Firefighting Systems Exam Flashcards
1
Q
Examine Fire Hose Stations
A
- Verify type, length and condition of hose
- Verify type and condition of nozzle (dual purpose type spray/jet)
- Verify operational condition of hydrant valve
- Verify operation of hydrant relief valves
- Verify location(s) consistent with FCP
2
Q
Examine Intl Shore Connection
A
- Verify presence
- Verify stowage location consistent with the FCP
- Verify presence of flange, bolts(4), washers(8) and gasket
3
Q
Examine Fire-Fighter’s Outfits
A
- Verify stowage location consistent with the FCP
- Verify quantity ( at least 2)
- Verify condition of personal equipment
- Verify condition of breathing apparatus 1200L/30Min (alarms at 200L/5min)
- Verify condition of life line (30m) and fire retardant
- Verify presence of spare charges (at least 2 for each SCBA)
4
Q
Examine Fire Control Plan (FCP)
A
- Verify currency of plan(s) or booklets
- Verify plan or booklet is in required languages
- Verify content of plan(s) or booklet
- Verify stowage of duplicate set of plan(s)
A duplicate set of FCP or a booklet containing such plans shall be permanently stored in a prominently marked weathertight enclosure outside the deckhouse for the assistance of shore-side fire-fighting personnel.
5
Q
Examine areas for compliance with SFP requirements
A
- Verify SFP boundaries with FCP
- Ensure no unapproved SFP modifications
- Evaluate fire door operation
- Verify electric cable/pipe penetrations are compatible with Fire control boundaries
- Verify operational tests of ventilation systems controls
6
Q
Examine fixed fire detection and alarm systems
A
- Verify operation
- Verify power sources
- Verify operation of alarms
- Verify operation of manually operated call points
- Verify periodic testing
7
Q
Examine Fire Main System
A
- Verify number of pumps (at least 2)
- Verify locations
- Verify remote start operation
- Verify pressure
- Verify relief valve installation
- Verify Fire station arrangements
- Verify condition of fire main piping
- Verify operation of emergency fire pump
8
Q
Examine Fire Pressure Water-spring and water mist fire extinguishing system
A
- Verify fixed system is arranged as indicated on the FCP or general arrangement plan
- Verify sprinkler pump arrangement for automatic activation
9
Q
Examine Fire High Pressure CO2 System
A
- Verify system is arranged as indicated in FCP
- Verify control valves are arranged and marked
- Verify operating instructions at control stations
- Verify closures for protected space openings
- Verify storage room arrangements
- Evaluate testing and inspection procedures
10
Q
Examine Low Pressure CO2 Fixed Fire Fighting System
A
- Verify system is arrange as indicated in the FCP or general arrangement plan
- Verify control valves are arranged and marked
- Verify operating instructions at control stations
- Verify closures for protected space openings
- Verify storage room arrangements
- Evaluate testing and inspection procedures
- Verify alarms and indicators
- Verify safety relief valves
11
Q
Examine Fixed High-Expansion Foam Fire Extinguishing System
A
- Verify system is arrange as indicated in the FCP or general arrangement plans
- Verify quantity and performance of foam concentrates