LOT 202.22 Circulating Water Flashcards
- LOT 202.22 Circulating Water*
- *
What will auto start the CW Screen Wash Pumps?
Lead Pump:
Screen D/P > 6”
One Screen Running
First Lag Pump:
10 Sec after lead pump start, Pressure < 102 psig
4 Screens Running
Second Lag Pump:
10 Sec after 1st lag pump start, Pressure < 102 psig
7 Screens Running
If pump started on low pressure will not stop. (Must reset)
Note:
Spray valves will open when pressure > 90 psig
- LOT 202.22 Circulating Water*
- *
What reservoir temperature will require running all four CW pumps?
69 ˚F
Running all four CW Pumps < 69 ˚F will raise the plant’s condensate depression and lower overall efficiency.
- LOT 202.22 Circulating Water*
- *
What will energize the blue start permissive light on CP009?
Discharge Column filled*
- *Seal Pressure > 30 psig**
- < 50 psig starts standby pump*
Discharge Valve Closed
> 5 mins since last CW pump start
Can use Jet pump to draw air and moisture out of CW discharge column.
- Uses screen wash header as prime water
- LOT 202.22 Circulating Water*
- *
What is the CW pump securing sequence?
- Third and Fourth Pumps:*
- *Once Discharge MOV 80% Open, Pump Stops**
Discharge MOV fully Closes
- First and Second Pumps:*
- *Once 2nd pump’s Discharge MOV 95% Open, BOTH PUMPS TRIP**
Valves Remain As-Is (95% Open / Fully Open)
Must wait 5 mins between securing pumps
Note:
PTL:**Bypasses 5 min TD but Discharge MOVs will still fully close
- LOT 202.22 Circulating Water*
- *
What is the CW pump start sequence?
- First Pump:*
- *10 sec after start, Discharge MOV opens to 40%**
- Second Pump:*
- *10 sec after start, 2nd Pump’s Discharge MOV fully opens**
Once 2nd Pump’s Discharge MOV is 35% open, 1st Pump’s Discharge MOV fully opens
- Third / Fourth Pump:*
- *10 sec after start, Discharge MOVs fully open**
Pump trips:
- Discharge MOV NOT moving after 24 sec
- Discharge MOV NOT 35% open in 32 sec
- LOT 202.22 Circulating Water*
- *
What systems utilize the CW discharge piping?
OL-ACW
ECW Blowdown
- *LWPS**
- Connects to OL-ACW (MAB Chiller 11 in overhead)*
- LOT 202.22 Circulating Water*
- *
What will trip a CW pump?
- Starting Pump:*
- *Discharge MOV NOT moving after 24 sec**
Discharge MOV NOT ≥ 35% open in 32 sec
- Stopping Last 2 CW Pumps:*
- *Stopping 1 pump trips both**
- Discharge valves remain open*