.AR Elect. PK PN NK NN (Welch's Highlighted Notes) Flashcards

1
Q

PK:

  • How many independent subsystems?
  • Normal Operating Voltage?
  • What is the required capacity/time and the minimum temperature required for PK? (on a loss of charger)…
A
  • Four independent subsystems (PKA, PKB, PKC and PKD).
    • Subsystem consists of battery, charger, control center and distribution panel
  • Normally operates at ~ 135 VDC.
    • Bus voltage limits are 129.0 - 139.8 VDC
    • Battery float voltage is normally 130.2 - 135.0 VDC
    • Equalizing mode max voltage 139.8 VDC
  • Capacity: supply required loads for 2 hours (loss of charger) at a minimum temperature of 60°F in the battery room.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

PK:

  • Battery rooms have what type of Q-Class of exhaust fans for Temp/H2 control?
    • What is its suction and discharge path to?
    • What ESFAS signal(s) start the Essential fans?
  • What normally cools DC Equipment Rooms?
  • Control Bldg Normal AHU normally takes suction from where?
  • What cools the DC Equipment and Battery rooms in a SIAS or LOP?
A

Control Building HVAC (Support System)

  • Battery rooms have normal and essential exhaust fans (Temp / H2 control).
    • Suction from battery room / discharge directly to atmosphere.
    • Essential fans start on SIAS/LOP
  • DC Equipment Rooms normally cooled by ESF Switchgear Room Normal AHU (WC).
  • Control Building Normal AHU normally takes suction on each DC equipment room.
  • SIAS or LOP: DC Equipment Room Essential AHUs (EC) cool DC Equipment and Battery rooms.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

PK:

Battery Chargers:

  • How many normal & backup chargers per train
  • list the Interlock(s)…What does it prevent?
  • PK chargers are powered from?…
  • Can the chargers be operated in parallel? why?
  • Are chargers Load Shed? If yes, how fast (seconds) do they reclose?
    • What happens to the MCC contactor supplying the charger? can it be operated locally?
A

Class 1E 125 VDC Battery Chargers

  • 1 normal charger per load center and 1 back-up charger per train.
  • Mechanical interlock prevents aligning back-up charger to both control centers
  • Powered from PHA/PHB
  • Chargers cannot be operated in parallel (may cause damage).
  • Chargers load shed by BOP-ESFAS, reclose in 5 seconds.
    • Opens MCC contactor supplying the charger, can be operated locally
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

[PK system Ground Detection & MCR Indications]:

Ground Detection:

  • Does PK alarm in MCR?
  • Color of light at control center? Resets locally?
  • Is PK grounded or ungrounded? Why?

MCR Indications:

  • List MCR PK meters…
  • The Battery Amps (gauge needle) goes To the right of zero… when it’s charging or discharging?
  • What do the volts indicate about the output breaker?
  • What are the 2 colors of the Back-up charger MCR indication lights? Which color shows which bus the spare charger is aligned to.
A

Ground Detection

  • MCR alarm.
  • White light lit at control center. Reset locally.
  • Ungrounded system (Increased reliability. Need negative and positive ground to degrade the system.)

MCR Indications

  • 125Vdc bus voltage
  • Battery Amps (To the right of zero when discharging)
  • Charger Amps/volts (volts will indicate if output bkr is tripped)
  • Back-up charger lights (Red/Green). Red light will show which bus the spare charger is aligned to.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

PK:

State the PK MCR Alarms and its SESS Alarms (if any)…

A

125V IE CC M41 CHGR A/AC PNL D21 TRBL Alarm (each board has this alarm)

  • Control center under voltage, ground or breaker trip
  • Battery Charger problems (over or under voltage, AC supply voltage low, charger failure or reverse current)
  • Distribution Panel overload

125V DC 1E CC M41 BAT BKR SESS Alarm (each board has this alarm)

  • WHITE section (SEIS) LIT if Breaker Not Closed or inoperable (No SEAS alarm)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

PK:

Transfer Switches (App. R)

  • What do they isolate for the Battery Chargers (Train A or B?) (Where is the switch located?)
  • What do they isolate for the Batteries (Train A or B?) (Where is the switch located?)
  • It also isolates the A Battery from which circuit breaker? (Where is the switch located?)
A

Transfer Switches (App. R)

  • Isolates load shedding and sequence permissive relays, B01 voltmeters and ammeters for B train Battery Chargers (B, D, BD) (Switch is located at the MCC that supplies the charger)
  • Isolates MCR breaker controls, voltmeters and ammeters for B train batteries (B, D). (Switch located at 125VDC Control Center)
  • Isolates A Battery from the MCR circuit breaker switch (Switch is located on control center PKA-M41)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

PK:

  • PK is control power to what equipment? ( and what happens if power is lost?…)
  • PK provides DG control power and field flashing…
    • What happens to DG on loss of power?
    • If DG was running prior to loss of power, what happens to the DG engine and the output breaker? why?
  • What happens to the Turbine Driven Aux Feedwater (TDAFW) MOVs and controls if PK is lost with AFA-P01 running?
  • PK chargers power (thru inverters) SI-SDC isolation valves… Can the charger alone power these valves?(SIC-UV-653 & SID-UV-654)
  • How does PK support the class inverters? If PK is lost, does the inverter Auto Transfer? (…where to?)
A

(PK) Supported Systems

  • Control power to class switchgear and load center breakers and relays (non-functional if power lost)
  • DG Control power and field flashing.
    • Loss of power: DG is not capable of starting.
    • If running prior to the loss, the engine would trip but the output breaker would remain closed (no control power).
  • TDAFW MOVs and controls
    • If DC power is lost with AFA-P01 running, it may trip on over speed.
  • SI: Supplies (thru inverters) SDC suction isolation valves.
    • Charger alone cannot provide sufficient power to operate SDC suction MOVs. Battery must be aligned (UV-653/654).
  • DC source to the class inverters. If lost, inverter auto transfers to the AC supply.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

(PK) LCO 3.8.4 DC Sources – Operating (Modes 1-4)

  • List the DC trains and its sub-channels…
    • What does each channel (normal or backup) include?
    • What makes a DC Bus operable?
  • If 1 Charger INOP…
  • LCO time in hours if 1 DC electrical subsystem INOP (reasons other than condition A)?
  • LCO time if both DC power systems INOP? (can it be entered voluntarily?)
  • SR 3.8.4.1: Terminal voltage ≥ ?
    • Based on what? Min float voltage per cell?
  • LCO 3.8.5 (shutdown) requires what type of source (DC or AC?) to support which LCO #? (Same actions as 3.8.2?)
A

(PK) LCO 3.8.4 DC Sources – Operating (Modes 1-4)

  • Train A and Train B DC electrical power subsystems
    • Train A (Channel A and C) / Train B (Channel B and D)
    • Each channel includes 125 Vdc bus, battery bank, and charger (normal or back-up)
    • Operable: all batteries and respective chargers operating and connected to the associated DC bus(es).
  • One Charger inoperable:
    • Restore terminal voltage within 2 hours
    • Verify float current ≤ 2 amps every 12 hours (battery is re-charged, battery declared inoperable if not met)
    • Restore the charger within 72 hours or RICT
  • 2 hours or RICT: One DC electrical power subsystem inoperable for reasons other than Condition A (one charger inoperable).
    • Example: two chargers inoperable on same train or battery inoperable
  • Both DC power subsystems inoperable: restore one within 1 hour OR RICT (cannot voluntarily enter)
  • SR 3.8.4.1: Terminal voltage ≥ 130.2 Vdc
    • Based on the nominal design voltage of the battery. Consistent with the minimum float voltage (2.17 Vdc per cell) times the number of connected cells or 130.2 V for a 60 cell battery at the battery terminals.
  • LCO 3.8.5 (shutdown) requires DC source to support LCO 3.8.10 (same actions as 3.8.2)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

(PK) ​LCO 3.8.6 Battery Parameters:

  • Battery limits to be Operable?
  • Float current is ≤ ? amps (…not required to be met if terminal voltage is low)
  • Cell float voltage is > ? Volts.
  • Electrolyte level ≥ ? mark on battery cell jar.
  • Pilot cell temperature is ≥ ?°F.
  • Battery capacity is ≥ ?% (test discharge)
  • Immediately declare Battery inoperable (& enter LCO 3.8.4 condition B):
    • Cell float voltage ≤ ? Volts and float current > ? amps.
    • Or if what conditions/parameters not met?
A

(PK) ​LCO 3.8.6 Battery Parameters:

  • Batteries shall be within limits when required to be operable.
  • Float current is ≤ 2 amps (not required to be met if terminal voltage is low)
  • Cell float voltage is > 2.07 V.
  • Electrolyte level ≥ level indication mark on battery cell jar.
  • Pilot cell temperature is ≥ 60°F.
  • Battery capacity is ≥ 80% (test discharge)
  • Immediately declare Battery inoperable (enter LCO 3.8.4 condition B):
    • Cell float voltage ≤ 2.07 V and float current > 2 amps.
    • Or other conditions not met (parameters not restored in time)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

(PK) ​​LCO 3.8.9 Distribution Systems – Operating (Modes 1-4):

  • List the trains that shall be operable…
  • Can a DC subsystem be considered OPERABLE if it’s energized (@ proper voltage) from its battery or charger?
  • How long to restore (time in hours)?
A

(PK) ​​LCO 3.8.9 Distribution Systems – Operating (Modes 1-4)

  • Train A and Train B AC, DC, and AC vital instrument bus electrical power distribution subsystems shall be operable
  • Operable DC electrical power distribution subsystems require the associated buses to be energized to their proper voltage from either the associated battery or charger.
  • All 125Vdc Control Centers and Distribution Panels are required.
  • Restore in 2 hours or RICT
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

(PN) Class 1E Inverters:

  • Includes which transfer switches?
  • List control centers?…
  • Bus voltage limits?…
  • Frequency range?…
A

(PN) Class 1E Inverters:

  • Includes both static and manual transfer switches
  • Inverters powered by associated 125 Vdc PK Control Center (PKA-M41/PKB-M42/PKC-M43/PKD-M44)
  • Converts (inverts) 125 Vdc to 120 Vac
  • Bus voltage limit: 118 - 126 Vac
  • Frequency: 59.5 - 60.5 Hz
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

(PN) Static Switch:

  • Electronic, solid state assembly.
  • On loss of normal power (inverter), does it auto transfer?….
  • Does it Auto transfer back?…
    • ​which 2 buttons pressed to transfer manually?…
    • Auto transfers to the voltage regulator:
      • ?…
      • ?…
      • ?…
  • Green light – means…?…
  • Amber light – means…?…
A

(PN) Static Switch:

  • Electronic, solid state assembly.
  • On loss of normal power (inverter), automatically transfers the distribution panel to the voltage regulator.
  • Does NOT transfer back automatically.
  • Distribution panel can be manually transferred by pushing one of the two pushbuttons:
    • INVERTER TO LOAD (Aligns to the inverter)
    • BYPASS SOURCE TO LOAD (Aligns to the voltage regulator)
  • Auto transfers to the voltage regulator:
    • Loss of the square wave to the harmonic filter.
    • Low inverter voltage to the static switch (~50% voltage)
    • Inverter output overload (120% inverter load ~200 Amps)
  • Green light – INVERTER SUPPLYING LOAD
  • Amber light – BYPASS SOURCE SUPPLYING LOAD
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

(PN) Voltage Regulator (480/120Vac regulating XFMRs):

  • Are they backup or normal?
  • Power: ? (MCCs…)
  • MCC contactor is load shed on what?… recloses?…
A

(PN) Voltage Regulator (480/120Vac regulating XFMRs):

  • Backup power supply for each channel
  • Power: PHA/PHB
  • MCC contactor is load shed on a LOP, contactor recloses 5 seconds after power restored
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

(PN) LCO 3.8.7 Inverters – Operating (Modes 1 – 4)

  • Train A and Train B inverters shall be operable in which modes?…
  • ?…
A

(PN) LCO 3.8.7 Inverters – Operating (Modes 1 – 4)

  • Train A and Train B inverters shall be operable in Modes 1-4
    • One inoperable - 7 days or RICT
    • If PN is de-energized, immediately enter LCO 3.8.9 (3.0.6 exception)
    • > 1 inverter inoperable – restore in 1 hour or RICT (cannot voluntarily enter)
  • Operable inverter: AC vital instrument bus to be powered by the inverter with output voltage and frequency within tolerances, and power input to the inverters from a 125 Vdc battery.
  • One inverter may be disconnected from its associated DC bus for ≤ 24 hours to perform an equalizing charge if:
    • Bus is energized from its Class 1E constant voltage source regulator; and
    • All other buses are energized from their associated operable inverters.
  • LCO 3.8.8 (shutdown) requires inverters to support LCO 3.8.10 (same actions as 3.8.2)
  • If inverter is inoperable (Cond A entered):
    • Do not perform planned maintenance on associated train DG
    • Do not perform planned maintenance on another RPS/ESFAS channel that puts that channel in trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

(PN) LCO 3.8.9 Distribution Systems – Operating (Modes 1 – 4):

  • ?…
A

(PN) LCO 3.8.9 Distribution Systems – Operating (Modes 1 – 4):

  • All four boards required.
  • Operable 120Vac board: energized to proper voltage from the inverter OR voltage regulator.
  • One 120V bus inoperable – Restore in 2 hours or RICT
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

(NK) NK Batteries:

  • Normal operating voltage?…
  • How long do they supply power?…
  • MCR indications for NK?…
A

(NK) NK Batteries:

  • Normal operating voltage _~ 135 Vd_c
  • Supply power for 2 hours following a loss of charger
  • Ratings: E - 2380 Amp-Hours / F - 3460 Amp-Hours
  • Battery breakers have MCR and local controls / indications
17
Q

(NK) NK Battery Chargers (E, E-1, EF, F, G):

  • Interlocks?…
  • Preferred method to swap chargers?… If chargers are having problems, then use which method?…
  • ?…
A

(NK) NK Battery Chargers (E, E-1, EF, F, G):

  • Backup charger (EF) output breakers have a mechanical interlock
  • EF Charger output breakers have MCR lights
  • Preferred method for swapping chargers is to place them in parallel before removing one. In the case where the in-service charger is having problems the preferred method is to remove the in-service charger first and then place the new charger in service.
  • Battery breakers must be closed prior to swapping chargers, reduces voltage transient.
18
Q

(NK) Control Centers (NKN-M45, NKN-M46) (& Ground Detection):

  • Normal bus voltage: #? Vdc
  • Bus voltage limit (range) ? Vdc
  • Motor and feeder breakers:
    • ?…

Ground Detection

  • Soft ground – MRC Alarms?
  • Hard ground – MCR Alarms?
  • How to reset ground relay?
A

(NK) Control Centers (NKN-M45, NKN-M46):

  • Normal bus voltage: 130 – 135 Vdc
  • Bus voltage limit 105 - 139.8 Vdc
  • Motor and feeder breakers:
    • Manually operated
    • Inverse time thermal overload protection (higher the current the shorter the time delay)
    • Instantaneous magnetic short-circuit protection

Ground Detection

  • Soft ground – NO MCR alarm. Yellow light on the ground detection assembly and white light at the Control Center.
  • Hard ground – MCR alarm. Yellow light on the ground detection assembly and a white light at the Control Center.
  • Ground relay must be RESET locally. RESET pushbutton is provided that is used to reset this relay when the condition clears.
  • Ground relay TEST push button on NKN-M45. NOT provided on NKN-M46.
19
Q

(NK) NK Panels, Locations, Loads:

  • Panel
    • (Location?)
    • Loads?
  • D41
    • ?
  • D42
    • ?
  • D43
    • ?
  • D44
    • ?
  • D45
    • ?
  • D19
    • ?
A

(NK) NK Panels, Locations, Loads:

  • Panel
    • (Location)
    • Loads
  • D41
    • (Turb Bldg 100’)
    • Switchgear control power
    • Main Generator auxiliaries
    • Turbine Building HVAC control
  • D42
    • (Aux Bldg 100’)
    • Switchgear control power
    • Radwaste annunciators
    • Motor Operated Disconnects
    • Plant annunciators
  • D43
    • (Turb Bldg 100’)
    • Oscillograph
    • Turbine Protection
    • Transformer annunciators
    • Plant annunciators
  • D44
    • (In NKN-M46)
    • RCP Breaker control
  • D45
    • (In SSR Room)
    • SSO Cabinet
  • D19
    • (Chlorinator Building)
    • Control Power to Cooling Tower area load centers
20
Q

(NN) Ground Detection (& Alarms):

  • D11 and D12 are ungrounded or grounded?…

120VAC PNL D11/D12/D15/D16 TRBL alarm

  • ?

Ground detection on NNN-D15/D16?

A

(NN) Ground Detection:

  • D11 and D12 are ungrounded and contain a ground fault detection system
    • Ground fault relays actuates a local RED light and MCR alarm.
    • Reset push button on the distribution panel.
    • RED light will stay illuminated until the ground is cleared and reset button pressed.
  • Powered from non-class 125Vdc (NKN-D42)

120VAC PNL D11/D12/D15/D16 TRBL alarm

  • Ground (NNN-D11 and D12 ONLY)
  • Undervoltage (100 Vac)
  • Breaker overload trip (main feed or load breakers)

No ground detection on NNN-D15/D16

21
Q

(NN) Static Transfer Switch:

  • Auto transfers to emergency at what voltage drop level?…
  • Auto transfers to normal if emergency source is?…
  • Explain Manual Bypass Switch?…
  • Preferred transfer method?…
A

(NN) Static Transfer Switch:

  • < 90 Vac: Auto transfers to emergency
  • Auto transfers to normal if emergency source is lost and normal is available.
  • Manual transfer back to normal.
  • Break before make transfer (~ 4 cycles).
  • Can be bypassed with a Manual Bypass Switch
    • Break before make
    • Requires SM permission to operate
    • Used to remove the static XFR switch from service
    • Normally in AUTO
  • Transfer to Emergency pushbutton is the preferred transfer method. (manually shifts the static XFR switch)
22
Q

(NN) Panel, Location, Normal Power Supply, Emergency Power Supply:

Panel

  1. (Location)
  2. Normal power supply
  3. Emergency power supply

D11

  1. ?

D12

  1. ?

D15

  1. ?

D16

  1. ?
A

(NN) Panel, Location, Normal Power Supply, Emergency Power Supply:

Panel

  1. (Location)
  2. Normal power supply
  3. Emergency power supply

D11

  1. (Cont Bldg 120’)
  2. NHN
  3. PHA-M31

D12

  1. (Cont Bldg 120’)
  2. NHN
  3. PHB-M32

D15

  1. (Turb Bldg 100’)
  2. NHN
  3. NHN-M19 (load shed)

D16

  1. (Aux Bldg 120’)
  2. NHN
  3. NHN-M20 (load shed, U1/U2 ONLY)
  • [PHB-M38 (U3 ONLY)]
23
Q

Purpose / design:

  • ?…

Voltage Regulators (VRs)

  • ?…
A

Purpose / design:

  • 120 Vac, single phase, 60 Hz regulated/filtered Non-essential reactor/auxiliary control/instrumentation (ungrounded supply) [D11/D12]
  • BOP loads (grounded supply) [D15/D16]

Voltage Regulators (VRs)

  • Single phase regulator XFMRs (480 to 120 Vac)
  • Produces regulated / filtered 120Vac
  • NNN-D15/D16 VRs are grounded