IBC Chapter 9 Flashcards
1
Q
- Where a fire protection system is required to be monitored, the approved supervising station must
comply with ____________.
A. NFPA 4
B. NFPA 13
C. NFPA 70
D. NFPA 72
A
- D Sec. 901.6
2
Q
- Which one of the following types of standpipe systems requires water from a fire department pumper to
be pumped into the system in order to supply the system demand?
A. automatic dry
B. automatic wet
C. manual wet
D. semi-automatic dry
A
- C Sec. 202
3
Q
- Which one of the following classes of standpipe systems is intended primarily for the use of building
occupants or the fire department during initial response?
A. Class I
B. Class II
C. Class III
D. Class IV
A
- B Sec. 202
4
Q
- In a Group A-2 occupancy, an automatic sprinkler system shall be provided throughout any fire area
having a minimum occupant load of _______________.
A. 50
B. 60
C. 100
D. 3000
A
- C Sec. 903.2.1.2, #2
5
Q
- A stadium press box in a Group A-5 occupancy having a maximum floor area of __________ square
feet need not be sprinklered.
A. 400
B. 1,000
C. 5,000
D. 12,000
A
- B Sec. 903.2.1.5
6
Q
- A sprinkler system is not required for Group E fire areas having a maximum floor area of ________
square feet except where located below the exit discharge level.
A. 2,500
B. 5,000
C. 12,000
D. 20,000
A
- C Sec. 903.2.3, #1
7
Q
- Where woodworking operations in a Group F-1 occupancy generate finely divided combustible waste,
an automatic sprinkler system is required where such operations occupy a minimum size floor area of
___________ square feet.
A. 1,001
B. 2,501
C. 5,001
D. 12,001
A
- B Sec. 903.2.4.1
8
Q
- In a single-story ambulatory care facility, an automatic sprinkler system is required where a minimum of
________ are recipients are incapable of self-preservation at any time.
A. 4
B. 6
C. 10
D. 20
A
- A Sec. 903.2.2, #1
9
Q
- An automatic sprinkler system shall be provided throughout a building with a Group M fire area located
a minimum of ____________ stories above grade plane.
A. 2
B. 3
C. 4
D. 6
A
- C Sec. 903.2.7, #2
10
Q
- Buildings containing which of the following residential occupancies must be sprinklered under all
conditions?
A. Groups R-1 and R-2 only
B. Groups R-1, R-2 and R-4 only
C. Groups R-2 and R-4 only
D. All Group R occupancies
A
- D Sec. 903.2.8
11
Q
- Where any portion of a basement is located a minimum of _________ feet from complying exterior
openings, the basement shall be provided with an automatic sprinkler system.
A. 50
B. 75
C. 100
D. 150
A
- B Sec. 903.2.11.1.3
11
Q
- A building shall be fully sprinklered where the combined area of all Group S-1 fire areas exceeds
_________ square feet.
A. 2,500
B. 5,000
C. 12,000
D. 24,000
A
- D Sec. 903.2.9, #3
12
Q
- A single-story Group S-1 repair garage need not be fully sprinklered where the fire area contains a
maximum of ________ square feet.
A. 2,500
B. 10,000
C. 12,000
D. 24,000
A
- C Sec. 903.2.9.1, #2
13
Q
- A Group S-2 parking garage used to store commercial buses need not be sprinklered where the fire area
has a maximum size of ________ square feet.
A. 2,500
B. 5,000
C. 10,000
D. 12,000
A
- B Sec. 903.2.10.1
14
Q
- A NFPA 13D sprinkler system is permitted to be installed in all but which one of the following uses?
A. Townhouse
B. Group R-3
C. Group R-4, Condition 1
D. Group R-2
A
- D Sec. 903.3.1.3
15
Q
- Which of the following spaces requiring sprinkler system protection is not required to use quickresponse or residential sprinklers?
A. light-hazard occupancies
B. sleeping units in Group R-1
C. care recipient sleeping units in Group 1-2
D. sales rooms of Group M
A
- D Sec. 903.3.2
16
Q
- The manual actuation device for a fire-extinguishing system for a commercial cooking system shall be
located a minimum of _________ feet and a maximum of ___________feet from the kitchen exhaust
system.
A. 3, 6
B. 5,10
C. 6, 12
D. 10, 20
A
- D Sec. 904.12.1
16
Q
- A minimum of __________ clearance shall be maintained between automatic sprinklers and the top of
piles of combustible fibers.
A. 12 inches
B. 18 inches
C. 3 feet
D. 5 feet
A
- C Sec. 903.3.3
17
Q
- Limited area sprinkler systems are only permitted to protect areas classified as
A. Light Hazard
B. Light Hazard or Ordinary Hazard Group l
C. Ordinary Hazard Group I or 2
D. Light Hazard, Ordinary Hazard Group l or Ordinary Hazard Group 2
A
- B Sec. 903.3.8.2
18
Q
- Connections for Class II standpipe systems shall be located so that all portions of the building are within
___________feet of a nozzle attached to _______ feet of hose.
A. 20, 50
B. 30, 100
C. 40, 125
D. 40, 150
A
- B Sec. 905.5
19
Q
- In a nonsprinklered Group B occupancy, a manual fire alarm system shall be installed where there are a
minimum of ________ occupants above or below the level of exit discharge.
A. 101
B. 201
C. 301
D. 501
A
- A Sec. 907.2.2, #2
20
Q
- A manual fire alarm system is not required in a Group E occupancy with a maximum occupant load of
______________ persons.
A. 30
B. 50
C. 300
D. 500
A
- B Sec. 907.2.3, Exc. l
21
Q
- Manual fire alarm boxes, where required, shall be located a maximum of _____________ feet from the
entrance to each exit.
A. 5
B. 10
C. 12
D. 20
A
- A Sec. 907.4.2.1
22
Q
- In a Group R-1 hotel providing 220 sleeping units, a minimum of _______ such units shall be provided
with visible alarm notification devices.
A. 3
B. 11
C. 17
D. 22
A
- C Table 907.5.2.3.2
23
25. The maximum sound pressure level for audible alarm notification appliances shall be dBA at the
minimum hearing distance from the audible appliance.
A. 60
B. 75
C. 90
D. 110
25. D Sec. 907.5.2.1.2
24
26. The manual actuation device for an automatic fire-extinguishing system serving a commercial cooking
system shall be installed a minimum of ________ inches and a maximum of _____ inches above the
floor.
A. 38, 42
B. 34,48
C. 38, 42
D. 42, 48
26. D Sec. 904.12. 1
25
27. A Class lII wet standpipe is not required for stages having a maximum size of __________ square feet.
A. 100
B. 400
C. 500
D. 1,000
27. D Sec. 905.3.4
26
28. Where natural ventilation is utilized for venting a smokeproof enclosure, each vestibule shall be
provided with a minimum ___________ -square-foot opening in the exterior wall.
A. 9
B. 16
C. 24
D. 35
28. B Sec. 909.20.3.3
27
29. Other than for an aircraft repair hangar, a one-story Group S-1 occupancy shall be provided with smoke
and heat vents or a mechanical smoke removal system where it exceeds _______ square feet in
undivided area.
A. 8,000
B. 10,000
C. 15,000
D. 50,000
29. D Sec. 910.2.1
28
31. Sprinkler protection is required for exterior balconies, decks and ground floor patios of dwelling units
where the building is of _______ construction and a roof or deck exists above.
A. combustible
B. Type IV
C. Type III
D. Type V
31. D Sec. 903.3.1.2., #1
29
30. Carbon monoxide detection, when required, shall be provided in all but which one of the following
locations?
A. Group E classroom
B. Group 1-1 group home sleeping units
C. Group 1-3 housing units
D. Group R-1 sleeping units
30. C Sec. 915.1.1
30
32. A manual fire alarm system shall be installed in all multistory Group F occupancies having a minimum
combined occupant load of ________ above or below the lowest level of exit discharge.
A. 50
B. 100
C. 300
D. 500
32. D Sec. 907.2.4, #2
31
33. The vestibule space in a smokeproof enclosure shall have a minimum width of ___________ inches
and a minimum length in the direction of egress travel of _________ inches.
A. 44, 60
B. 44, 72
C. 60, 60
D. 60, 84
33. B Sec. 909.20.1
32
34. Fire pump rooms, where required, shall be provided with a suitable means for maintaining the
temperature above ____________.
A. 40°F
B. 50°F
C. 55°F
D. 68°F
34. A Sec. 913.3
33
35. Where a fire command center is required by other provisions of the code, the room shall be a minimum
of __________ square feet in area.
A. 96
B. 100
C. 144
D. 200
35. D Sec. 911.1.3