IBC 1001 - 1005,1008, 1009, 1013, 1015 Flashcards
1
Q
- A court or yard that provides access to a public way for one or more exits is considered a(n) __________.
A. exit access way
B. egress court
C. public way
D. horizontal exit
A
- B Sec. 202
2
Q
- Which of the following elements is not a distinct and separate part of the means of egress?
A. exit discharge
B. exit access
C. exit
D. exit convergence
A
- D Sec. 202
3
Q
- That portion of the exit access that occupants must traverse before two separate and distinct paths of
egress travel to two exits are available is considered a _____________.
A. means of egress
B. single egress path
C. common path of egress travel
D. limited egress travel distance
A
- C Sec. 202
4
Q
- Panic hardware that is listed for use on fire door assemblies is considered to be __________ hardware.
A. fire egress
B. fire exit
C. panic
D. panic and fire
A
- B Sec. 202
5
Q
- An alternating tread device has a series of steps that are positioned a minimum of degrees and maximum of _________ degrees from horizontal.
A. 30, 45
B. 45, 60
C. 50, 70
D. 60, 75
A
- C Sec. 202
6
Q
- A 1,500-square-foot (net) woodworking shop classroom in a high school is considered to have a design
occupant load of ________ persons.
A. 25
B. 30
C. 75
D. 100
A
- B Table 1004.5
6
Q
- In determining the design occupant load for the sales area of a mercantile facility, the floor area shall be
divided by a factor of one occupant per________square feet.
A. 20
B. 30
C. 50
D. 60
A
- D Table 1004.5
7
Q
- For areas having fixed seats and aisles, the occupant load for bench seating without armrests is based on
one occupant for each_________ inches of seating length.
A. 15
B. 18
C. 24
D. 30
A
- B Sec. 1004.6
8
Q
- In a fully-sprinklered Group M retail sales building having an occupant load of 3,200 occupants, the minimum total calculated means of egress width for egress elements other than stairways shall be ______________ inches if an emergency voice/alarm communication system is provided.
A. 960
B. 640
C. 480
D. 320
A
- C Sec. 1005.3.2, Exc. 1
9
Q
- A stairway serving 160 occupants in a fully-sprinklered Group 1-2 hospital shall be a minimum of ____________ inches in width.
A. 42
B. 44
C. 48
D. 60
A
- C Sec. 1005.3.1
10
Q
- Multiple means of egress shall be sized so that the loss of any one means of egress shall not reduce the available capacity to less than __________of the required capacity.
A. 10 percent
B. 25 percent
C. 33 1/3 percent
D. 50 percent
A
- D Sec. 1005.5
11
Q
- When fully open, a door is permitted to project into the required width of the path of egress travel a maximum of ____________.
A. one-half the required width
B. one-half the actual width
C. 3 ½ inches
D. 7 inches
A
- D Sec. 1005.7.1
12
Q
- Up to 50 percent of the ceiling area of a means of egress may have a minimum ceiling height of ___________ where reduced by protruding objects.
A. 78 inches
B. 80 inches
C. 84 inches
D. 90 inches
A
- B Sec. 1003.3.1
13
Q
- At a doorway, the minimum headroom clearance below any door closer or stop shall be _____________ inches.
A. 76
B. 78
C. 80
D. 84
A
- B Sec. 1003.3.1, Exc
14
Q
- At an exterior door not required to be accessible in a Group F-1 occupancy, what is the maximum permitted elevation change?
A. 1/2 inch
B. 1 inch
C. 7 inches
D. 8 inches
A
- C Sec. 1003.5, Exc. 1