Feed Water Flashcards
Purpose of the Feedwater system?
- Raise system pressure and supply water to the S/Gs
- Maintains proper water level in S/Gs
- S/Gs provide heat transfer from the core (RCS) to turbine and auxiliary equipment
Feed water pumps draw suction from?
- 70% from Condensate system
- 30% from Heater Drain Pumps
FWS safety related functions?
Feed Water System
- Has no safety functions
- AFWS is aligned for safeguard operation.
Main Feedwater Pumps
Power supplies?
- A 4kV Bus 1
- B 4kV bus 4
Manual Start of 1st FW pump must have?
- At least 1 condensate pump running
- Sufficient suction pressure (235psig)
- Oil Pressure at least 8psig
- All FW header block valves must be closed (V2-6 A/B/C) with power supplied to them
- No FW isolation signals
- S/G level are less than 75%
Manual Start of 2nd FW pump must have?
- Both condensate pumps running
- Sufficient suction pressure (235psig)
- Oil pressure of 8psig
FW pump trips that dont autostart other FW pump
- Undervoltage on bus
- Loss of Condensate pump
- Low suction pressure with low flow (235psig, 3100gpm)
- Si Signal
- HiHi S/G level (2/3 in 1/3 S/G lvl >75%)
FW Pump trips that will autostart other FW pump
- Electrical overload on motor
- Minimum flow (935psig)
- Low Lube oil pressure (6psig)
FW Pump Recirc Valves
FCV-1444 and FCV-1445
Purpose?
- Ensure minimum flow necessary for cooling of the MFP during low flow conditions.
- AOV
- When in Auto, open when flow lowers to 1475gpm, closes at 3100gpm.(only open when associated pump is running)
6A/6B Feedwater Heaters
purpose?
-Raise FW temperature using HP Turbine extraction steam.
V2-6 A/B/C
Feedwater Header Block Valves
Power supplies?
Purpose?
- Used to Isolate the FW pump discharge from the Main Feedwater Reg. Valve
- A MCC-5
- B&C MCC-6
- All 3 must be closed to start first MFW pump.
- NW of MFW pumps 1st floor
FCV-478, 488, 498
Feed Regulating Valves
- Regulate FW flow to the S/Gs to maintain programmed S/G level.
- AOV
- First Floor Turbine Building NW of MFW pumps
FCV-479, 489, 499
Feed Reg. Bypass valves
- Regulate FW flow to the S/Gs during low load conditions for finer feed flow control. (<15% power)
- AOV
- 2nd level Turbine building NW FRV bypass room
Feed Flow Venturi purpose?
- FW flow indication
- Input to the RPS and S/G level control.
FWUFM purpose?
-Highly accurate FW flow measurement system.