IBC 713 - 720 Flashcards
- A shaft enclosure shall have a minimum 2-hour fire-resistance rating where connecting a minimum of
stories.
A. two
B. three
C. four
D. six
l. C Sec. 713.4
- Where the annular space at the penetration of horizontal assemblies is filled with an approved material, noncombustible piping may connect a maximum of stories, provided the horizontal assemblies require no fire-resistance rating.
A. 2
B. 3
C. 4
D. 5
- D Sec. 714.6.1
- In which of the following locations is a fire-resistant joint system required to protect all joints?
A. floors within malls
B. horizontal exit walls
C. mezzanine floors
D. roofs where openings are permitted
- B Sec. 715.1, Exc.
- Fire-resistant joint systems are not required for control joints having a maximum width of inch when tested in accordance with ASTM E 119 or UL 263.
A. 0.25
B. 0.375
C. 0.5
D. 0.625
- D Sec. 715.1, Exc. #9
- In a nonsprinklered building, a fire door assembly in an exit passageway shall have a maximum transmitted temperature end point of above ambient at the end of 30 minutes of standard fire test exposure.
A. 250°F
B. 450° F
C. 600°F
D. 650°F
- B Sec. 716.2.2.3
- A fire door assembly in a 1-hour fire barrier used in an interior exit stairway enclosure shall have a minimum fire protection rating of hour.
A. 1/3
B. ½
C. ¾
D. 1
- D Table 716.1(2)
- An opening into a laundry chute access room shall be protected by opening protectives having a minimum fire protection rating of .
A. 20 minutes
B. 45 minutes
C. 1 hour
D. 1 1/2 hours
- B Sec. 713.13.3
- Fire door assemblies required in a 2-hour exterior wall shall have a minimum fire protection rating of
.
A. 20 minutes
B. 45 minutes
C. 1 hour
D. 90 minutes
- D Table 716.1(2)
- Penetrations in shall be tested for air leakage in accordance with the requirements of UL 1479.
A. smoke partitions
B. smoke barriers
C. fire barriers
D. fire walls
- B Sec. 714.5.4
- In which one of the following locations may self-closing or automatic-closing devices be omitted from required fire doors?
A. Group E corridor doors
B. doors in common walls separating Group R-1 sleeping units
C. doors between vertical exit enclosures mid exit passageways
D. Group 1-2 smoke barrier doors
- B Sec. 716.2.6.1
- Where an elevator lobby is required in a nonsprinklered building, it shall be separated from the floor level through the use of .
A. smoke barriers
B. fire barriers
C. fire partitions
D. smoke partitions
- C Sec. 713.14., 3006.3 #1
- Which one of the following fire-rated glazing markings is required for a sidelight adjacent to a 1-hour interior exit stairway door assembly?
A. D-H-45
B. D-H-O-H-20
C. D-H-O-H-45
D. W-60
- D Table 716.1(2)
- Where automatic-closing fire doors are installed, which one of the following locations does not require closing upon actuation of smoke detectors?
A. corridor doors in an office building
B. doors in a fire barrier separating control areas
C. a pair of doors installed in a fire wall
D. a single door installed in a smoke partition
- A Sec. 716.2.6.6
- Access openings for waste or linen chutes shall be located in rooms enclosed by minimum fire barriers.
A. 1
B. 1 ½
C. 2
D. 3
- A Sec. 713.13.3
- What is the minimum required fire-protection rating for a fire window assembly located in a 2-hour fire barrier?
A. ¾ hours
B. 1 hour
C. 1 ½ hours
D. fire windows
- D Table 716.1(3)