WG/WL Flashcards
1
Q
State alarm setpoint to WG/VG header
A
9#
2
Q
State Setpoint for VG-V-50 auto opening
A
12#
3
Q
State setpoint for WG-V-82/83 (relief valves)
A
15#
4
Q
State VG-V-57 interlock
A
If either PAH-FN-8A/B are not running then VG-V-57 shuts
5
Q
State the unmonitored release paths
A
WG-V-129 (Hydrogen surge tank relief
VG-V-82
VG-V-83
WAH-FN-72
6
Q
State interlock for WG-V-1602
A
IF RM-6504 goes into alarm then WG-V-1602 will auto close
7
Q
State interlock for RM-6509
A
Auto closures WL-FCV-1458-1, or 1458-2 on Hi Rad signal.
8
Q
State flow rates for WL-FCV-1458-1/2
A
WL-FCV-1458-1: 20-150GPM
WL-FCV-1459-2: 0-20 GPM
9
Q
State interlocks for WL-FCV-1458-1/2
A
Auto close if:
- High rad from RM-6509
- Other FCV not full closed
- Running discharge pump trips