State the Diesel Generators Ratings…

A

Diesel Generators Ratings:

  • 4.16 kV
  • Rated speed and accept load within 10 seconds
  • 5500 KW continuous output
  • 6050 KW (110% rated load) for 2 hours out of 24 hours.
  • 20 cylinder, V-type, turbocharged engine
  • Operates at 600 rpm
  • 6.55 gpm (fuel oil used at 100% load)
  • Operation < 25% load (1375 kW) should be minimized to prevent carbon buildup.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • State how is the EDG supported by the Essential Spray Pond System
  • Loss of SP?…
  • If SP is Inoperable?…
A

Essential Spray Pond System

  • Associated Spray Pond pump auto starts when the DG starts
  • Cools jacket water, lube oil and intercooler HXs.
  • Loss of SP, DG must be locally stopped by AO:
    • 15 minutes unloaded
    • 2.6 minutes fully loaded

If SP is inoperable, declare associated DG inoperable (LCO 3.0.6 exception)