____ percent greater than that of new hose.
- 50 percent
- First Principle.
If all other conditions are the same, friction loss varies directly with the ______ of the hose or pipe.
- Length
- Second Principle.
When hoses are the same size, friction loss varies approximately with the ___________ of the increase in the velocity of the flow.
NOTE: Velocity is proportional to flow.
- Square
- Third Principle.
For the same discharge, friction loss varies __________ as the ______ power of the diameter of the hose.
Whenever possible the driver/operator, in conjunction with the unit officer, should consider using larger diameter hose sizes to reduce friction loss.
- Inversely,
fifth power
- Fourth Principle.
For a given velocity, friction loss is approximately the same, regardless of the _________ on the water.
- Pressure
- With water being virtually incompressible, a pressure of _________ psi is required to reduce its volume one percent. Pump 179.
- 30,000 psi
- The _______________________________is the average amount of water used per day based on the total amount of water used in a water distribution system over the period of one year.
- average daily consumption (ADC)
- The _____________________________ is the maximum total amount of water that was used during any 24-hour interval within a 3-year period.
- maximum daily consumption (MDC)
- The _______________________________is the maximum amount of water used in any 1-hour interval over the course of a day. Pump 188.
- peak hourly consumption (PHC)
- A fog stream may be produced by_____________________, by_____________________, or a combination of these methods.
- deflection at the periphery,
impinging jets of water
- Most constant flow nozzles feature a ____________________stream and are equipped with an adjustable pattern range
- periphery-deflected stream
- Most constant flow nozzles are designed to operate at a nozzle pressure of ______ psi.
- 100 psi
- Nozzles for use on handlines may be solid, fog, or broken stream design, ranging in size from a ____inch “booster” nozzle to a nozzle suitable for a ___inch diameter hoseline. Page 199.
- ¾ inch, 3 inch
- Operating at a pressure of up to _____ psi, high pressure fog nozzles produce a stream with significant forward velocity, but a relatively low volume of water delivery.
- 800 psi
- Featuring a stream of fast-moving, fine spray, high-pressure fog nozzles may use an impinging stream. These nozzles are best suited for wildland fires and are not recommended for structural fire fighting due to their low water flow of only ____ to _____ gpm.
- 8 to 15 gpm
- The piercing nozzle is generally designed as ___ to ___ foot hollow steel rod _____ inches in diameter.
- 3 to 6 foot, 1 ½ inches in diameter
- Flowing only ____ to _____ gpm at a nozzle pressure of ______ psi, the impinging holes of the chimney nozzle produce a very fine mist which turns to steam in the hot interior of the chimney flue. Pump 201.
- 1.5 to 3 gpm, 100 psi
- As water is discharged from a nozzle at a given pressure, a counterforce pushes back against firefighters operating the hoseline. This force, called nozzle reaction, illustrates Newton’s ________ Law of Motion: For every action there is an equal and opposite reaction.
- Third law of motion
- TQ** When two hoselines of equal length are Siamesed to supply a fire stream, friction loss is approximately _____ percent less than that of a single hoseline at the same nozzle pressure.
- 25 percent
- The following are safe and efficient nozzle pressures for common fire streams:
Solid stream nozzle (handline) = ___ psi
Solid stream nozzle (master stream) = ___ psi
Fog nozzle = ____ psi
Low pressure fog nozzle = ___ or ___ psi.
50
80
100
50 or 75
- Based on the NFPA 1901 standard, for every discharge outlet equipped with a flowmeter, a pressure gauge shall also be provided. These flowmeters must display flow in increments of _____ gpm or less. Pump 282.
- 10 gpm
- With proper calibration, a flowmeter in good working order should be accurate to a tolerance of plus or minus ____ percent.
- 3 percent
- Each discharge equipped with a flowmeter must have a digital readout display mounted within ______ inches of the control valve for that discharge. If a pressure gauge is mounted at the ___-inch location, then the flowmeter must be mounted within _____ inches adjacent to the pressure gauge.
- 6 inches.
6 inch.
2 inches.
Driver/operators must be aware of the margin of difference when using the Condensed Q formula. Although sufficient for many fireground calculations, the friction loss results will be ________ percent greater than when using the FL= CQ2L formula.
- 20 percent greater
- TQ** ___________________are constructed with moveable elements that automatically compensate for wear, maintaining a tighter fit with closer clearances as the pump is used.
- Rotary Vane pumps
- Pumps used in the fire service constructed with a single impeller are referred to as single-stage centrifugal pumps. These may consist of front-mount pumps, power take off, auxiliary engine driven, and midship pumps that use a single intake impeller and a simple casing to provide flow capacities up to _______ gpm.
- 2,250 gpm
- When the pump transfer valve is in the _______ position, each of the impellers takes water from a source and delivers it to the discharge. Each of the impellers is capable of delivering its rated pressure while flowing _____percent of its rated capacity; therefore, the total amount of water the pump can deliver is equal to the sum of the stages.
- Volume. 50 percent
- When the transfer valve is set in the ________position, all water from the intake manifold is directed into the eye of the first impeller. Depending on the specific pump, the first stage increases the pressure and discharges ____ to ____ percent of the volume capacity through the transfer valve and into the eye of the second impeller.
- Pressure position. 50 to 70 percent
- In the parallel mode, the pump will be capable of supplying 100 percent of its rated capacity at _____ psi at _____ feet of lift with ____ feet of suction hose while drafting.
- 150 psi. 10 feet of lift. 20 feet of suction hose
- Many power-operated transfer valves operate at pressures as high as _____ psi.
- 200 psi
- In the past, conventional PTO units were limited to powering pumps up to approximately ____ gpm. However, some manufacturers now provide full torque power take-offs that allow for the installation of pumps as large as ______ gpm. Pump 308.
- 500 gpm. 1,250 gpm
- With the engine idling and the pump engaged, most speedometers will indicate between ____ to ____ mph.
- 10 to 15 mph
- The piping system and the fire pump itself must be capable of withstanding a hydrostatic test of ______ psi before being placed into service. Pump 312.
- 500 psi
- According to NFPA® 1901 pumpers with a capacity of 500 gpm or less should have piping capable of flowing _____ gpm.
- 250 gpm
- Pumpers with a capacity greater than 500 gpm should be able to flow at least _____ gpm.
- 500 gpm
- TQ** Many pumpers are equipped with tank-to-pump piping as large as ____ inches in diameter.
- 4 inches
- Pumps rated greater than ______gpm capacity may require more than one large intake connection at each location. Pump 314.
- 1,500 gpm
- As a minimum, all fire apparatus with a rated pump capacity of ___ gpm or greater must be equipped with at least ____ 2 1⁄2-inch discharges. Pumps rated less than ____ gpm are required to have only _____ 2 1⁄2-inch discharge.
- 750 gpm, Two, 750 gpm, one
- A minimum of ______-inch piping, valves, and elbows must be used to supply discharges where 1 1⁄2-, 1 3⁄4-, or 2-inch handlines are attached.
- 2 inch
- All valves should be designed and maintained so that they are easily operable at pressures of up to _____ psi.
- 250 psi
- According to NFPA® 1901, apparatus equipped with tanks of less than 1,000 gallons must have a tank fill line of at least _____-inch in diameter. Tanks greater than 1,000 gallons must be provided with at least a _____-inch tank fill line.
- 1 inch. 2 inch
- NFPA® 1901 requires that all intakes or discharges that are _____ inches or greater be equipped with slow acting valve controls.
- 3 inches or greater
- TQ** NFPA® 1901 requires some type of pressure control device to be part of any fire apparatus pumping system. This device must operate within _______to ______ seconds after the discharge pressure rises and restricts the pressure from exceeding ______ psi above the set level. Pump 318.
- 3 to 10 seconds. 30 psi above
- It is generally recommended that the intake relief valves be set to open when the intake pressure rises more than _____ psi above the necessary operating pressure.
- 10 psi above
- The electronic governor also features cavitation protection by returning the engine to idle when intake pressure drops below ____ psi. Pump 321.
- Below 30 psi
- The operator manual supplied by the fire pump manufacturer should specify the preferred engine speed (rpm) for priming but, in general, the range is between ______ to _____ rpm. Activate the primers with the engine at idle speed and then increase the throttle to the specified rpms.
- 1000 to 1,200 rpm
- The master intake gauge (vacuum or compound gauge) is connected to the intake side of the pump and measures either positive pressure or a vacuum. This gauge is usually calibrated from ____ to ____ psi of positive pressure and from ____ to ____ inches of mercury (vacuum) on the negative side.
- 0 to 600 psi, 0 to 30 inches of mercury
- When the vacuum reading approaches _____ inches, the pump is nearing its capacity and is not able to supply additional lines.
- 20 inches
- Driver/operators should maintain a residual pressure of at least ____ psi on their master intake gauge at all times during pumping operations.
- 20 psi
- Water supply systems must maintain a residual pressure of at least ____ psi within their mains for several reasons; contamination from sources outside the main may occur if the pressure in the main drops too low.
- 20 psi
- The ability to overcome losses in pressure is limited to atmospheric pressure at sea level (_____ psi or _____ inches Hg). Pump 352.
- 14.7 psi. or 30 imches Hg
- This pressure (atmospheric pressure) decreases approximately 0.5 psi or 1 inch of Hg for each 1,000 feet of altitude gain. In a city located 5,000 feet above sea level, the atmospheric pressure is _____ psi.
- 12.2 psi
Most pumps are able to develop a vacuum capacity of approximately _____ inches of mercury (Hg).
- 22 inches of mercury
- When using a portable tank or swimming pool for drafting operations, a low-level strainer is the appliance of choice. These strainers are designed to sit directly on the bottom of a tank or pool and allow water to be effectively drafted down to a depth of approximately ___ inches.
- 2 inches
- Water temperature will also affect drafting operations. Water below ____°F or above ____°F may adversely impact the ability of the pump to reach capacity. Pump 356.
- 90
- __________________to a water source is an important factor in selecting a drafting site. Because drafting is accomplished by evacuating air from the pump and allowing atmospheric pressure to push the water into it, a maximum of ______ psi is available.
- Accessibility. 14.7 psi
- All fire pumps meeting NFPA and Underwriter’s Laboratories Inc. requirements are rated to pump their capacity at _____ feet of lift. Pump 357.
- 10 feet of lift
- A pumper in good working order can lift water a maximum of ____ feet.
- 25 feet
- To create an effective fire stream, a lift of no greater than ______ feet is recommended. Working with this lift, the pump operates at about ______ percent of its rated capacity.
60 percent.
- Most priming pumps are intended to work most effectively when the engine is set at a rate between ______ and ______ rpm.
- 1,000 to 1,200 rpm
- The entire priming action typically requires ____ to ____ seconds from start to finish. However, when up to 20 feet of intake hose lifting a maximum of 10 vertical feet, it may take as long as ______ seconds (45 seconds in pumps larger than 1250 gpm) to accomplish this.
- 10 to 15 seconds.
30 seconds
- When specific information is unavailable, driver/operators should pump ____ psi into the FDC when supporting automatic sprinkler systems.
- 150 psi
- Add approximately ___ psi for each floor above the fire department connection that will have operating fire streams.
- 5 psi
- Do not use pump discharge pressures in excess of ______ psi unless the standpipe system, hose, and appliances have been designed to function under high pressures.
- 185 psi
- When a standpipe system is known to be equipped with pressure-reducing valves, the elevation pressure used must be based on the_________________________________________________.
- total height of the standpipe or zone being used
- Pressure-Reducing Valve — Valve installed at standpipe connection that is designed to reduce the amount of water pressure at that discharge to a specific pressure, usually _____ psi.
- 100 psi
- An external standpipe may also be created by hoisting up, or rolling hose down the outside of a building, securing it inside every ______ or ______ floors.
- Two or three floors
- Theoretical Lift — Theoretical, scientific height that a column of water may be lifted by atmospheric pressure in a true vacuum; at sea level, this height is _______ feet. The height will decrease as elevation increases. Pump 404.
- 33.9 feet
- For every 1,000 feet of altitude, the atmospheric pressure decreases by approximately _____psi.
- 0.5 psi
- In the fire service, _______________ is defined as the greatest height to which any amount of water may be raised through an intake hose to the pump.
- Maximum lift
- In most circumstances, maximum lift is approximately ______feet.
- 25 feet
- _____________________ — Height a column of water may be lifted in sufficient quantity to provide a reliable fire flow. Lift may be raised through a hard suction hose to a pump, taking into consideration the atmospheric pressure and friction loss within the hard suction hose; ________________ is usually considered to be ______ feet.
- Dependable lift.
Dependable lift.
14.7 feet
- All fire department pumping apparatus are rated when drafting with a minimum lift of ____ feet from the center of a pump intake to the surface of water through ____ feet of hard intake hose. A strainer is submerged at least ___ feet in a water depth of at least ___ feet.
- 10 feet of lift. 20 feet of hose. 2 feet. 4 feet
- As the lift or friction loss in hard intake hose is increased, the water supply capability of the pump decreases. The pump may only deliver about ____ percent of its capacity if lift is increased by 5 feet , to a 15-foot lift, and ____ percent at a 20 foot lift.
- 70 percent. 60 percent.
- Floating pumps placed in an adequate water source can develop and maintain a flow of up to ____ gpm.
- 500 gpm
- Although lesser depths may be suitable, ___ feet of water all around a barrel-type strainer is generally considered the minimum for that type of equipment.
- 2 feet
- Floating strainers may be used for water as shallow as___ foot.
- 1 foot
- Low-level strainers are most commonly used to draft from portable water tanks. These devices may draw water as shallow as ___ to ___ inches, but generally will not provide the flow required to reach the capacity of the pumping apparatus.
- 1 to 2 inches
- Although they may vary in size, cisterns typically range from ___________ to ________ gallons. Pump 415.
- 10,000 to 100,000 gallons
- Large Diameter Hose (LDH) — Relay-supply hose of _____ to _____ inches in diameter; used to move large volumes of water quickly with a minimum number of pumpers and personnel.
- 3 ½ inch to 6 inches
- TQ** Centrifugal pumps are rated to pump at their maximum volume capacity at __ psi at draft.
- 150 psi
- As previously mentioned, fire department pumpers are rated to flow their maximum volume at ____psi, 70 percent of their maximum at ____ psi, and 50 percent of their maximum at ____ psi at draft.
- 150 psi, 200 psi, 250 psi
- It is advisable for driver/operators to maintain an intake pressure of ___ to ___ psi as a relay pumper.
- 20 to 30 psi
- For relay pumpers equipped with an adjustable intake relief valve, they should be set to ___ psi above the static pressure of the water system to which it is attached or ___ psi above the discharge pressure of the previous pumper in the relay.
- 10 psi. 10 psi.
- Attack pumpers equipped with an adjustable intake relief valve should be set between ___ and ___ psi to establish a stable operating condition. Pump 434.
- 50 and 75 psi
- The driver/operator of the attack pumper should expect small variations in pressure during relay pumping operations. You should not attempt to correct minor fluctuations as long as the intake pressure does not drop below ___ psi.
- 20 psi
- Driver/operators should refer to NFPA _____ for further information regarding the placement of relief devices.
- NFPA 1962
- In accordance with NFPA® 1901, water tenders must be designed to be filled at a rate of at least ______ gpm so that pumpers assigned to the fill site must be rated at that capacity or greater.
- 1,000 gpm
- Vehicle weight restrictions generally limit single rear axle apparatus to a maximum capacity of _______ gallons.
- 2,000 gallons
- For apparatus with a capacity greater than _______ gallons , tandem rear axles, tri-axles, or semi-trailers are required.
- 2,000 gallons
- Tenders featuring pumps of ____ gpm or greater rating are often called pumper/tenders.
- 750 gpm
- Pumper/tenders have large water tanks and the ability to pump at ____ gpm or greater.
- 750 gpm
- The vacuum tender is able to self-fill from a static water source at a rate of up to ______ gpm with a lift of up to ____ feet. These apparatus are also capable of discharging its water tank at a rate up to _______ gpm.
- 2,000/ 22 feet/ 1,750 gpm
- With a gravity dump, gravity is used to empty water from the tank. These dumps often use ____-inch or larger round or square piping with a valve that extends to the exterior of the vehicle.
- 8 inch
- When possible, a water supply source capable of supplying at least ______ gpm should be chosen in order to match the NFPA® recommended rate at which tenders should be filled. Pump 452.
- 1000 gpm
- Nurse Tanker — Very large water tanker (generally _______ gallons or larger) that is stationed at the fire scene and serves as a portable reservoir rather than as a shuttle tanker. Also known as Nurse Tender.
- 4,000 gallons
- NFPA® 1901 requires all tenders to have the capability to dump at a minimum average flow rate of _______ gpm for the first ___ percent of its tank capacity. Pump 462.
- 1000 gpm. 90 percent
- A simple dump site may feature the use of one portable tank that is supplied directly by water shuttle tenders. This operation is generally adequate for fire fighting operations that require relatively low flow rates (less than _____ gpm).
- 300 gpm
- Any tank, regardless of type, should be set up on a surface that is as level as possible and have a capacity at least _____ gallons larger than the water tank on the apparatus that will supply it.
- 500 gallons
- The dump site pumper should utilize a low-level strainer to allow for continuous drafting to a point of about ___inches.
- 2 inches
- Incidents that require a flow rate in excess of ____ gpm are best served by a multiple tank operation.
- 300 gpm
- Most multi-tank operations use from ____ to _____ portable tanks.
- Two to five portable tanks
- For operations that require more than three tanks and jet siphons and flows over 500 gpm, __________________ should be used to transfer water to the tank supplying the attack pumper.
- Parallel Jet Siphons
- ( question from fired up: tender fill lines should be pressurized at ____-___ psi at all times.) page 472 in the skill sheets. Place pumper in pump gear and charge tender fill lines, keeping pumper in gear and fill lines charged at all times. Follow local SOPs for discharge pressure, usually between ____ and ____ psi
- 100-150 psi
- (Hose size between the hydrant and pumper at the fill site is ____ LDH minimum.)
- One LDH minimum
- Many modern fuels, including gasoline, are blended with up to ___ percent solvent additives. Treat these products as polar solvents during emergency operations.
- 15 percent solvent additives
- Most fire fighting foam concentrates are formulated to mix with ____ to ____ percent water.
- 94 to 99.9 percent
- Class A foams are formulated to be proportioned within certain limits established by the manufacturer to achieve specific objectives. These percentages may range from a little as ___ percent to ___ percent.
- 0.1 to 1 percent
- When bulk storage of foam concentrates is required, some fire departments or industrial facilities may specify ____ gallon containers, called ______. Pump 484.
- 275 gallon, totes
- Foam concentrate tanks on municipal fire apparatus generally range from ___ to ____ gallons, while foam pumper or tenders may carry _______ gallons or more of concentrate.
- 20 to 200 gallons. 8,000 gallons
- Available since the 1940s, _________ foam technology has only recently been widely accepted and used for increasing numbers of structure, wildland, coal, tire storage, and other fires involving deep seated fuels.
- Class A foam
- The shelf life of properly stored foam solution can be as long as ___years making it an economical choice to purchase in bulk quantities.
- 20 years
- Class A foam concentrates may be mixed with percentages as little as _____ to ______ percent.
0.1 to 1.0 percent
The following guidelines are commonly used for proportioning Class A foam:
186. Fire attack and overhaul with standard fog nozzles — ____ to ____ percent concentrate.
- Fire attack, overhaul = 0.2-0.5 percent