IBC 706 - 712 Flashcards
- Fire walls must be constructed of noncombustible materials unless separating buildings of Type construction.
A. I
B. III
C. IV
D. V
- D Sec. 706.3, Exc.
- A fire wall separating Type VA buildings housing Group M occupancies must have a minimum fire- resistance rating of hour(s).
A. 1
B. 2
C. 3
D. 4
- C Table 706.4
- In a Type IIB building containing a Group B occupancy, what is the minimum required fire-resistance rating for a fire wall?
A. l hour
B. 2 hour
C. 3 hour
D. 4 hour
- B Table 706.4, Note a
- As a general provision, what minimum distance must a fire wall extend horizontally beyond the exterior surface of exterior walls?
A. 18 inches
B. 20 inches
C. 30 inches
D. 4 feet
- A Sec. 706.5
- In general, what minimum distance above the roof must a fire wall extend?
A. 18 inches
B. 30 inches
C. 3 feet
D. 4 feet
- B Sec. 706.6
- Where a fire wall occurs at a location where the roof heights differ, the fire wall may terminate at the underside of the lower roof slab, provided .
A. the lower roof is of noncombustible construction
B. the first 10 feet of the lower roof assembly has a minimum 1-hour rating
C. the exterior wall of the higher portion is I-hour to a height of 10 feet
D. openings in the lower roof have a minimum 45-minute fire-protective rating
- B Sec. 706.6.1, Exc.
- Embedded ends of combustible members entering masonry or concrete fire walls shall be separated a minimum distance of inch(es).
A. 1
B. 2
C. 4
D. 6
- C Sec. 706.7
- The aggregate width of openings in a fire wall is limited to a maximum of of the length of the wall.
A. 10 percent
B. 25 percent
C. 33 1/3 percent
D. 50 percent
- B Sec. 706.8
- Fire barriers are required for the separation of all the following building elements, except
.
A. shaft enclosures
B. exit passageways
C. incidental uses
D. fire-resistance-rated corridors
- D Secs. 707.3; 708.1, #3
- In nonrated buildings, construction supporting fire barriers need not be protected by equivalent fire resistance where the fire barriers are used for .
A. 1-hour occupancy separations
B. 1-hour interior exit stairways
C. 1 -hour incidental use separations
D. 2-hour horizontal exits
- C Sec. 707.5.1, Exc. 2
- In a nonsprinklered building, any single opening in a fire barrier is limited to a maximum area of
square feet.
A. 20
B. 100
C. 120
D. 156
- D Sec. 707.6
- Openings in a fire barrier are permitted to be unlimited in area and aggregate width where the fire barrier is utilized as a(n) .
A. interior exit stairway enclosure
B. horizontal exit wall
C. incidental use separation
D. control area separation
- A Sec. 707.6, Exc. 2
- Where vertical openings are created for an escalator system in a fully sprinklered hotel, special opening protection methods are established, other than automatic shutters, where the openings connect a maximum of stories.
A. Two
B. Three
C. Four
D. Six
- C Sec. 712.1.3.1
- A floor opening is permitted between a maximum of two stories without a shaft enclosure, under limited conditions, in all but which one of the following occupancies?
A. Group A-2
B. Group H-2
C. Group 1-2
D. Group S-2
- C Sec. 712.1.9
- Fire walls shall be designed and constructed in accordance with IBC Section 706 or .
A. NFPA 286
B. NFPA 221
C. UL 1040
D. UL 2079
- B Sec. 706.2