IBC 701-705 Flashcards
- An opening around a penetrating item is a(n) .
A. annular space
B. penetration
C. through penetration
D. joint
- A Sec. 202
- A is a listed device installed in a ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly to limit automatically the radiative heat transfer through an air inlet/outlet opening.
A. horizontal fire damper
B. ceiling radiation damper
C. combination fire/smoke damper
D. horizontal access door
- B Sec. 202
- The time period that a through-penetration firestop system limits the spread of fire through a penetration when tested in accordance with ASTM E 814 or UL 1479 is considered .
A. fire protection rating
B. an F rating
C. a T rating
D. a fire-resistance rating
- B Sec. 202
- consists of building materials installed to resist the free passage of flame to other areas of the building through concealed spaces.
A. Draftstopping
B. Fireblocking
C. Firestopping
D. Opening protectives
- B Sec. 202
- The measurement between the face of an exterior wall and the closest interior lot line is described as the
.
A. fire separation distance
B. fire exposure setback
C. clearance to construction
D. exterior fire exposure
- A Sec. 202
- A must have sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall.
A. fire wall
B. fire separation wall
C. fire barrier
D. smoke barrier
- A Sec. 202, 706.2
- A smoke compartment is created by enclosure of a space on all sides, including top and bottom, by
.
A. smoke partitions
B. smoke barriers
C. shaft enclosure construction
D. fire partitions
- B Sec. 202
- The T rating for a penetration firestop system is based on a maximum temperature rise of °F above its initial temperature through the penetration on the nonfire side when tested in accordance with AS1M E 184 or UL 1479.
A. 250
B. 325
C. 375
D. 400
- B Sec. 202
- Unless alternate methods are used for determining the fire-resistance ratings of building elements, the test procedures set forth in ASTM E 119 or shall be applicable.
A. ANSIZ97.1
B. ASCE5
C. UL 263
D. UL 555
- C Sec. 703.2
- Where a fire barrier is required to be identified by signage in an accessible concealed attic space, the identification shall occur at maximum intervals of feet measured horizontally along the wall.
A. 15
B. 20
C. 30
D. 40
- C Sec. 703.7
- A projection extending beyond an exterior wall that is located 6 feet from an interior lot line shall be located such that a minimum of inches is provided between the lot line and the edge of the projection.
A. 12
B. 24
C. 30
D. 48
- D Table 705.2
- Composite materials with a noncombustible structural base are considered noncombustible where the surface material is limited to inch in thickness and has a maximum flame spread index of
.
A. ½. 25
B. 1/16, 50
C. 1/8, 25
D. 1/8, 50
- D Sec. 703.5.2
- Projections beyond an exterior wall are not permitted where the exterior wall has a maximum fire separation distance of inches.
A. 12
B. 24
C. 30
D. 36
- B Table 705.2
- For wall and opening protection, projections and roof covering requirements, an assumed imaginary line shall be placed between unless they are considered a single building.
A. court walls
B. fire areas
C. buildings on the same lot
D. different occupancies
- C Sec. 705.3
- In a building of Type III construction, projections may be .
A. of noncombustible construction
B. of combustible construction
C. of minimum one-hour fire-resistance-rated construction
D. of any approved materials
- D Sec. 705.2.2