Fire Detection and Actuation System Flashcards
1
Q
Fire Detection and actuation system purpose?
A
-FDAS is designed to provide the control room with early indication of a fire by using automatic flame, heat and smoke detectors; and to protect various vital plant equipment and personnel by actuating selected fire suppression systems.
2
Q
FDAPs in the Aux building?
A
-FDAP-A1, A2, B1, B2
3
Q
FDAPs in the Condensate Polishing Buildig?
A
-FDAP-I and I1
4
Q
Location and info for FDAP-A1 and A2
Zones/Powered from?
A
- A1 on First floor Aux building beside SWBooster pumps. Has zones 1-12,20,and 28. Powered from MCC-10
- A2 in the E1/E2 room clean side, has zones 13-19,21-27, 29 and 30 (29 and 30 only on A train) Powered from MCC-10
- Can inhibit zones
5
Q
Location and info for FDAP-B1 and B2
Zones/ Powered from
A
- B1 Aux hallway south of WGDP. Has zones 1-12, 20 and 28. Powered from MCC-9
- B2 E1/E2 room RCA side. Has zones 13-19,21-27. Powered from MCC-9
- Cannot inhibit zones
6
Q
FDAP’s have a backup power that will last how long?
A
-4 hour back up battery