.AR Elect. SBOGs (Welch's Highlighted Notes) Flashcards

1
Q

Purpose/Function/Limitations:

  • SBOGS are backup for what station event?.
  • SBO assumed on how many units?
  • Required by which CFR?
  • FSAR – how many hours coping time?
    • How long/time assumed to start SBOGs?.
  • When is the second SBOG used?…
  • LOOP: energize which NAN bus within howmuch time? why?
  • SBOGs operation coordinated through which Unit?
  • SBOGs cannot supply which two Units simultaneously?
  • If a unit’s NBN-X03 XFMR is faulted, can SBOG still supply that unit?
  • LOOP: SBOG used to energize the SWYD loads within how many hours hours
    • Maintains what?
    • SBOGs (2)
  • fuel type?
  • MW? Design bases?
  • Max loading based on whatSBOG temp < °F?
  • RMP? Type of gears used?
  • RPM? (generator speed)
A

Purpose/Function/Limitations:

  • Backup source of power during station blackout.
  • SBO only assumed on one unit. (LOOP and both DGs fail – loss of all AC)
  • Required by 10CFR50.63 (cope with SBO, core cooling and CTMT integrity)
  • FSAR – 16 hour SBO coping time.
    • Assumes one SBOG is started within 1 hour.
  • Second SBOG is used if the first one fails or if MDAFW pump is required.
  • LOOP: energize NAN-S07 within 1 hour to maintain the SBOG batteries.
    • Maintains SBOG availability for a SBO
  • SBOGs operation coordinated through Unit 1
  • SBOGs cannot supply U2/U3 simultaneously
  • If a unit’s NBN-_X03 XFMR is faulted, SBOG cannot supply that unit_.
  • LOOP: SBOG used to energize the SWYD loads within 2 hours
    • Maintains PCB control power and PCB availability

SBOGs (2)

  • Liquid fueled gas turbines
  • 4.27 MW (Design Basis is 3698 KW)
  • Max loading based on maintaining SBOG temp < 1330°F
  • 14,951 rpm turbine speed. Reduction gears used.
  • 1800 rpm generator speed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Gas turbine operations:

  • what are the 3 main sub-components of SBOGs?
  • what are the 3 main sub-components of SBOGs?
  • Compressor blades…
  • Air is forced into…
  • Where is the Air/Fuel mixture ignited?
  • Turbine gases rapidly…
  • … blades spin.
A

Gas turbine operations:

  • Compressor
  • Combustor
  • Turbine
  • Compressor has blades that turn like a fan to pull air into the gas turbine.
  • Air is forced into the combustor, where fuel mixes with the compressed air.
  • Air/fuel mixture is ignited in the combuster
  • Burning gases rapidly expand out of combustor into the turbine. Gases transfer energy to the turbine blades.
  • Causes the blades to spin.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Acceleration (…Startup Sequence…)

  • At what % speed is the energy of the hot gases from the combustor enough to maintain turbine speed. “Self-Sustaining Speed.”?
  • ?°F = what at the turbine 3rd stage?
  • At what % speed do the Bleed Air Valve close, and the Variable Vane Controller actuates open?
A

Acceleration (…Startup Sequence…)

  • 66% speed - energy of the hot gases from the combustor is enough to maintain turbine speed. “Self-Sustaining Speed.” Turbine starting system disengages. Pre/Post Lube Oil Pump stops. Atomizing air is now supplied from the compressor.
  • 400°F (turbine 3rd stage) - ignition system switches off.
  • 90% speed - Bleed Air Valve closes, Variable Vane Controller actuates open.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

{[…Not highlighted in Welch’s Notes…]}

Engine support systems

  • Explain…

Lube Oil System

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

Engine support systems

  • 480Vac power normally fed from NHN-M56 (NAN-S06).
  • If power lost, power is fed from a step down XMFR from the SBOG 13.8 kV bus and an automatic transfer switch.

Lube Oil System

  • Two lube oil cooler packages. Cooled by electric fans.
  • 24 Vdc pre/post lube pumps
  • Engine driven MLO pump
  • PCVs/TCVs/Oil reservoir
  • Turbine Shutdowns: (Low oil level or pressure)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

{[…Not highlighted in Welch’s Notes…]}

Battery Charger and Battery Rack Assembly (2 per generator & 1 for switchgear)

  • Explain…

Engine Air System

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

Battery Charger and Battery Rack Assembly (2 per generator & 1 for switchgear)

  • 24 Vdc for control voltage (Generator #1 NEN-H01A)
  • 24 Vdc for diesel start (Generator #1 NEN-H02A)
  • 125 Vdc for switchgear control power (NKN H22)

Engine Air System

  • Pressurize oil seals.
  • Cool turbine rotor disks and first stage nozzles.
  • Supply Control Air for operation of the fuel control system.
  • Assist in obtaining smooth engine operation by preventing surge conditions at critical speeds.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

{[…Not highlighted in Welch’s Notes…]}

Start System

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

Start System

  • Capable of a black start.
  • Battery DC power source is independent from the unit’s PK and NK power.
  • Diesel-hydraulic start system provide the rotational force start the SBOG up to 66% speed.
  • At 66% speed, the turbine engine provides its own power to accelerate to 100% speed.
  • Diesel engine supplies compressed air and hydraulic pressure to the turbine.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

{[…Not highlighted in Welch’s Notes…]}

Fuel system

  • Explain…

Combined Generator Control Module

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

Fuel system

  • Controls the fuel pressure and regulates the fuel flow according to operating requirements
  • Use fuel pumps (1 is shaft driven)

Combined Generator Control Module

  • Controls Speed/load and Voltage/KVAR

Vibration Monitoring System

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

{[…Not highlighted in Welch’s Notes…]}

Turbotronic Control System (Controls the turbine functions, 24 Vdc power)

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

Turbotronic Control System (Controls the turbine functions, 24 Vdc power)

  • Sequences operating systems during starting, running, and shutdown, to provide necessary protection during all phases of operations; and to monitor package system parameters during operation
  • Power factor (pf) must be manually maintained (raise load, raise voltage / lower load, lower voltage)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

{[…Not highlighted in Welch’s Notes…]}

Fire Detection and Suppression System

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

Fire Detection and Suppression System

  • Uses light sensors or “Fire Eyes” to detect the presence of fire.
  • Lock out before the SBOG enclosure doors are opened to prevent inadvertent CO2 discharge.
  • Fire System Control is located on each SBOG control panel and consists of a Lockout switch.
  • FP system lockout prevents actuation of the CO2.
  • The fire eyes have protective covers that can be installed if the engine needs to run with the doors opened (one door at a time for vibe data and for < 10 minutes), but the thermal and hazardous gas level detectors will still force a shutdown if they are tripped by temperature or Lower Explosive Limit that exceeds the threshold. 10 min limit for open doors prevents high summer temp from causing SBOG shutdown.
  • Alarm: FP system not in Auto or fire eyes are covered.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

{[…Not highlighted in Welch’s Notes…Except Acceleration 66% & Self-Sustaining Speed]}

Start-up sequence

Time sensitive step (< 2 min):

  • Explain…

Press “Start” button.

  • Explain…

Diesel Starting Engine Start

  • Explain…

Ignition

  • Explain…

Acceleration

  • Explain… (highlighted in Welch’s notes!!!)

Generation

  • Explain…
A

{[…Not highlighted in Welch’s Notes…Except Acceleration 66% & Self-Sustaining Speed]}

Start-up sequence

Time sensitive step (< 2 min):

  • Once the SBOG reaches “Ready to Load” a 2 minute timer starts on 24VDC battery charger failed alarm.
  • If charger failed alarm not clear within 2 minutes, the SBOG will automatically shut down.
  • AO has to energize NHN-M73 upon receiving the “Ready to Load” light. Has to close SBOG output breaker (energizing NAN-S07) and ensure ABT transfers.
  • Also applies during testing. Will need to re-close the battery charger supply breakers within 2 minutes vice the SBOG output breaker.

Press “Start” button.

  • Starts the Pre/Post Lube Oil Pump (runs for 30 seconds)
  • Enclosure purge fan will run for two minutes if not in a SBO.

Diesel Starting Engine Start

  • After 2 minute enclosure purge or 30 seconds pre-lube, the diesel starts.
  • Diesel will pressurize the air assist tank to 120 psig.
  • Diesel-driven hydraulic pump provides pressure to engine starting motor. Compressor and turbine begin to rotate.

Ignition

  • Starting circuit opens Fuel Purge Valve (drains old fuel)
  • Fuel Boost Pump starts
  • 15% speed - Fuel Purge Valve closes.
  • 21% speed - Fuel Control Valve sends fuel to the Igniter Torch and Fuel Injector Nozzles.
  • Atomizing air mixed into the Fuel Injector Nozzles and the Ignition Circuit is energized. Lights the Igniter Torch.
  • Open Bleed Air Valve enables compressed air to bypass the turbine to make starting easier and prevent turbine surge.
  • Variable Vanes in the compressor are at minimum position to prevent compressor stall during the turbine acceleration.
  • As the temperature of the air leaving the combustor begins to rise the turbine begins to take over the load of turning the shaft.

Acceleration

  • 66% speed - energy of the hot gases from the combustor is enough to maintain turbine speed. “Self-Sustaining Speed.” Turbine starting system disengages. Pre/Post Lube Oil Pump stops. Atomizing air is now supplied from the compressor.
  • 400°F (turbine 3rd stage) - ignition system switches off.
  • 90% speed - Bleed Air Valve closes, Variable Vane Controller actuates open.

Generation

  • 85% speed - voltage regulator flashes the generator field.
  • 90% speed - Generator Voltage and Start Time are verified and the “Ready to Load” timer is activated.
  • 10 seconds after the Turbine speed reaches 90% the “Ready to Load” lite comes on.
  • 100% speed the Governor Control system assumes control of the turbine.
  • Total time elapsed is ~ 1 min 35 seconds.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

{[…Not highlighted in Welch’s Notes…]}

SBOG Shutdown Sequence:

  • Explain…
A

{[…Not highlighted in Welch’s Notes…]}

SBOG Shutdown Sequence:

  • < 300kW before shutting down the SBOG
  • Reduce SBOG load (communicate with MCR)
  • Open SBOG Output Breaker on NAN-S07
  • Press “Stop” push button.
  • Goes into a 3 minute cool down mode indicated by the “cool down” light on the SBOG Control Panel. During this time the turbine is running at 100% speed with no load.
  • At the end of the cool down period the SBOG will begin to slow down. When it reaches 90% speed the SBOG “Running” light goes out.
  • In an “Emergency,” SBOG can be stopped using the “Fast Stop” push button:
    • Immediately closes the Fuel Cutoff valve and the trips open the SBOG Output Breaker.
    • Cool down period is also eliminated and the SBOG slows to a stop.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly