ESP 7 - AWP Variations and Additional Requirements Flashcards
What is Restoration of Motive Power defined as?
The controlled temporary re-energisation of selected energy sources to facilitate controlled mechanical movement of parts. The selected sources will then be de-energised and locked-off again, before any work can continue.
What are the two systems that apply on a WTG?
- Mechanical equipment and Electrical Infrastructure
- High Voltage System
Mechanical equipment and electrical infrastructure are covered by what rules?
Electrical Safety Program (ESP)
The High Voltage System is covered by what rules?
HV Safety Rules
The agreed boundary between the ESP and HV Safety Rules is confirmed where?
In the Safety Rules Inclusion Certificate (SRIC)
Between the AE and HV Senior Authorised Person, agreements will be made when a cross boundary AWP is to be created. What will be agreed on?
- Safety documents required for the work
- Required competence of the technicians
- Isolations required on both systems and precautions required to carry out the work
- Specific locking requirements and caution notices
- Sequence of isolations/switching