LOT 202.15 SGWLC Flashcards
1
Q
- LOT 202.15 SGWLC*
- *
How does the MFRVs control SGWL?
A
- SG Water Level Mismatch:*
- *2.5 (Actual Level - Program Level)**
- Flow Mismatch:*
- *0.6 (Steam Flow - Feed Flow)**
MFRVs are level dominant.
2
Q
- LOT 202.15 SGWLC*
- *
How does the LPRVs control SGWL?
A
- SG Water Level Mismatch:*
- *Actual Level - Program Level**
- PR NI Compensation:*
- *Auctioneered High NI**
Low Power Feed Reg Valves are level dominant.
3
Q
- LOT 202.15 SGWLC*
- *
What is program SGWL?
A
- *70.7%**
- SGNR Level*
7300 cabinets maintain program level
4
Q
- LOT 202.15 SGWLC*
- *
If a SG Pressure channel fails, how does steam flow fail?
A
- SG Pressure Fails High:*
- *Steam Flow Fails High**
- SG Pressure Fails Low:*
- *Steam Flow Fails Low**
5
Q
- LOT 202.15 SGWLC*
- *
How does the SGFPTs control SGWL?
A
- Pressure Mismatch:*
- *Actual D/P - Reference D/P**
- Actual D/P:*
- *Feed Pressure (PT-558) - Steam Pressure (PT-557)**
- Reference D/P:*
- *0% - 20% Steam Flow: 65 psid**
- *100% Steam Flow: 169 psid**
- Goes up linearly from 20% - 100%*
- PT-558 (Common Header Feed Pump Discharge Pressure)
- PT-557 (MS Equalizing Header)
- Same as steam dumps
Note:
Steam flow is the selected steam flow channel on CP006.