.AR Elect. DG-EDGs Diesels (Welch's Highlighted Notes) Flashcards
1
Q
State the Diesel Generators Ratings…
A
Diesel Generators Ratings:
- 4.16 kV
- Rated speed and accept load within 10 seconds
- 5500 KW continuous output
- 6050 KW (110% rated load) for 2 hours out of 24 hours.
- 20 cylinder, V-type, turbocharged engine
- Operates at 600 rpm
- 6.55 gpm (fuel oil used at 100% load)
- Operation < 25% load (1375 kW) should be minimized to prevent carbon buildup.
2
Q
- State how is the EDG supported by the Essential Spray Pond System…
- Loss of SP?…
- If SP is Inoperable?…
A
Essential Spray Pond System
- Associated Spray Pond pump auto starts when the DG starts
- Cools jacket water, lube oil and intercooler HXs.
-
Loss of SP, DG must be locally stopped by AO:
- 15 minutes unloaded
- 2.6 minutes fully loaded
If SP is inoperable, declare associated DG inoperable (LCO 3.0.6 exception)