.AR Elect. SBOGs (Welch's Highlighted Notes) Flashcards
Purpose/Function/Limitations:
- SBOGS are backup for what station event?.
- SBO assumed on how many units?
- Required by which CFR?
- FSAR – how many hours coping time?
- How long/time assumed to start SBOGs?.
- When is the second SBOG used?…
- LOOP: energize which NAN bus within howmuch time? why?
- SBOGs operation coordinated through which Unit?
- SBOGs cannot supply which two Units simultaneously?
- If a unit’s NBN-X03 XFMR is faulted, can SBOG still supply that unit?
- LOOP: SBOG used to energize the SWYD loads within how many hours hours
- Maintains what?
- SBOGs (2)
- fuel type?
- MW? Design bases?
- Max loading based on whatSBOG temp < °F?
- RMP? Type of gears used?
- RPM? (generator speed)
Purpose/Function/Limitations:
- Backup source of power during station blackout.
- SBO only assumed on one unit. (LOOP and both DGs fail – loss of all AC)
- Required by 10CFR50.63 (cope with SBO, core cooling and CTMT integrity)
- FSAR – 16 hour SBO coping time.
- Assumes one SBOG is started within 1 hour.
- Second SBOG is used if the first one fails or if MDAFW pump is required.
-
LOOP: energize NAN-S07 within 1 hour to maintain the SBOG batteries.
- Maintains SBOG availability for a SBO
- SBOGs operation coordinated through Unit 1
- SBOGs cannot supply U2/U3 simultaneously
- If a unit’s NBN-_X03 XFMR is faulted, SBOG cannot supply that unit_.
- LOOP: SBOG used to energize the SWYD loads within 2 hours
- Maintains PCB control power and PCB availability
SBOGs (2)
- Liquid fueled gas turbines
- 4.27 MW (Design Basis is 3698 KW)
- Max loading based on maintaining SBOG temp < 1330°F
- 14,951 rpm turbine speed. Reduction gears used.
- 1800 rpm generator speed
Gas turbine operations:
- what are the 3 main sub-components of SBOGs?
- what are the 3 main sub-components of SBOGs?
- Compressor blades…
- Air is forced into…
- Where is the Air/Fuel mixture ignited?…
- Turbine gases rapidly…
- … blades spin.
Gas turbine operations:
- Compressor
- Combustor
- Turbine
- Compressor has blades that turn like a fan to pull air into the gas turbine.
- Air is forced into the combustor, where fuel mixes with the compressed air.
- Air/fuel mixture is ignited in the combuster
- Burning gases rapidly expand out of combustor into the turbine. Gases transfer energy to the turbine blades.
- Causes the blades to spin.
Acceleration (…Startup Sequence…)
- At what % speed is the energy of the hot gases from the combustor enough to maintain turbine speed. “Self-Sustaining Speed.”?
- ?°F = what at the turbine 3rd stage?
- At what % speed do the Bleed Air Valve close, and the Variable Vane Controller actuates open?
Acceleration (…Startup Sequence…)
- 66% speed - energy of the hot gases from the combustor is enough to maintain turbine speed. “Self-Sustaining Speed.” Turbine starting system disengages. Pre/Post Lube Oil Pump stops. Atomizing air is now supplied from the compressor.
- 400°F (turbine 3rd stage) - ignition system switches off.
- 90% speed - Bleed Air Valve closes, Variable Vane Controller actuates open.
{[…Not highlighted in Welch’s Notes…]}
Engine support systems
- Explain…
Lube Oil System
- Explain…
{[…Not highlighted in Welch’s Notes…]}
Engine support systems
- 480Vac power normally fed from NHN-M56 (NAN-S06).
- If power lost, power is fed from a step down XMFR from the SBOG 13.8 kV bus and an automatic transfer switch.
Lube Oil System
- Two lube oil cooler packages. Cooled by electric fans.
- 24 Vdc pre/post lube pumps
- Engine driven MLO pump
- PCVs/TCVs/Oil reservoir
- Turbine Shutdowns: (Low oil level or pressure)
{[…Not highlighted in Welch’s Notes…]}
Battery Charger and Battery Rack Assembly (2 per generator & 1 for switchgear)
- Explain…
Engine Air System
- Explain…
{[…Not highlighted in Welch’s Notes…]}
Battery Charger and Battery Rack Assembly (2 per generator & 1 for switchgear)
- 24 Vdc for control voltage (Generator #1 NEN-H01A)
- 24 Vdc for diesel start (Generator #1 NEN-H02A)
- 125 Vdc for switchgear control power (NKN H22)
Engine Air System
- Pressurize oil seals.
- Cool turbine rotor disks and first stage nozzles.
- Supply Control Air for operation of the fuel control system.
- Assist in obtaining smooth engine operation by preventing surge conditions at critical speeds.
{[…Not highlighted in Welch’s Notes…]}
Start System
- Explain…
{[…Not highlighted in Welch’s Notes…]}
Start System
- Capable of a black start.
- Battery DC power source is independent from the unit’s PK and NK power.
- Diesel-hydraulic start system provide the rotational force start the SBOG up to 66% speed.
- At 66% speed, the turbine engine provides its own power to accelerate to 100% speed.
- Diesel engine supplies compressed air and hydraulic pressure to the turbine.
{[…Not highlighted in Welch’s Notes…]}
Fuel system
- Explain…
Combined Generator Control Module
- Explain…
{[…Not highlighted in Welch’s Notes…]}
Fuel system
- Controls the fuel pressure and regulates the fuel flow according to operating requirements
- Use fuel pumps (1 is shaft driven)
Combined Generator Control Module
- Controls Speed/load and Voltage/KVAR
Vibration Monitoring System
{[…Not highlighted in Welch’s Notes…]}
Turbotronic Control System (Controls the turbine functions, 24 Vdc power)
- Explain…
{[…Not highlighted in Welch’s Notes…]}
Turbotronic Control System (Controls the turbine functions, 24 Vdc power)
- Sequences operating systems during starting, running, and shutdown, to provide necessary protection during all phases of operations; and to monitor package system parameters during operation
- Power factor (pf) must be manually maintained (raise load, raise voltage / lower load, lower voltage)
{[…Not highlighted in Welch’s Notes…]}
Fire Detection and Suppression System
- Explain…
{[…Not highlighted in Welch’s Notes…]}
Fire Detection and Suppression System
- Uses light sensors or “Fire Eyes” to detect the presence of fire.
- Lock out before the SBOG enclosure doors are opened to prevent inadvertent CO2 discharge.
- Fire System Control is located on each SBOG control panel and consists of a Lockout switch.
- FP system lockout prevents actuation of the CO2.
- The fire eyes have protective covers that can be installed if the engine needs to run with the doors opened (one door at a time for vibe data and for < 10 minutes), but the thermal and hazardous gas level detectors will still force a shutdown if they are tripped by temperature or Lower Explosive Limit that exceeds the threshold. 10 min limit for open doors prevents high summer temp from causing SBOG shutdown.
- Alarm: FP system not in Auto or fire eyes are covered.
{[…Not highlighted in Welch’s Notes…Except Acceleration 66% & Self-Sustaining Speed]}
Start-up sequence
Time sensitive step (< 2 min):
- Explain…
Press “Start” button.
- Explain…
Diesel Starting Engine Start
- Explain…
Ignition
- Explain…
Acceleration
- Explain… (highlighted in Welch’s notes!!!)
Generation
- Explain…
{[…Not highlighted in Welch’s Notes…Except Acceleration 66% & Self-Sustaining Speed]}
Start-up sequence
Time sensitive step (< 2 min):
- Once the SBOG reaches “Ready to Load” a 2 minute timer starts on 24VDC battery charger failed alarm.
- If charger failed alarm not clear within 2 minutes, the SBOG will automatically shut down.
- AO has to energize NHN-M73 upon receiving the “Ready to Load” light. Has to close SBOG output breaker (energizing NAN-S07) and ensure ABT transfers.
- Also applies during testing. Will need to re-close the battery charger supply breakers within 2 minutes vice the SBOG output breaker.
Press “Start” button.
- Starts the Pre/Post Lube Oil Pump (runs for 30 seconds)
- Enclosure purge fan will run for two minutes if not in a SBO.
Diesel Starting Engine Start
- After 2 minute enclosure purge or 30 seconds pre-lube, the diesel starts.
- Diesel will pressurize the air assist tank to 120 psig.
- Diesel-driven hydraulic pump provides pressure to engine starting motor. Compressor and turbine begin to rotate.
Ignition
- Starting circuit opens Fuel Purge Valve (drains old fuel)
- Fuel Boost Pump starts
- 15% speed - Fuel Purge Valve closes.
- 21% speed - Fuel Control Valve sends fuel to the Igniter Torch and Fuel Injector Nozzles.
- Atomizing air mixed into the Fuel Injector Nozzles and the Ignition Circuit is energized. Lights the Igniter Torch.
- Open Bleed Air Valve enables compressed air to bypass the turbine to make starting easier and prevent turbine surge.
- Variable Vanes in the compressor are at minimum position to prevent compressor stall during the turbine acceleration.
- As the temperature of the air leaving the combustor begins to rise the turbine begins to take over the load of turning the shaft.
Acceleration
- 66% speed - energy of the hot gases from the combustor is enough to maintain turbine speed. “Self-Sustaining Speed.” Turbine starting system disengages. Pre/Post Lube Oil Pump stops. Atomizing air is now supplied from the compressor.
- 400°F (turbine 3rd stage) - ignition system switches off.
- 90% speed - Bleed Air Valve closes, Variable Vane Controller actuates open.
Generation
- 85% speed - voltage regulator flashes the generator field.
- 90% speed - Generator Voltage and Start Time are verified and the “Ready to Load” timer is activated.
- 10 seconds after the Turbine speed reaches 90% the “Ready to Load” lite comes on.
- 100% speed the Governor Control system assumes control of the turbine.
- Total time elapsed is ~ 1 min 35 seconds.
{[…Not highlighted in Welch’s Notes…]}
SBOG Shutdown Sequence:
- Explain…
{[…Not highlighted in Welch’s Notes…]}
SBOG Shutdown Sequence:
- < 300kW before shutting down the SBOG
- Reduce SBOG load (communicate with MCR)
- Open SBOG Output Breaker on NAN-S07
- Press “Stop” push button.
- Goes into a 3 minute cool down mode indicated by the “cool down” light on the SBOG Control Panel. During this time the turbine is running at 100% speed with no load.
- At the end of the cool down period the SBOG will begin to slow down. When it reaches 90% speed the SBOG “Running” light goes out.
- In an “Emergency,” SBOG can be stopped using the “Fast Stop” push button:
- Immediately closes the Fuel Cutoff valve and the trips open the SBOG Output Breaker.
- Cool down period is also eliminated and the SBOG slows to a stop.