Diesel Generator/Cable Vault CO2 Fire Suppression Flashcards

1
Q

Purpose of the EDG CO2 Fire Suppression system?

How many bottles

A
  • Extinguish a fire in the EDG rooms by smothering and cooling.
  • 19 bottles
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If there is a fire in Either EDG Room what happens?

A
  • 30sec alarm delay (Alarm cylinder takes 30mins to exhaust)
  • 4 Pilot cylinders open to fill header to open the rest of the CO2 cylinders (2 with manual handwheels for manual operation)
  • 19 CO2 cylinders empty into either EDG A (Zone2) or EDG B (Zone1)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

HADs

How many in each room, what is it, what it does

A
  • 2 in each room.
  • Thine walled bulb shaped chamber, head expands the air in the chamber, the increasing air pressure is transmitted via tubing to the ROR release assembly.
  • ROR releases pilot pressure which beings actuation sequence.
  • Closes Dampers/Stops Supply fans, exhaust fans AND STOPS FUEL OIL TRANSFER PUMPS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Other indicators in room. Zone 1 and 2
Do they actuate CO2
What do they do?

A
  • 2 infrared flame detectors
  • 1 heat detector
  • 1 manual pull station
  • Does not actuate CO2
  • Closes Dampers/Stops Supply fans and exhaust fans
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Purpose of the Cable Vault fire system?

How many Bottles?

A
  • Extinguish a fire in the North Cable Vault room, Zone 9
  • Extinguish a fire in the South Cable Vault Room, Zone 10
  • 36 bottles total
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

North Cable Vault gets how many Cylinders?

South?

A
  • Gets 7 cylinders. Either from Main bank or reserve bank.

- All 18 from either Main bank, or Reserve bank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where are the CO2 cylinders for zone 9 and 10?

A

Pipe Ally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When will CO2 actuate in Zone 9 or 10?

A
-Need 2 separate fire alarm signals from the same fire detection zone.
(one on each train)
-Can be manually operated from Cylinders
-Can be operated from FDAP A-1 or B-1
-Manual pull stations. 2 in each zone.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly