LOT 202.23 OL-ACW Flashcards
- LOT 202.23 OL-ACW*
- *
What does OL-ACW cool?
Main Turbine Lube Oil (2)
SGFPT Lube Oil (6)
Generator H2 (1)
CL-ACW (2)
RCB Chillers (3)
MAB Chillers (4)
- LOT 202.23 OL-ACW*
- *
Where does OL-ACW discharge to?
CW piping
- LOT 202.23 OL-ACW*
- *
Which loads have auto TCV’s?
Gen H2 cooler (1)
Turbine Lube Oil Coolers (2)
SGFPT Lube Oil Coolers (6)
Gen H2 Cooler TCVs controlled on CP007.
- LOT 202.23 OL-ACW*
- *
What are the starting permissives and auto starts for the OL-ACW pumps?
- Auto Start:*
- *System Pressure - Low (68 psig)**
- Downstream of the strainer*
- *Trip of Running Pump**
- Starting Permissives:*
- *Seal Water Pressure ≥ 18 psig [Unit 1 ONLY]**
- Will not trip pump*
Note:
Pressure indicator on CP009 is pressure downstream of strainer NOT pump discharge pressure.
- LOT 202.23 OL-ACW*
- *
What powers the OL-ACW pumps?
- Pump 11:*
- *LC 1D2**
- Pumps 12/13:*
- *LC 1D1**
Controlled on CP009/Locally
- LOT 202.23 OL-ACW*
- *
What TCVs can be controlled from the control room?
- CP007:*
- *Gen H2 cooler**
- Both TCVs*
Raising demand causes bypass to open and suction to close.
Note:
All other TCVs are local control only
- LOT 202.23 OL-ACW*
- *
Which loads receive full flow on a loss of air?
Everything but CL-ACW
MG H2 and Main Turbine LO have 2 auto TCVs.
- Provides more constant flow and temperature